Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25)

Original title Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), Version 1.0.0 (14 July 2026)

Open Compute Project Foundation · Keegan Yaroch (Dow, editor), Gerald Singer (PFX Group) et al.

OCP PG 25 v1.0.0 (July 2026) defines purity, impurity, corrosion and filtration limits for a ready-to-use 25-28% propylene glycol, silicate-free, dyed coolant for cold plate liquid cooling.

On this page

Overview

The Open Compute Project (OCP) PG 25 Base Specification defines minimum quality and documentation requirements for single-phase propylene glycol based cold plate fluids used in technology cooling systems (TCS). The editor is Keegan Yaroch of Dow; contributors represent PFX Group, Castrol, Indorama Ventures and Third Coast Chemicals. The document is version 1.0.0 dated 14 July 2026 and uses OCP modular specification template v1.6.0.

Composition requirements: propylene glycol of at least 99.5% purity (USP/EP grade), 25-28% glycol by weight (about 24.5-27.5% by volume), corrosion inhibitors compatible with common metallurgy and a dye additive for leak detection and fluid identification. Silicate-based additives are prohibited. The fluid is supplied ready to use, pH must be stable between 7.5 and 10.5 in final form, the manufacturer must show consistent composition across regions and batches and must filter to 50 microns or finer before transfer to containers.

Target limits for blending water (Table 1): chloride <10 ppm, sulfate <10 ppm, calcium <2 ppm, magnesium <2 ppm, total hardness <15 ppm (CaCO3), iron <2 ppm and electrical conductivity <25 µS/cm (20°C). Final fluid impurity limits (Table 2): copper, iron and aluminium <2 ppm, chloride <5 ppm, sulfate <10 ppm, calcium <5 ppm, magnesium <10 ppm and silicon <10 ppm.

Performance tests are corrosion by a modified ASTM D8040 (Table 3: copper and brass 5 mg and 0.2 mpy, 304/304L and 316/316L stainless steel 2 mg and 0.1 mpy) and thermal stability by a modified ASTM D7437: 98.5 mL of fluid is blended with 1.5 mL of hard water and aged at 90°C for two weeks, and precipitate must stay below 0.25 mL. The document says this is a screening-level indicator and does not by itself ensure long-term reliability. Transportation, storage, labelling, certificate of analysis (COA), technical and safety data sheets, traceability, analytical record retention (at least three years), remediation chemicals and technical support are also specified.

Key points

  1. Propylene glycol purity is at least 99.5% (USP/EP grade); source and purity must be documented.
  2. Blend is 25-28% propylene glycol by weight (about 24.5-27.5% by volume); dye additive required, silicate additives prohibited.
  3. Ready-to-use pH must be stable between 7.5 and 10.5.
  4. Blending water: chloride <10 ppm, sulfate <10 ppm, Ca <2 ppm, Mg <2 ppm, hardness <15 ppm, Fe <2 ppm, conductivity <25 µS/cm (20°C).
  5. Fluid impurity limits: Cu, Fe, Al <2 ppm; chloride <5 ppm; sulfate <10 ppm; Ca <5 ppm; Mg <10 ppm; Si <10 ppm.
  6. Corrosion limits: copper and brass 5 mg (0.2 mpy), stainless steel 304/304L and 316/316L 2 mg (0.1 mpy).
  7. Thermal stability: precipitate below 0.25 mL after two weeks at 90°C (98.5 mL fluid + 1.5 mL hard water).
  8. Final filtration at 50 microns or finer; particle distribution data may be required above 25 micron filtration.
  9. Analytical records are kept at least three years.

Using it in design

  • Specify the cold plate loop fluid to the PG25 specification; request glycol purity, dye and inhibitor information, pH and impurity results in the product TDS and COA.
  • Confirm that fill and make-up water meets the conductivity (<25 µS/cm) and hardness (<15 ppm) limits.
  • Check loop materials (copper, brass, 304/316 stainless) against the specification coupon limits; do not accept silicate products.
  • Write glycol concentration, inhibitor level and pH monitoring intervals and remediation chemical supply into the commissioning and operations plan.
  • For globally distributed projects add filter fineness (50 microns or finer) and regional product consistency to the supplier contract.

Who should read it

Data-centre engineers and fluid suppliers selecting and specifying coolant for direct-to-chip cooling loops.

Document contents

  1. License
  2. Compliance with OCP Tenets
  3. Scope
  4. Base Specification Overview
  5. Product Composition Requirements
  6. Performance Requirements
  7. Transportation and Storage Requirements
  8. Documentation Requirements
  9. Product Maintenance and Support
  10. Compliance
  11. Referenced Methods
  12. References

Related standards

  • OCP Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids
  • ASTM D1287
  • ASTM D5827
  • ASTM D6130

Publication details

Authors
Keegan Yaroch (Dow, editor); Gerald Singer (PFX Group); Tom Corrigan (PFX Group); Florian Rueping (Castrol); David Miller (Faradaic Enterprises)
Publisher
Open Compute Project Foundation
Year
2026
Document number
Version 1.0.0
Document language
English
Source type
Industry body
Access
Free to read
Licence
OWFa 0.9: Open Compute open specification licence; redistribution permitted
Original licence note

Section 1.1: contributions under Modified OWFa 0.9; usage under Modified OWFa 0.9 FSA (as of 16 Oct 2024). Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Keegan Yaroch (Dow, editor); Gerald Singer (PFX Group); Tom Corrigan (PFX Group); Florian Rueping (Castrol); David Miller (Faradaic Enterprises) (2026). Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), Version 1.0.0 (14 July 2026). Open Compute Project Foundation. Version 1.0.0. https://www.opencompute.org/documents/ocp-base-specification-pg25-v1-0-0-final-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.