Cooling Environments - Cold Plate: Rope Leak Sensor Base Specification
Original title Rope Leak Sensor Base Specification, Revision 1.0.0 (OCP Cooling Environments - Cold Plate)
Open Compute Project Foundation · Berhanu Wondimu, Zhikui Ren et al.
OCP Rope Leak Sensor Rev 1.0.0 (Feb 2026) defines a 4-pin, 3.3-12 Vdc, tach-output leak sensor interface and alarm signal logic for direct-to-chip servers using water-based coolant.
On this page
Overview
The Rope Leak Sensor Base Specification Revision 1.0.0, authored by Intel with contributors including CoolIT, Envicool, PermAlert and Tatsuta Electric, is effective from 2 February 2026. Its scope is a leak sensor rope for single-phase direct-to-chip (DTC) liquid cooled IT equipment using water-based coolant (water or propylene glycol); use may extend to products such as CDUs, chillers and rack manifolds. The target system is a 1U server node because of space limits.
The sensor has three parts: the rope, which changes electrical state (resistance, capacitance) on contact with liquid, a power cable and an electrical circuit that turns the state change into a signal the data acquisition system recognises (such as tach/frequency output). The rope must be flexible enough to route along coolant tubes and cold plate interfaces and be placed below the tubes and fittings; absorbent tape improves leak capture.
Electrical requirements: 4-pin wire connector, input supply 3.3-12 Vdc (±10% of rated voltage), open-drain or open-collector tach output; an LED status indicator is recommended. Environmental: operating temperature 0-85°C, non-operating (shipping) -40-85°C, relative humidity 0-95%. Signal (Table 5): pin 3 gives a frequency (for example 50-100 Hz) in normal state, low on leak and high on sensor fault (open circuit); pin 4 is low when the power cable is present and high when absent.
The sensor gives a discrete signal regardless of leak volume. The mitigation plan depends on the application: the board management controller (BMC) or CPLD runs plans such as alarm, notification and IT shutdown, and some applications use a timer to separate false alarm from real leak. Rope sensors are reusable after completely drying; if not dry the IT may not restart. The specification also covers false alarm reduction techniques and material and regulatory certification (UL, CE, RoHS, REACH). Physical dimensions such as rope diameter and length are left to the vendor.
Key points
- Rev 1.0.0, 2 February 2026; authors Intel; contributors CoolIT, Envicool, PermAlert, Tatsuta and others.
- Scope: single-phase DTC liquid cooled IT with water-based coolant; target 1U server node.
- Interface: 4-pin wire connector; input 3.3-12 Vdc (±10%).
- Output signal: tach (open drain or open collector).
- Operating temperature 0-85°C; non-operating -40-85°C; relative humidity 0-95%.
- Normal state gives a frequency (for example 50-100 Hz), leak gives low, open-circuit fault gives high.
- Pin 4: low when the power cable is present, high when absent.
- The sensor gives a discrete (leak or no leak) signal regardless of volume.
- The sensor is reusable after completely drying.
Using it in design
- Reserve a dedicated 4-pin header on the server board for the leak sensor and avoid confusion with CPU fan headers.
- Place the rope sensor below coolant tubes and fittings and use absorbent tape to improve capture.
- In BMC or CPLD firmware handle leak (low), open circuit (high) and cable absence as separate alarms; define the mitigation plan (notification, IT shutdown, cutting CDU or manifold flow) in advance.
- Where false alarms are a risk, define timer logic and add sensor drying time to the maintenance procedure.
- Select sensor supply voltage (3.3 Vdc standby, 12 Vdc normal) to match the board standby and normal modes.
Who should read it
Hardware and data-centre engineers designing leak detection for liquid cooled servers, CDUs and rack manifolds.
Document contents
- License
- Compliance with OCP Tenets
- Change Log
- Scope
- Overview
- Regulatory Requirements
- Physical Specifications
- Electrical Requirements
- Environmental Requirements
- Interface Requirements
- Onboard Power Specification
- Material of Construction
- Firmware Configuration
- Leak Mitigation/Hardware Management
- False Alarm Reduction Techniques
- Glossary
- References
Related standards
- OCP Leak Detection and Intervention white paper
- OCP Cold Plate Cooling Loop Requirements
Publication details
- Authors
- Berhanu Wondimu; Zhikui Ren; Yuehong Fan; David Zhou (Intel Corporation)
- Publisher
- Open Compute Project Foundation
- Year
- 2026
- Document number
- Rev 1.0.0
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- OWFa 1.0: Open Compute open specification licence; redistribution permitted
Original licence note
Section 1: contributions under OWF CLA 1.0; usage governed by OWFa 1.0 Specification License. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Berhanu Wondimu; Zhikui Ren; Yuehong Fan; David Zhou (Intel Corporation) (2026). Rope Leak Sensor Base Specification, Revision 1.0.0 (OCP Cooling Environments - Cold Plate). Open Compute Project Foundation. Rev 1.0.0. https://www.opencompute.org/documents/rope-leak-sensor-base-specification-r1-0-0-final-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.