Immersion Server Demonstrated Reliability at Datacenter Scale Deployment (OCP EMEA Summit 2025)
Open Compute Project Foundation · Austin Hipes
A field report presented at the OCP EMEA Summit 2025 tracks the reliability of about 3,600 single-phase immersion-cooled servers in a tier-1 data centre in Asia-Pacific from 2023 to early 2025.
On this page
Overview
The deck was presented by Austin Hipes in the Immersion Cooling track of the OCP EMEA Summit 2025 in Dublin. It reports the field reliability of about 3,600 single-phase immersion-cooled Xeon servers in a tier-1 data centre in Asia-Pacific, tracked quarterly from 2023 to early 2025. The deployment consists of 3,590 servers: 2,932 2nd-gen and 658 3rd-gen Xeon. They sit in single-phase immersion tanks with PAO4 dielectric, run 24x7 and were deployed between 2H 2022 and 2H 2023. The facility hosts air-cooled, direct-to-chip and immersion servers side by side.
Failures are broken down by component, with failures caused by the air-to-immersion conversion and by cable choice separated out. All reported failures number 202 on 2,932 2nd-gen servers (about 0.9% average per quarter) and 76 on 658 3rd-gen servers (about 1.9%). Excluding conversion-related and DAC cable failures leaves 133 failures (0.6%) for 2nd gen, of which memory is 36% and HDD 23%.
Downtime is converted into availability: fleet uptime is above 99.999%, with about 443 million power-on hours and 1,112 h total downtime. Memory and drives dominate failures. Limit: it covers one facility and one hardware family, yet it is one of the few published fleet-scale reliability datasets for immersion.
Key points
- 3,590 servers (2,932 2nd-gen and 658 3rd-gen Xeon) in single-phase immersion tanks with PAO4 dielectric, 24x7 duty, deployed 2H 2022 to 2H 2023.
- All reported failures: 202 on 2,932 2nd-gen servers (about 0.9% average per quarter) and 76 on 658 3rd-gen servers (about 1.9%).
- Excluding conversion-related and DAC cable failures: 133 failures (0.6%) for 2nd gen; memory 36% and HDD 23%.
- Fleet uptime above 99.999%: about 443 million power-on hours with 1,112 h total downtime.
- The facility hosts air-cooled, direct-to-chip and immersion servers side by side.
Using it in design
- Assess immersion cooling’s availability impact using component-level field AFR data for tanks and servers.
- Flag conversion of air-cooled servers (cables, PSU firmware) as a reliability risk in design notes.
- Include memory and drives in the spares plan as the dominant failure sources in immersion fleets.
- Treat the results as single-facility data; do not generalise directly to other fluids or hardware.
Who should read it
Designers evaluating immersion cooling, and operations and reliability engineers.
Related standards
- OCP Immersion Requirements
Publication details
- Authors
- Austin Hipes
- Publisher
- Open Compute Project Foundation
- Year
- 2025
- Document number
- OCP EMEA Summit 2025, Immersion Cooling track
- Event
- OCP EMEA Summit 2025, Dublin
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Austin Hipes (2025). Immersion Server Demonstrated Reliability at Datacenter Scale Deployment (OCP EMEA Summit 2025). Open Compute Project Foundation. OCP EMEA Summit 2025, Immersion Cooling track. OCP EMEA Summit 2025, Dublin. https://drive.google.com/file/d/168h6CsA4weoNITyBx9lMdPiypScZLv8L/view
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.