A study on the compatibility and service life of aluminium capacitors and synthetic coolants
npj Materials Degradation / Springer Nature · Ziheng Zhao, Heqian Wang et al.
An npj Materials Degradation paper that ages conductive polymer capacitors in synthetic oil at 70, 80 and 100 °C and predicts structural failure after about 492 days at 50 °C.
On this page
Overview
The paper examines how surface-mount aluminium electrolytic capacitors behave in immersion cooling fluids, a combination the authors say is widely used in data centres yet little studied. Conductive polymer capacitors are put through accelerated ageing in synthetic oil at 70 °C, 80 °C and 100 °C. The work comes from the University of Science and Technology Beijing together with ZTE.
The main finding is that the dominant failure mode is swelling of the butyl rubber seal, not electrical drift. Swelling deforms the part so that it can no longer be assembled onto a circuit board. The authors attribute this to coolant molecules infiltrating the rubber matrix, extending polymer chains and lowering thermal stability. At the same time the PEDOT conductive polymer de-dopes, which raises equivalent series resistance (ESR).
Using an Arrhenius model, swelling-induced failure has an activation energy of 43.7 kJ/mol and a predicted time to structural failure of about 492 days at 50 °C. The result applies to the tested capacitor and coolant pair. The paper offers a physicochemical framework for component reliability design in immersion-cooled systems.
Key points
- Ageing ran at 70, 80 and 100 °C in synthetic oil on conductive polymer surface-mount aluminium capacitors.
- The dominant failure mode is butyl rubber swelling; the structural deformation prevents circuit assembly.
- Electrical drift is not the primary failure; PEDOT de-doping raises ESR.
- Activation energy for swelling-induced failure is 43.7 kJ/mol.
- The Arrhenius model predicts structural failure after about 492 days at 50 °C.
- The life estimate is extrapolated from accelerated tests, not from a multi-year operating trial.
Using it in design
- Request coolant compatibility data from the manufacturer for capacitor seals and rubber parts on immersion-cooled boards.
- Apply Arrhenius extrapolation of service life only to the tested material and coolant pair.
- Add rubber-swelling tendency, ESR and capacitance monitoring to coolant acceptance testing.
- When setting fluid temperature, account for failure time shortening exponentially with temperature.
Who should read it
Designers selecting servers and components for immersion cooling, and reliability engineers assessing coolant compatibility.
Publication details
- Authors
- Ziheng Zhao; Heqian Wang; Jinqiao Zheng; Cong Shao; Hao Yu; Hao Miao; Kui Xiao
- Publisher
- npj Materials Degradation / Springer Nature
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher Rights and permissions specifies CC BY-NC-ND 4.0. Commercial full-text redistribution is not authorized by that license. HTML abstract and rights inspected; PDF request returned HTML.
Citation
Ziheng Zhao; Heqian Wang; Jinqiao Zheng; Cong Shao; Hao Yu; Hao Miao; Kui Xiao (2026). A study on the compatibility and service life of aluminium capacitors and synthetic coolants. npj Materials Degradation / Springer Nature. https://doi.org/10.1038/s41529-026-00898-2
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.