White Paper: Pumped 2P Refrigerant-Based Direct Liquid Cooling (DLC) Technology for Next Generation AI Clusters with High TDP Accelerators, v1.0 (14 February 2025)
Open Compute Project Foundation · Devdatta Kulkarni (Intel), Russ Tipton (Vertiv) et al.
An OCP white paper that explains how pumped two-phase direct-to-chip cooling works, covering cold-plate physics, CDU types, manifolds, couplings and refrigerant choice. It is one of the few open references that sizes two-phase CDU options for facility planning.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
The paper opens with the context that a single accelerator chip now reaches 1000 W TDP and that TDP grew 2.5 times between 2020 and 2024. It stresses that a rack can hold up to 72 accelerators, that HBM stacks are a thermal bottleneck, and that component temperature limits stay the same for long-term reliability. The solution, developed with Intel, Vertiv, Honeywell and Parker, uses the medium-pressure fluid R-515B as its example; the authors state that no particular vendor is being favoured.
The operating principle is as follows: refrigerant moves from a reservoir in the CDU by mechanical pump through row and rack manifolds and quick-disconnect couplings into cold plates, where part of the liquid evaporates, giving iso-thermal heat transfer and a very high wall heat-transfer coefficient. The liquid-vapour mixture condenses in the CDU heat exchanger and returns to the reservoir. Exit vapour quality must stay below 100% to avoid dry-out; in series-connected plates the downstream plate has a lower saturation temperature and higher vapour quality.
The most useful part for sizing is the four CDU types: in-row refrigerant-to-liquid (about 400 kW at 45 degC facility water), in-row refrigerant-to-air (about 180 kW at 35 degC air), in-rack refrigerant-to-liquid (about 100 kW) and in-rack refrigerant-to-air (about 40 kW). In one measured comparison, the single-phase PG25 plate's performance depended on flow rate, while the two-phase plate's performance was independent of refrigerant flow as long as there was no dry-out.
The fluid section compares medium-pressure options (R-134a, R-513A, R-515B, R-1234ze(E), R-1234yf) and low-pressure options (Novec 7000, R-245fa, R-1233zd(E)) on GWP, safety class, normal boiling point and pressure at 50 degC. The paper lists advantages (no corrosion or biological growth, dielectric fluid, warmer facility water, waste-heat recovery) and also discusses drawbacks: system cost is slightly above single-phase today, PFAS regulation could affect fluorinated fluids, and fluid safety and leak management require compliance with the relevant codes and standards. The paper is licensed CC BY-SA 4.0.
Key points
- Accelerator TDP grew 2.5 times between 2020 and 2024; chips reach 1000 W today and a rack holds up to 72 accelerators.
- Four CDU types: in-row refrigerant-to-liquid about 400 kW (45 degC facility water), in-row refrigerant-to-air about 180 kW (35 degC air), in-rack refrigerant-to-liquid about 100 kW, in-rack refrigerant-to-air about 40 kW.
- Mass flow must keep cold-plate exit vapour quality below 100%, otherwise dry-out occurs.
- In series-connected cold plates, the downstream plate runs at lower saturation temperature and higher vapour quality.
- In a same-plate comparison of PG25 (single phase) and R-515B (two phase), the two-phase plate's thermal performance was largely independent of refrigerant flow rate.
- Demonstrations are cited as supporting processors above 2 kW and servers above 10 kW in 1 OU within typical IT and rack volumes.
- R-515B: GWP 293, safety class A1, normal boiling point -19 degC, 995 kPa at 50 degC; R-1233zd(E): GWP 1, A1, boiling point 18.2 degC, 293 kPa at 50 degC.
- Couplings are described with seals compatible with R134a, R454B, R-515B, R1233zd, R1234yf and R1234ze.
- It can be applied in existing air-cooled sites through air-assisted liquid cooling (a side-car configuration).
Using it in design
- In facility planning, choose between in-row (400 kW or 180 kW) and in-rack (100 kW or 40 kW) CDU types according to rack density, taking 45 degC facility water for the in-row liquid type and 35 degC air for the air type as input conditions.
- Evaluate the option of warmer facility water for chiller load, dry coolers and waste-heat recovery scenarios; the paper presents this benefit as climate dependent.
- When choosing cold-plate and series arrangement, make the exit vapour quality limit (below 100%) and a dry-out margin design criteria.
- In fluid selection, weigh GWP, safety class and PFAS regulatory risk together; for flammable fluids plan additional safety measures and a leak-check frequency.
- Connect leak detection to the BMS and define a filter-drier service plan; add procedural steps against moisture ingress at quick-disconnect points.
Who should read it
Mechanical designers evaluating direct-to-chip cooling for high-density AI halls, CDU and cold-plate manufacturers and operators.
Document contents
- Introduction
- Compliance with Open Compute Project Tenets
- Pumped Two-Phase (P2P) Liquid Cooling Solutions (what it is and its advantages, heat path from chip to outdoor rejection, cold plates, CDU, quick-disconnect couplings, refrigerant-grade hose, charge management, flow distribution, pressure regulation, filtration, secondary fluid network)
- Coolants/Refrigerants for Pumped Two-Phase Cooling (medium-pressure and low-pressure)
- Application and Installation Support
- Conclusions
- Glossary and references
Related standards
- OCP Guidelines for Using Dielectric Heat Transfer Fluids in Two-Phase Cold Plate-Based Liquid-Cooled Racks
Read the document
ocp-pumped-2p-refrigerant-dlc-whitepaper-2025.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Devdatta Kulkarni (Intel); Russ Tipton (Vertiv); Elvis Leka (Parker Hannifin Sporlan); Joe Bankston (Parker Hannifin); Qingyang Wang (Accelsius); Jeff King (Intel)
- Publisher
- Open Compute Project Foundation
- Year
- 2025
- Document number
- Version 1.0
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Devdatta Kulkarni (Intel); Russ Tipton (Vertiv); Elvis Leka (Parker Hannifin Sporlan); Joe Bankston (Parker Hannifin); Qingyang Wang (Accelsius); Jeff King (Intel) (2025). White Paper: Pumped 2P Refrigerant-Based Direct Liquid Cooling (DLC) Technology for Next Generation AI Clusters with High TDP Accelerators, v1.0 (14 February 2025). Open Compute Project Foundation. Version 1.0. https://www.opencompute.org/documents/2p-refrigerant-based-dlc-wp-v1-pdf-1/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.