White paperPDF2025

White Paper: Pumped 2P Refrigerant-Based Direct Liquid Cooling (DLC) Technology for Next Generation AI Clusters with High TDP Accelerators, v1.0 (14 February 2025)

Open Compute Project Foundation · Devdatta Kulkarni (Intel), Russ Tipton (Vertiv) et al.

An OCP white paper that explains how pumped two-phase direct-to-chip cooling works, covering cold-plate physics, CDU types, manifolds, couplings and refrigerant choice. It is one of the few open references that sizes two-phase CDU options for facility planning.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The paper opens with the context that a single accelerator chip now reaches 1000 W TDP and that TDP grew 2.5 times between 2020 and 2024. It stresses that a rack can hold up to 72 accelerators, that HBM stacks are a thermal bottleneck, and that component temperature limits stay the same for long-term reliability. The solution, developed with Intel, Vertiv, Honeywell and Parker, uses the medium-pressure fluid R-515B as its example; the authors state that no particular vendor is being favoured.

The operating principle is as follows: refrigerant moves from a reservoir in the CDU by mechanical pump through row and rack manifolds and quick-disconnect couplings into cold plates, where part of the liquid evaporates, giving iso-thermal heat transfer and a very high wall heat-transfer coefficient. The liquid-vapour mixture condenses in the CDU heat exchanger and returns to the reservoir. Exit vapour quality must stay below 100% to avoid dry-out; in series-connected plates the downstream plate has a lower saturation temperature and higher vapour quality.

The most useful part for sizing is the four CDU types: in-row refrigerant-to-liquid (about 400 kW at 45 degC facility water), in-row refrigerant-to-air (about 180 kW at 35 degC air), in-rack refrigerant-to-liquid (about 100 kW) and in-rack refrigerant-to-air (about 40 kW). In one measured comparison, the single-phase PG25 plate's performance depended on flow rate, while the two-phase plate's performance was independent of refrigerant flow as long as there was no dry-out.

The fluid section compares medium-pressure options (R-134a, R-513A, R-515B, R-1234ze(E), R-1234yf) and low-pressure options (Novec 7000, R-245fa, R-1233zd(E)) on GWP, safety class, normal boiling point and pressure at 50 degC. The paper lists advantages (no corrosion or biological growth, dielectric fluid, warmer facility water, waste-heat recovery) and also discusses drawbacks: system cost is slightly above single-phase today, PFAS regulation could affect fluorinated fluids, and fluid safety and leak management require compliance with the relevant codes and standards. The paper is licensed CC BY-SA 4.0.

Key points

  1. Accelerator TDP grew 2.5 times between 2020 and 2024; chips reach 1000 W today and a rack holds up to 72 accelerators.
  2. Four CDU types: in-row refrigerant-to-liquid about 400 kW (45 degC facility water), in-row refrigerant-to-air about 180 kW (35 degC air), in-rack refrigerant-to-liquid about 100 kW, in-rack refrigerant-to-air about 40 kW.
  3. Mass flow must keep cold-plate exit vapour quality below 100%, otherwise dry-out occurs.
  4. In series-connected cold plates, the downstream plate runs at lower saturation temperature and higher vapour quality.
  5. In a same-plate comparison of PG25 (single phase) and R-515B (two phase), the two-phase plate's thermal performance was largely independent of refrigerant flow rate.
  6. Demonstrations are cited as supporting processors above 2 kW and servers above 10 kW in 1 OU within typical IT and rack volumes.
  7. R-515B: GWP 293, safety class A1, normal boiling point -19 degC, 995 kPa at 50 degC; R-1233zd(E): GWP 1, A1, boiling point 18.2 degC, 293 kPa at 50 degC.
  8. Couplings are described with seals compatible with R134a, R454B, R-515B, R1233zd, R1234yf and R1234ze.
  9. It can be applied in existing air-cooled sites through air-assisted liquid cooling (a side-car configuration).

Using it in design

  • In facility planning, choose between in-row (400 kW or 180 kW) and in-rack (100 kW or 40 kW) CDU types according to rack density, taking 45 degC facility water for the in-row liquid type and 35 degC air for the air type as input conditions.
  • Evaluate the option of warmer facility water for chiller load, dry coolers and waste-heat recovery scenarios; the paper presents this benefit as climate dependent.
  • When choosing cold-plate and series arrangement, make the exit vapour quality limit (below 100%) and a dry-out margin design criteria.
  • In fluid selection, weigh GWP, safety class and PFAS regulatory risk together; for flammable fluids plan additional safety measures and a leak-check frequency.
  • Connect leak detection to the BMS and define a filter-drier service plan; add procedural steps against moisture ingress at quick-disconnect points.

Who should read it

Mechanical designers evaluating direct-to-chip cooling for high-density AI halls, CDU and cold-plate manufacturers and operators.

Document contents

  1. Introduction
  2. Compliance with Open Compute Project Tenets
  3. Pumped Two-Phase (P2P) Liquid Cooling Solutions (what it is and its advantages, heat path from chip to outdoor rejection, cold plates, CDU, quick-disconnect couplings, refrigerant-grade hose, charge management, flow distribution, pressure regulation, filtration, secondary fluid network)
  4. Coolants/Refrigerants for Pumped Two-Phase Cooling (medium-pressure and low-pressure)
  5. Application and Installation Support
  6. Conclusions
  7. Glossary and references

Related standards

  • OCP Guidelines for Using Dielectric Heat Transfer Fluids in Two-Phase Cold Plate-Based Liquid-Cooled Racks

Read the document

ocp-pumped-2p-refrigerant-dlc-whitepaper-2025.pdf

PDF · 1.3 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Devdatta Kulkarni (Intel); Russ Tipton (Vertiv); Elvis Leka (Parker Hannifin Sporlan); Joe Bankston (Parker Hannifin); Qingyang Wang (Accelsius); Jeff King (Intel)
Publisher
Open Compute Project Foundation
Year
2025
Document number
Version 1.0
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Devdatta Kulkarni (Intel); Russ Tipton (Vertiv); Elvis Leka (Parker Hannifin Sporlan); Joe Bankston (Parker Hannifin); Qingyang Wang (Accelsius); Jeff King (Intel) (2025). White Paper: Pumped 2P Refrigerant-Based Direct Liquid Cooling (DLC) Technology for Next Generation AI Clusters with High TDP Accelerators, v1.0 (14 February 2025). Open Compute Project Foundation. Version 1.0. https://www.opencompute.org/documents/2p-refrigerant-based-dlc-wp-v1-pdf-1/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.