A holistic design of an energy-efficient data center with solar PV integration
International Journal of Energy Studies · Muhammed Burak Oyacı, Önder Kızılkan
A Tier III-compliant 500 m² data centre designed for Ankara has a CLTD-derived heat gain of 470.63 kW; an 85.05 kWp rooftop PV array yields 192 MWh a year, covering 2.07% of demand.
On this page
Overview
Oyacı and Kızılkan of Isparta University of Applied Sciences treat architecture, cooling load, equipment selection and solar integration for a mid-scale Tier III-compliant data centre in Ankara within one framework. The facility houses 60 cabinets of 45U at an average 7 kW each, with a 12 m x 18 m white space and 500 m² total usable area.
Cooling load is calculated by the CLTD method at Ankara's peak summer conditions (34 °C dry bulb, 40% RH). Total internal heat gain comes to 470.63 kW, served by three CRAH units in a 2N arrangement with cold aisle containment and a raised floor. The UPS room adds a cooling demand of 170.33 kW. The chilled water plant has two 750 kW chillers, each capable of free cooling.
On the electrical side, the UPS is sized at 462 kW and chosen modular for expansion. Cooling runs directly from the diesel generators; a gap of about 30 seconds during generator start is accepted on the strength of the room's thermal mass and pre-cooled air. Generator load is 1,645.3 kVA, met by two 1,700 kVA units in N+1, with 28,800 L of underground fuel per generator for 72 hours of autonomy.
The 85.05 kWp rooftop PV system produces about 192,355 kWh a year and covers only 2.07% of the 9.28 GWh annual demand. A 29.33 MWp ground-mounted system is dimensioned to cover all of it. With the 2023 Turkish grid factor of 0.42 kg CO₂/kWh, the rooftop system avoids about 80.8 tonnes of CO₂ a year and the ground-mounted system 3,897.6 tonnes. Because PV output is intermittent, the paper proposes ATS-controlled dual-mode charging through the existing UPS infrastructure instead of direct connection to critical load.
Key points
- Facility: 500 m², 60 cabinets x 7 kW, Tier III-compliant; white space 12 m x 18 m.
- Design condition for Ankara summer: 34 °C dry bulb, 40% RH, ground temperature 15 °C.
- CLTD total internal heat gain is 470.63 kW; three CRAH units in 2N.
- Aisle dimensions: hot aisle 1.8 m, cold aisle 1.2 m; 3 m between cabinets and walls.
- UPS 462 kW, modular; UPS room cooling load 170.33 kW.
- Two 750 kW chillers with free cooling; glycol mixture 30% glycol, 70% water.
- Generator load 1,645.3 kVA; two 1,700 kVA units (N+1), 28,800 L fuel per generator for 72 hours.
- Rooftop PV 85.05 kWp: 192,355 kWh a year, 2.07% of demand, about 727,102 TRY saved (at 3.78 TRY/kWh).
- Ground-mounted PV 29.33 MWp: full demand, about 35.066 million TRY saved and 3,897.6 t CO₂ avoided a year.
- The abstract gives annual demand as 9.28 GWh; the highlights section quotes 10.76 GWh.
Using it in design
- Calculate cooling load at local peak summer conditions with an explicit safety factor, and size CRAH and chillers from that sum.
- When sizing generator and transformer, include the starting inrush of mechanical and UPS loads and the 1.3 factor on UPS load.
- Where cooling runs from generators, verify that the room's thermal mass and pre-cooled air volume cover the roughly 30 second gap.
- Since roof area covers a small fraction of demand, derive PV capacity first from roof capacity, then from the target renewable share.
- For PV on critical load, review the ATS-controlled charging strategy together with UPS module loading.
- Size fuel storage for the target autonomy (72 hours in the example) and add a fuel polishing system.
Who should read it
Engineers designing mid-scale data centres in Türkiye and similar climates, and investment decision makers assessing renewable integration.
Document contents
- Introduction
- Materials and Methods
- Results and Discussion
- Conclusion
Publication details
- Authors
- Muhammed Burak Oyacı; Önder Kızılkan
- Publisher
- International Journal of Energy Studies
- Year
- 2025
- Document number
- 10(3), 787–806
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected. Free reading is not commercial redistribution permission; metadata and original short summaries only.
Citation
Muhammed Burak Oyacı; Önder Kızılkan (2025). A holistic design of an energy-efficient data center with solar PV integration. International Journal of Energy Studies. 10(3), 787–806. https://doi.org/10.58559/ijes.1750386
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
