Planer PRD-V dry coolers and performance correction factors
Planer
Planer's PRD-V V-type dry coolers span 138 to 939 kW; the standard duty is 40/35°C water, 25°C air and zero altitude, with correction factors for glycol, altitude and fin material.
On this page
Overview
The PRD-V series in Planer's air-cooled chiller catalogue is a range of modular dry coolers with a V-type coil design. Features include a copper-tube aluminium-fin coil, high-airflow axial fans, a CE-standard power and control panel, pressure equipment directive compliance, a centrifugal pump and a stainless reserve tank. Fan speed control and microprocessor control are standard; epoxy-coated aluminium fins, stainless steel casing, EC fans, a spray system and a self-draining system are options.
The model tables give 12 models from 138 kW to 939 kW (PRDV 80102 to 80107 and 80202 to 80207). Each row lists water capacity, water flow, number of fans, fan power and current, sound level at 10 m and weight. For example the 80102 is 138.5 kW, 41.1 m³/h with two fans, while the 80207 is 938.6 kW and 282.6 m³/h. The dimension table gives length, width, height and water connections.
Performance conditions are tied to EN 1048 and Eurovent 7/C/003: fluid water, air inlet 25°C, water inlet 40°C, water outlet 35°C, altitude 0 m, sound level at 10 m in dBA (EN 13487). Factors are given for other fluids (0.95 for 34% ethylene glycol), fin materials (coated aluminium 0.97, copper 1.03) and altitude; the altitude factor follows fR = 1 - (0.000075 × H) (0.93 at 1000 m).
Real capacity is catalogue capacity multiplied by the three factors. In the catalogue example a 258.5 kW model with 34% glycol (0.95), 1000 m (0.93) and coated aluminium (0.97) falls to about 221.5 kW. For other temperature differences the manufacturer asks to be consulted. The catalogue also gives freezing points of water-glycol mixes (-19°C at 34% glycol, -37°C at 50%) and explains the model code.
Key points
- Capacity range is 138-939 kW; 12 models (PRDV 80102-80107 and 80202-80207).
- Standard condition: water 40/35°C, air 25°C, altitude 0 m; EN 1048 and Eurovent 7/C/003.
- Fluid correction: 0.95 for 34% ethylene glycol.
- Fin material factor: coated aluminium 0.97, copper 1.03.
- Altitude factor fR = 1 - 0.000075×H; 0.93 at 1000 m and 0.78 at 3000 m.
- Real capacity = catalogue capacity × fSA × fM × fR; the example 258.5 kW model drops to about 221.5 kW.
- Water flow runs from 41.1 m³/h (80102) to 282.6 m³/h (80207); fan power 4-28 kW.
- Freezing point: -8°C at 20% glycol, -19°C at 34%, -25°C at 40%, -37°C at 50%.
Using it in design
- If the design water temperature difference is not 40/35°C, request a manufacturer selection; the catalogue table holds for this condition only.
- Apply the three correction factors for glycol content, fin material and site altitude to catalogue capacity and confirm adequate margin.
- Set freeze protection by choosing glycol content against the site's lowest outdoor temperature and confirm it in the freezing point table.
- In coastal or dirty environments, include the capacity factor when choosing epoxy-coated or copper fins.
- Correct the 10 m sound level for distance (about -14 dBA at 50 m, for example).
Who should read it
Mechanical engineers designing free-cooling or heat-rejection circuits with dry coolers.
Document contents
- PRD-V series dry coolers
- Model table
- Technical drawing and dimensions
- Performance conditions
- Correction factors
- Capacity calculation example
- Water-glycol freezing points
- Model nomenclature
Publication details
- Authors
- Planer
- Publisher
- Planer
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Planer Planer PRD-V dry coolers and performance correction factors. Planer. https://www.planerchillers.com/storage/products/catalogs/prd-v-serisi-katalog.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.