Cable Bonding Methods
Original title Kablo Topraklama Yöntemleri
Türk Prysmian Kablo ve Sistemleri A.Ş.
A Turkish Prysmian guide compares single-point, split single-point and both-end bonding of cable screens and armour in terms of induced voltage and circulating-current losses.
On this page
Overview
The guide defines the purpose of earthing as protecting human life and system continuity, and names three classes: protective, operational and lightning earthing. In Turkey earthing rules are given by the Regulation on Earthing in Electrical Installations. It stresses that electronic and microprocessor-based components are sensitive to electromagnetic effects. The magnetic-field section explains that conductors carrying alternating current induce a circulating current in the armour, proportional to the current in the conductor. In two-core cables and three-phase circuits the magnetic fields largely cancel; if magnetic material such as steel-wire armour or an iron conduit is present the field is much stronger. Circulating currents increase losses and cable heating.
In the installation-formation section, trefoil arrangement keeps the cores equidistant, reducing circulating currents and losses, and takes less space, but its lower heat dissipation than flat formation reduces current-carrying capacity. Flat formation carries more current but needs more space, and the centre cable is affected by the fields of the neighbouring phases, so bonding of screens and armour is important.
Bonding types are given under three headings. With single-point bonding there is no circulating current and losses are low; but a voltage proportional to length and current is induced at the open end, which makes insulation critical there. Because earth-fault current returns by external paths, a parallel earth conductor bonded at both ends is used. Split single-point bonding suits longer distances. Both-end bonding is the most economical, but continuous circulating current flows in the screen, raising losses and heating, so it is usually chosen with trefoil formation.
Key points
- Earthing is classed as protective, operational or lightning earthing.
- The circulating current induced in armour or screen is proportional to the conductor current.
- Magnetic material such as steel-wire armour or an iron conduit greatly increases the conductor's magnetic field.
- Trefoil reduces losses and saves space; its current-carrying capacity is lower than flat formation.
- Single-point bonding has no circulating current; the induced voltage at the open end makes insulation quality critical.
- With single-point bonding, a parallel earth conductor bonded at both ends carries the earth-fault current.
- Both-end bonding is the most economical; continuous circulating current causes losses and heating, so trefoil is preferred.
- Split single-point bonding follows the same principle as single-point and suits longer distances.
Using it in design
- On armoured MV and LV cable routes, choose the bonding method (single-point, split, both-end) by length and load current.
- With single-point bonding, calculate the induced voltage at the open end and the insulation level; design the parallel earth conductor.
- With both-end bonding, include the circulating-current loss in the current-rating calculation and use trefoil where possible.
- In flat formation, check heating of the centre cable and voltage imbalance.
- On sensitive electronics and data runs, confirm the screen is earthed.
Who should read it
Electrical engineers designing MV and LV cable routes, earthing and screen or armour bonding.
Document contents
- Introduction
- Magnetic field formation
- Cable installation formations
- Cable bonding types: single-point, split single-point, both-end
Publication details
- Authors
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Publisher
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Year
- Year not stated
- Document number
- Technical article; cable screen and armour bonding
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Undated article. Simplified magnetic-field statements and universal ampacity comparisons were not treated as validated design equations.
Citation
Türk Prysmian Kablo ve Sistemleri A.Ş. Kablo Topraklama Yöntemleri. Türk Prysmian Kablo ve Sistemleri A.Ş.. Technical article; cable screen and armour bonding. https://tr.prysmian.com/sites/tr.prysmian.com/files/2024-05/Kablo_Topraklama_Y%C3%B6ntemi.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.