Technical guideFree to readYear not stated

Shielding and Balance Performance of Data Cables and Similar Shielded Cables in Relation to Shield Design

Original title Data Kablolarının ve Benzer Ekranlı Kabloların Ekran Tasarımı ile İlgili Ekranlama ve Denge Performansı

Türk Prysmian Kablo ve Sistemleri A.Ş. · Christian Pfeiler

A technical paper by Prysmian (Draka) R&D manager Dr. Christian Pfeiler explaining shield naming (U/UTP, F/UTP, S/FTP) under ISO/IEC 11801 and IEC 61156, and the limits for transfer impedance, coupling attenuation and balance (TCL, EL TCTL).

On this page

Overview

The paper explains that balanced high-frequency data cables give natural protection against electromagnetic influence through balanced-mode propagation even when unshielded, that shielding increases this protection and that international standards measure the degree of protection with parameters. Table 1 shows which shield designs relate to which categories: from Cat 5e to Cat 6A U/UTP, F/UTP, SF/UTP and double-screened U/FTP, F/FTP, S/FTP; Cat 7 and above require individually screened pairs. The source is a cable manufacturer and it summarises its own product portfolio at the end.

Naming follows the 'oo/iii' form: oo denotes the overall screen (F foil, S braid, SF foil and braid) and iii the screen of the individual balanced element (FTP foil-screened pair, UTP unscreened). Screening performance is measured by two parameters: transfer impedance (shielded cables only, measured per IEC 62153-4-3) and coupling attenuation (shielded and unshielded, measured per IEC 62153-4-5). For unshielded cables, coupling attenuation is closely tied to cable balance, which is expressed by TCL and EL TCTL.

Limits are given in IEC 61156-5 and -6: Grade 1 transfer impedance is 10 mΩ/m at 1 MHz and 60 mΩ/m at 100 MHz; Grade 2 is 50 mΩ/m at 1 MHz and 1000 mΩ/m at 100 MHz. Coupling attenuation for 30-100 MHz is Type I 85 dB, Type Ib 70 dB, Type II 55 dB, Type III 40 dB. TCL levels 1-4 are 40, 50, 60 and 70 dB, and EL TCTL levels 35, 35, 45 and 55 dB. For Class EA shielded channels, coupling attenuation in E1, E2 and E3 environments is 40, 50 and 60 dB.

An important distinction: under ISO/IEC 11801, for an unshielded cabling system only the balance parameters (TCL, EL TCTL) are specified and for a shielded system only coupling attenuation; in shielded systems the balance parameters in field testing are for information only. A braided screen gives the best screening and good electrical contact with connectors; where cost savings are needed, Type Ib braided cables are used. Because the document carries product information, the designer should verify principles and limits against the standards.

Key points

  1. Naming oo/iii: oo overall screen (F foil, S braid, SF foil and braid), iii individual element screen (FTP or UTP).
  2. Cat 7 and above require individually screened pairs; individually screened pairs are not common in Cat 5e.
  3. Screen performance is measured by transfer impedance (IEC 62153-4-3) and coupling attenuation (IEC 62153-4-5).
  4. Grade 1 transfer impedance: 10 mΩ/m at 1 MHz, 10 at 10 MHz, 30 at 30 MHz, 60 at 100 MHz.
  5. Coupling attenuation (30-100 MHz): Type I 85 dB, Type Ib 70 dB, Type II 55 dB, Type III 40 dB.
  6. TCL levels 1-4: 40, 50, 60 and 70 dB; EL TCTL levels 1-4: 35, 35, 45 and 55 dB.
  7. U/UTP cables generally have Type II or Type III coupling attenuation performance.
  8. Class EA shielded channel coupling attenuation: E1 40 dB, E2 50 dB, E3 60 dB (30-100 MHz).
  9. Under ISO/IEC 11801 a shielded system specifies only coupling attenuation; balance parameters are defined only for Class I and II (Cat 8).

Using it in design

  • Decide between shielded and unshielded cabling and the required coupling attenuation type from the environment's electromagnetic conditions (M.I.C.E. E1-E3).
  • In cable datasheets, check naming such as U/UTP, F/UTP and S/FTP and the coupling attenuation type (I, Ib, II, III); do not rely on the category name alone.
  • For shielded systems, include earthing continuity of the screen with connectors and connecting hardware in the specification and field testing.
  • For unshielded cabling, evaluate balance parameters (TCL, EL TCTL) as an acceptance criterion.
  • Read manufacturer portfolio tables as examples, not selection data, and verify them against the standards.

Who should read it

Engineers designing structured cabling, specification writers selecting cables for EMC, and field test engineers.

Document contents

  1. Naming of Shield Designs
  2. Screening Performance Parameters
  3. Limit Values for Screening Parameters and Relevant Cable Designs
  4. Screening and Balance Requirements for Cables by Cabling System
  5. Screening Performance within the Draka UC-Cable Range

Related standards

  • ISO/IEC 11801
  • IEC 61156
  • IEC 62153-4-3
  • IEC 62153-4-5

Publication details

Authors
Christian Pfeiler
Publisher
Türk Prysmian Kablo ve Sistemleri A.Ş.
Year
Year not stated
Document number
Technical article
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Author identified on PDF cover. Publication year not established; no current-standard conformity inferred.

Citation

Christian Pfeiler Data Kablolarının ve Benzer Ekranlı Kabloların Ekran Tasarımı ile İlgili Ekranlama ve Denge Performansı. Türk Prysmian Kablo ve Sistemleri A.Ş.. Technical article. https://tr.prysmian.com/sites/tr.prysmian.com/files/media/documents/data-kablolarinin-ve-benzer-ekranli-kablolarin-ekran-tasarimi-ile-ilgili-ekranlama-ve-denge-performansi_0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.