Cable Lugs and Cable Compatibility
Original title Kablo Pabucu ve Kablo Uyumu
Türk Prysmian Kablo ve Sistemleri A.Ş.
A Turkish Prysmian technical note explains how TS EN 60228 conductor design relates to lug geometry through a test on 35-95 mm² sizes, and describes the fire risk of poor crimping.
On this page
Overview
The note opens by stating that selecting the right cable accessory and ensuring accessory compatibility matter as much as selecting the cable. It explains what cable lugs are, how they are used and that copper is the most common metal. Fork or U-shaped lugs are used for screw terminals, closed ring or O-type lugs for bolted applications, and pin or flat-tab lugs for crimped and blade terminals.
The compatibility section states that IEC 60228 is the most common standard for conductor design and that TS EN 60228:2007 is used in Turkey. The standard makes a maximum DC conductor resistance at 20 °C per 1 km mandatory for the electrical cross-section, but sets no mandatory requirement for the geometric cross-section and gives only an informative diameter range. According to the note, the electrical cross-section is the important parameter, not the geometric one.
In response to market comments about mismatches, the manufacturer tested three lugs from each of three lug manufacturers for the 35, 50, 70 and 95 mm² sizes. The results show that Prysmian conductors fit every correctly made lug sample when properly crimped. Table 3 compares lug diameters with conductor diameters.
The poor-connection section names over-crimping as the most common error: the conductor is crushed, wire breaks develop under vibration and bending, resistance rises, and overheating can damage the insulation and cause a fire. The conclusion recommends using a hydraulic crimping tool and having it calibrated before the interval the tool manufacturer recommends. Choosing a lug larger than the conductor reduces the contact surface, and arcing in the voids can start a fire.
Key points
- TS EN 60228:2007 makes a maximum DC conductor resistance at 20 °C per 1 km mandatory for the electrical cross-section.
- The geometric diameter range is informative and guiding only in the standard (Annex C, Table C.2).
- Test: three lug manufacturers, 35, 50, 70 and 95 mm² sizes, three samples each.
- With a correctly made lug and correct crimping, Prysmian conductors fit fully.
- Over-crimping is the most common error: the conductor is crushed, wires break, resistance and heat rise.
- A lug larger than the conductor reduces contact surface; arcing in voids creates fire risk.
- Use of a hydraulic crimping tool, calibrated at the interval the tool manufacturer recommends, is advised.
- Lug types: fork (screw terminal), ring (bolt), pin and flat-tab (crimped and blade terminals).
Using it in design
- In lug specifications, state lug selection matched to conductor cross-section together with a TS EN 60228-compliant conductor type.
- Make hydraulic tool use and calibration records an acceptance condition for site crimping.
- Check for heating from over-crimping and oversized lugs at commissioning with thermal-camera scans.
- Where cross-section reduction is needed, confirm that the lug can join a thicker conductor to a smaller connector but with adequate contact surface.
- For lug materials other than copper, confirm conductor and lug material compatibility with the manufacturer.
Who should read it
Electrical engineers designing and executing low-voltage cable terminations, installation crews and site quality-control staff.
Document contents
- Introduction
- What is a cable lug?
- Types of use
- Lug and cable compatibility
- Consequences of an improper connection
- Conclusion
- References
Related standards
- IEC 60228
Publication details
- Authors
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Publisher
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Year
- Year not stated
- Document number
- Technical article; 5 pages
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Original publication year is not established; upload-folder and migrated HTML dates were not used as the article year.
Citation
Türk Prysmian Kablo ve Sistemleri A.Ş. Kablo Pabucu ve Kablo Uyumu. Türk Prysmian Kablo ve Sistemleri A.Ş.. Technical article; 5 pages. https://tr.prysmian.com/sites/tr.prysmian.com/files/2024-05/Kablo_Pabucu_ve_Uyumu.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.