Technical guideFree to readYear not stated

Voltage drop calculations during fire (Prysmian)

Original title Yangın Esnasında Gerilim Düşümü Hesaplamaları

Türk Prysmian Kablo ve Sistemleri A.Ş.

A Türk Prysmian technical note shows that at 750 °C fire temperature copper conductor resistance rises by a factor of 3.0342, and that voltage drop on a 50 m burning cable goes from 1.4% to 4.2-4.3%.

On this page

Overview

This technical note from Türk Prysmian Kablo ve Sistemleri A.Ş. explains how to calculate voltage drop in fire-resistant cables during a fire. In a fire the cable temperature leaves the safe operating range given in standards; unless special materials are used the maximum operating temperature is taken as 90 °C for XLPE insulation and 70 °C for PVC. As temperature rises, conductor resistance and therefore voltage drop increase. The worst case is not a partial exposure but a long section or the whole cable exposed to fire.

The method is simple: VD = coefficient x I x L, the voltage-drop coefficient by cross-section (mV/A/m) multiplied by current and route length. For the fire case the 90 °C coefficient is multiplied by a correction factor calculated for 750 °C. The factor is 1+0.00393 x (750-20) / (1+0.00393 x (90-20)) = 3.0342, where 0.00393 per °C is the copper temperature coefficient. Because the length burnt and the temperature distribution along the cable are not known, assumptions are required.

The examples use 2XH FE 180 cable at 240 V. Example 1: 2x2.5 mm2, 50 m, 5 A: normally 3.3 V (1.4%) with 13.19 mV/A/m; with 2 m at 750 °C, 3.6 V (1.5%); with all 50 m at 750 °C, 10 V (4.2%). Example 2: 3x120 mm2, 50 m, 200 A: normal 3.4 V (1.4%); 2 m burnt 3.7 V (1.5%); all burnt 10.3 V (4.3%). If the exposed length is small, the voltage drop changes little.

If voltage drop is to stay under 4% when 50 m of cable burns, the cross-section should be increased by one or two steps: 4 mm2 instead of 2.5 mm2 in example 1 (8.24 mV/A/m, 6.3 V, 2.6%) and 150 mm2 instead of 120 mm2 in example 2 (0.29 mV/A/m, 8.8 V, 3.7%). The note also gives a table of mV/A/m values for N2XH FE 180 cables from 1.5 to 500 mm2, usable for 2XCH and 2XRH FE180 products.

Key points

  1. Maximum operating temperature: XLPE 90 °C, PVC 70 °C (without special materials); in fire, resistance and voltage drop rise.
  2. Voltage drop formula: VD = coefficient x I x L; fire correction factor at 750 °C is 3.0342 (copper temperature coefficient 0.00393/°C).
  3. Example 1 (2x2.5 mm2, 5 A, 50 m, 240 V): normal 3.3 V (1.4%); 2 m burnt 3.6 V (1.5%); 50 m burnt 10 V (4.2%).
  4. Example 2 (3x120 mm2, 200 A, 50 m, 240 V): normal 3.4 V (1.4%); 2 m burnt 3.7 V (1.5%); all burnt 10.3 V (4.3%).
  5. A partial length in fire changes the voltage drop little; a long section or the whole cable raises it markedly.
  6. To hold the 4% limit, cross-section increase: 4 mm2 instead of 2.5 mm2 (2.6%) and 150 mm2 instead of 120 mm2 (3.7%).
  7. The coefficient table is given for N2XH FE 180; for example 0.28 mV/A/m for 1x240 mm2 in flat laying.

Using it in design

  • For loads that must run in a fire (fire pump, smoke extraction, emergency lighting) check cable cross-section separately against voltage drop at fire temperature (correction factor 3.0342).
  • Write the cable length that could be exposed to fire as a project assumption; since the worst case is the whole route burning, calculate on that basis.
  • If you set an upper limit such as 4%, include enlarging the cross-section by one or two steps on long routes from the start.
  • Reapply the 240 V single-phase examples to a three-phase system with your own voltage and current; the table coefficients stay the same.

Who should read it

Electrical designers selecting fire-resistant cables and engineers for fire safety and emergency power systems.

Document contents

  1. Introduction
  2. Voltage drop calculations during fire
  3. Voltage drop calculation
  4. Examples 1 and 2
  5. Correction factor calculation (750 °C)
  6. N2XH FE 180 voltage drop coefficient table

Publication details

Authors
Türk Prysmian Kablo ve Sistemleri A.Ş.
Publisher
Türk Prysmian Kablo ve Sistemleri A.Ş.
Year
Year not stated
Document number
Technical article; 3 pages
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Undated technical note. The compact formula omits the mV-to-V factor in its first expression, while worked examples include 0.001; no formula is imported automatically.

Citation

Türk Prysmian Kablo ve Sistemleri A.Ş. Yangın Esnasında Gerilim Düşümü Hesaplamaları. Türk Prysmian Kablo ve Sistemleri A.Ş.. Technical article; 3 pages. https://tr.prysmian.com/sites/tr.prysmian.com/files/2024-05/Yang%C4%B1n_Esnas%C4%B1nda_Gerilim_D%C3%BC%C5%9F%C3%BCm%C3%BC_Hesab%C4%B1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.