Piller UB-V Series for Data Centres: electrically coupled UPS topology
Original title UB-V Series for Data Centres
Piller
Piller UNIBLOCK UB-V is an electrically coupled UPS in modules from 1100 kVA / 1.0 MW to 3600 kVA / 3.24 MW; the manufacturer claims 98% efficiency at 100% load, 97% at 50% load and a 5x higher MTBF than static UPS.
On this page
Overview
The manufacturer page presents Piller's UNIBLOCK UB-V series as a new-generation electrically coupled UPS for cloud hyperscale, wholesale colocation and large enterprise data centres. In an electrically coupled UPS the energy store connects to the UPS unit only electrically, and power semiconductors control the flow for both discharge and recharge. The page positions conventional static UPS and UB-V within that same class.
The power range is 1100 kVA / 1.0 MW to 3600 kVA / 3.24 MW, in both battery and kinetic (flywheel) storage versions. Because a single module provides high power, fewer modules need paralleling, which the page ties to higher reliability of the power string. Units can operate at low or medium voltage and have bi-directional power flow, allowing power to feed back to the grid or move between sources in a microgrid.
The performance claims are: online efficiency of 98% at 100% load and 97% at 50% load (typical static UPS 96.3% at both points); a mean time between failures for a single unit 5 times that of a typical static UPS because there are no power capacitors or fans; and offline service intervals of as little as once every five years. The e-VENTLOG remote monitoring package can remove annual service shutdowns for up to five years in controlled environments. These are qualified manufacturer claims.
The cost section says capital cost per kW falls as rating rises and that more than 20% of technical plant room space can be saved. As an example, a 48 MW data centre could save up to $7.5 million in electricity cost over ten years at $0.1 per kWh.
Key points
- Power range 1100 kVA / 1.0 MW to 3600 kVA / 3.24 MW; battery or kinetic storage version.
- Online efficiency 98% at 100% load and 97% at 50% load; typical static UPS 96.3% at both points.
- No power capacitors or electric fans; single-unit MTBF 5 times that of typical static UPS.
- Offline service interval as little as 5 years; e-VENTLOG enables shutdown-free annual checks.
- Operates at low or medium voltage; bi-directional power flow with feed-back to the grid.
- More than 20% plant room space saving; cost per kW falls as rating rises.
- A 48 MW data centre could save up to $7.5 million in electricity over 10 years (at $0.1/kWh).
Using it in design
- In multi-megawatt halls, count the single-module power (up to 3.24 MW) as a way to cut the number of paralleled modules in the power-chain and failure-point count.
- Multiply the efficiency differences (98% and 97% against 96.3%) by your annual load profile to get ten-year energy cost; since the claims are qualified, ask the manufacturer for verification.
- Choose battery or kinetic storage by autonomy time, maintenance and footprint requirements.
- Medium-voltage connection and feed-back to the grid affect switchgear and protection design; coordinate early.
Who should read it
Power designers and investors choosing large UPS architecture in hyperscale and colocation data centres.
Document contents
- UB-V Series for Data Centres
- Electrically Coupled UPS
- What Makes The UB-V Series Different
- UB-V Series UPS Benefits
- Cloud, colo and enterprise
- Capital Efficiency
- Operational Efficiency
- Piller e-VENTLOG
- Redefining UPS Topologies
Publication details
- Authors
- Piller
- Publisher
- Piller
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Piller UB-V Series for Data Centres. Piller. https://www.piller.com/product/ub-v-series-for-data-centres/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
