Piller UNIBLOCK UBT legacy technical data

Piller

A two-page Piller product data sheet issued on 29 March 2011 for the UNIBLOCK UBT rotary UPS series, covering six models from 420 kVA to 1670 kVA: output power factor 0.8, efficiency up to 96%, input current distortion below 3% and input power factor 0.99.

On this page

Overview

The sheet gathers the six ratings of the UNIBLOCK UBT series in one table: UBT 420, 500, 625, 800, 1100 and 1670. Rated apparent power, active power and output current are given for each model, for example 1670 kVA, 1336 kW and 2410 A for the UBT 1670. Output voltage is 400/231 V, adjustable by ±5%, and input voltage is 400/231 V ±10%. Rated frequency is 50 Hz, with stability stated as 0.1% static when self controlled, 1% when on mains and 1% dynamic.

The first page lists the series highlights: leading and lagging output power factor without derating, unlimited crest factor and 100% load step capability, the ability to clear short-circuit faults without using the bypass, 99% harmonic isolation between input and output, a natural sine-wave output and redundant on-board power supplies. A medium-voltage option and a water-cooling option that uses building chilled water are also listed.

Physical data fall into two frame sizes. The UBT 420, 500 and 625 measure 2710 x 980 x 2300 mm (width, depth, height) and weigh 5800 kg. The UBT 800, 1100 and 1670 measure 4600 x 1320 x 2700 mm; weight is 13050 kg for the first two and 14500 kg for the UBT 1670. Backup time is customised per project. The 2011 sheet describes the earlier UBT series; the current UBT+ series is a separate product and is assessed from its own data sheet.

Key points

  1. Six models: UBT 420 (336 kW, 606 A), UBT 500 (400 kW, 722 A), UBT 625 (500 kW, 902 A), UBT 800 (640 kW, 1155 A), UBT 1100 (880 kW, 1588 A), UBT 1670 (1336 kW, 2410 A).
  2. Output power factor 0.8; efficiency up to 96%.
  3. Input power factor 0.99; input current distortion below 3%.
  4. Output voltage 400/231 V adjustable by ±5%; input voltage 400/231 V ±10%; input frequency 50 Hz, adjustable between ±1% and ±5%.
  5. Small frame (420 to 625 kVA): 2710 x 980 x 2300 mm, 5800 kg. Large frame (800 to 1670 kVA): 4600 x 1320 x 2700 mm, 13050 kg or 14500 kg.
  6. Options: battery temperature sensor, 4 pole construction for galvanic isolation, Castell or Kirk key interlocks, water cooling, SNMP adapter, Profibus-DP, up to 3 protocol gateways and 3 I/O cards.
  7. Backup time is customised; the sheet gives no fixed duration.

Using it in design

  • Use the unit masses in floor loading calculations: 5800 kg for the small frame and 13050 to 14500 kg for the large frame, on footprints of roughly 2.7 x 1.0 m and 4.6 x 1.3 m.
  • Read active power at the 0.8 power factor: the 1670 kVA model delivers 1336 kW, so match IT load in kW.
  • Size output cables and busbars from the rated current in the table (1588 A for the UBT 1100, for example).
  • Base generator and transformer sizing on the 0.99 input power factor and the current distortion below 3%.
  • Use this sheet when assessing an existing UBT installation, and the current UBT+ data sheet for a new design.

Who should read it

Electrical engineers selecting large UPS systems, operations teams assessing existing UBT installations, and designers doing structural load calculations.

Document contents

  1. Highlights
  2. Output
  3. Input
  4. General data
  5. Options

Publication details

Authors
Piller
Publisher
Piller
Year
2011
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Piller (2011). Piller UNIBLOCK UBT legacy technical data. Piller. https://piller.dk/wp-content/uploads/2019/08/roterende-ups-ubt_data.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.