ABB Compact ATS: Compact without Compromise (OTM_C_D)
Original title ABB Compact ATS compact without compromise 1SCC308001B0201
ABB
ABB catalogue for the 40, 63 and 125 A OTM_C_D Compact ATS family: fixed (C20D) and adjustable (C21D) versions, 2 to 4 poles, IEC 60947-6-1 testing and mains/generator transfer delays.
On this page
Overview
The catalogue presents ABB's single-housing automatic transfer switch (ATS) that needs no external power supply. The manufacturer states about 40% less cabinet space than conventional solutions. The device is tested to IEC 60947-6-1 and the listed applications include residential, commercial and industrial buildings as well as telecom and data centres as a standby-power transfer device. All live parts are enclosed and an external handle allows manual transfer in an emergency.
The family has two versions. OTM_C20D is fixed: predefined delay times and voltage thresholds, for network/network applications. OTM_C21D is adjustable: for network/network and network/genset applications, with configurable transfer and back-switching delays, adjustable voltage thresholds and Modbus RTU through a plug-in module. Tables list 2, 3 and 4 pole units at 40, 63 and 125 A with ordering codes and weights (1.75 kg for 3 poles, 2.00 kg for 4 poles).
Technical features give rated operational voltage 220-240 V single phase and 380-415 V three phase (±20%), frequency 50/60 Hz ±10%, operating temperature -20 to +55 °C, altitude up to 2000 m and IP20 front panel. Voltage sensing accuracy is 5% on the fixed and 3% on the adjustable version. On the C21D the undervoltage threshold is 0.7-0.95 Ue, overvoltage 1.05-1.3 Ue, transfer delay 0-30 s, back-switching delay 0-900 s and generator stop delay 240 s.
The document is a product catalogue: it describes an integrated transfer device rather than a contactor and control-relay combination. Voltage unbalance and invalid-frequency detection are not marked for either version; where that is required a different ATS controller is needed.
Key points
- Frame sizes OTM40, OTM63, OTM125; 2, 3 and 4 poles; 1.75 kg for 3 poles, 2.00 kg for 4 poles.
- Rated voltage 220-240 V (single phase) and 380-415 V (three phase), ±20%; 50/60 Hz ±10%.
- Voltage sensing accuracy 5% on C20D, 3% on C21D; Uimp 6 kV, overvoltage category III.
- C21D: undervoltage 0.7-0.95 Ue, overvoltage 1.05-1.3 Ue, transfer delay 0-30 s, back-switching delay 0-900 s, generator stop 240 s.
- C20D is for network/network only; network/genset transfer needs the C21D.
- Rated current in an enclosure at 40 °C is 40, 63 and 125 A; at 60 °C it is 32, 50 and 100 A.
- Conditional short-circuit rating 50 kA at 415 V with up to 125 A gG fuse; Icw 2.5 kA at 690 V for 1 s.
- Mechanical endurance 10 000 operations; loss per pole 1.6, 2.8 and 6.3 W (40, 63, 125 A).
- Operating temperature -20 to +55 °C, altitude up to 2000 m, IP20 front panel.
Using it in design
- Choose the C21D for a generator-backed data hall incomer; the C20D does not suit generator transfer.
- Coordinate fuses to the catalogue's conditional short-circuit table, for example at most 125 A gG for 50 kA at 415 V.
- In a 60 °C enclosure rate the switches at 32/50/100 A instead of 40/63/125 A.
- If transfer on voltage unbalance or frequency deviation is required, record in the specification that this range does not detect it.
- Tune back-switching and generator stop delays together with the UPS and generator load acceptance.
Who should read it
Electrical engineers and panel builders designing low-voltage distribution and standby-power transfer.
Document contents
- Compact without compromise
- Safety and protection, space saving, affordable range
- Ordering information (OTM_C20D fixed, OTM_C21D adjustable)
- Technical features and functionality
- Time delays and signals
- Technical data OTM40...125
- Accessories
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ABB ABB Compact ATS compact without compromise 1SCC308001B0201. ABB. https://library.e.abb.com/public/012ee8cbadee4756a726670c61372a13/ABB_compacts_ATS_1SCC308001B0201_21-11.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.