Microchannel heat pipes with evaporative condensation
Original title Analysis of an Evaporative Condensation System Coupled to a Microchannel-Separated Heat Pipe for Data Centers
Energies (MDPI AG) · Ying Wang, Xiang Huang et al.
This 2022 Energies study examines a microchannel separated heat pipe system with evaporative condensation; under Xi'an conditions it calculates 62.04% annual energy saving and an annual average COP of 9.43.
On this page
Overview
The study proposes a microchannel-separated heat pipe cooling system with evaporative condensation to reduce data-centre cooling power. The system switches among three operating modes according to outdoor air quality parameters, maximising use of natural cooling sources.
Experimental tests find the ideal liquid-loading rate of the heat pipe system to be 114.4%. Under Xi'an conditions the annual operating hours of the three modes account for 47.2%, 6.1% and 46.7%. With an annual average COP of 9.43, the hybrid system saves 62.04% of annual energy compared with the standard cooling system and the server room cooling system.
Key points
- The system switches among three operating modes; mode choice depends on outdoor air quality parameters.
- The ideal liquid-loading rate is found to be 114.4%.
- Under Xi'an conditions, annual operating hours of the three modes are 47.2%, 6.1% and 46.7%.
- Annual average COP is 9.43; annual energy saving is 62.04%.
Using it in design
- Recompute the saving potential of separated heat pipe and evaporative-condensation hybrids with your own climate data; results are specific to Xi'an.
- Set the heat pipe liquid-loading rate at the optimum value in design.
- Define mode switching logic by outdoor temperature and air quality thresholds.
Who should read it
Mechanical engineers researching natural-cooling and heat-pipe data-centre cooling systems.
Publication details
- Authors
- Ying Wang; Xiang Huang; Junjie Chu; Yan Du; Xing Tang; Cong Dai; Gang Ma
- Publisher
- Energies (MDPI AG)
- Year
- 2022
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Ying Wang; Xiang Huang; Junjie Chu; Yan Du; Xing Tang; Cong Dai; Gang Ma (2022). Analysis of an Evaporative Condensation System Coupled to a Microchannel-Separated Heat Pipe for Data Centers. Energies (MDPI AG). https://doi.org/10.3390/en15239056