Microchannel heat pipes with evaporative condensation

Original title Analysis of an Evaporative Condensation System Coupled to a Microchannel-Separated Heat Pipe for Data Centers

Energies (MDPI AG) · Ying Wang, Xiang Huang et al.

This 2022 Energies study examines a microchannel separated heat pipe system with evaporative condensation; under Xi'an conditions it calculates 62.04% annual energy saving and an annual average COP of 9.43.

On this page

Overview

The study proposes a microchannel-separated heat pipe cooling system with evaporative condensation to reduce data-centre cooling power. The system switches among three operating modes according to outdoor air quality parameters, maximising use of natural cooling sources.

Experimental tests find the ideal liquid-loading rate of the heat pipe system to be 114.4%. Under Xi'an conditions the annual operating hours of the three modes account for 47.2%, 6.1% and 46.7%. With an annual average COP of 9.43, the hybrid system saves 62.04% of annual energy compared with the standard cooling system and the server room cooling system.

Key points

  1. The system switches among three operating modes; mode choice depends on outdoor air quality parameters.
  2. The ideal liquid-loading rate is found to be 114.4%.
  3. Under Xi'an conditions, annual operating hours of the three modes are 47.2%, 6.1% and 46.7%.
  4. Annual average COP is 9.43; annual energy saving is 62.04%.

Using it in design

  • Recompute the saving potential of separated heat pipe and evaporative-condensation hybrids with your own climate data; results are specific to Xi'an.
  • Set the heat pipe liquid-loading rate at the optimum value in design.
  • Define mode switching logic by outdoor temperature and air quality thresholds.

Who should read it

Mechanical engineers researching natural-cooling and heat-pipe data-centre cooling systems.

Publication details

Authors
Ying Wang; Xiang Huang; Junjie Chu; Yan Du; Xing Tang; Cong Dai; Gang Ma
Publisher
Energies (MDPI AG)
Year
2022
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Ying Wang; Xiang Huang; Junjie Chu; Yan Du; Xing Tang; Cong Dai; Gang Ma (2022). Analysis of an Evaporative Condensation System Coupled to a Microchannel-Separated Heat Pipe for Data Centers. Energies (MDPI AG). https://doi.org/10.3390/en15239056

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.