Data centre cooling with dam water

Original title Study on the Performance of a Newly Designed Cooling System Utilizing Dam Water for Internet Data Centers

Energies (MDPI AG) · Selorm Kwaku Anka, Nicholas Lamptey Boafo et al.

This 2022 Energies study examines a hybrid forced/free-cooling system using dam deep water; with hourly data from 16 South Korean cities it finds a 67% annual operating performance over a conventional air-source system.

On this page

Overview

The study develops a new hybrid system combining a forced-cooling cycle and a free-cooling cycle to raise year-round energy efficiency of an internet data centre with high heat loads. The system uses a dam deep water source to reduce energy consumption. It runs in forced-cooling mode when entering water temperature exceeds the mode change temperature of 9 °C, and switches to free-cooling mode below it.

The hybrid system's cooling performance was assessed under varied entering-water temperatures, and annual energy saving was compared with a conventional system on integrated COP using hourly weather and water temperature data from 16 cities in different South Korean climate zones. Because effectiveness depends on the outside climate, suitability must be assessed by region. Experimental findings show that the new system gives a 67% annual operating performance over a conventional air-source internet data centre cooling system.

Key points

  1. The hybrid system combines forced-cooling and free-cooling cycles.
  2. The mode change temperature is 9 °C entering water.
  3. Annual performance is estimated with hourly air and water temperature data from 16 South Korean cities.
  4. A 67% annual operating performance over the conventional air-source system is found.
  5. Effectiveness depends on the outside climate; suitability needs regional assessment.

Using it in design

  • For hybrid systems using natural cold sources such as deep, lake or dam water, set the mode change temperature (9 °C in the study) from your source's annual temperature profile.
  • Assess the suitability of a natural cooling source by region using hourly air and water temperature data.
  • Treat the 67% annual performance figure as a result specific to the South Korean data.

Who should read it

Mechanical engineers evaluating natural-water-source data-centre cooling and site selection.

Publication details

Authors
Selorm Kwaku Anka; Nicholas Lamptey Boafo; Kwesi Mensah; Samuel Boahen; Kwang Ho Lee; Jong Min Choi
Publisher
Energies (MDPI AG)
Year
2022
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Selorm Kwaku Anka; Nicholas Lamptey Boafo; Kwesi Mensah; Samuel Boahen; Kwang Ho Lee; Jong Min Choi (2022). Study on the Performance of a Newly Designed Cooling System Utilizing Dam Water for Internet Data Centers. Energies (MDPI AG). https://doi.org/10.3390/en15249274

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.