Evaluating External Heat Rejection Options for Liquid-Cooled Data Center Applications

Baltimore Aircoil Company

A Baltimore Aircoil Company white paper simulates four heat rejection configurations for an 18 MW liquid-cooled module across six climates and concludes the best choice is a climate-dependent, multi-variable optimization.

On this page

Overview

The white paper is written against the background of AI and HPC pushing rack densities beyond air cooling and driving adoption of direct-to-chip liquid cooling. It argues that the thermal challenge shifts from heat removal in the IT space to rejecting heat outdoors, making heat rejection strategy one of the most consequential design decisions. Figures from the AFCOM 2026 survey show AI training densities exceeding 350 kW/rack by 2030 against an air cooling limit of about 50 kW/rack.

The study covers the heat rejection side upstream of the CDU. An 18 MW module runs at 69.8 °F (21 °C) supply and 87.8 °F (31 °C) return between the outdoor equipment and the CDU. Four configurations are compared: air-cooled chillers with integrated air-cooled condensers (ACC), water-cooled chillers with dry coolers (WCC + DAC), with adiabatic dry coolers (WCC + ADAC) and with closed circuit cooling towers (WCC + CCCT).

The six locations are London, Amsterdam, Dubai, Dulles (Virginia), Amarillo (Texas) and Chicago, simulated with ASHRAE 2025 bin weather data. Load is a constant 100% across 8,760 hours. A variable-speed magnetic-bearing air-cooled chiller represents ACC; free-cooling chillers are excluded because of about 15% lower capacity and up to 50% higher fan energy. For water-cooled systems the condenser water ΔT is 14.4 °F, initial approach about 14.4 °F and condenser pump efficiency 70%.

The conclusion is that selection cannot be reduced to one metric or technology preference. Evaporative-assisted systems (WCC + CCCT) consistently minimize energy use and peak demand; dry systems (ACC and WCC + DAC) save water but often cost more energy and infrastructure; adiabatic solutions (WCC + ADAC) are a flexible middle ground, especially in drier climates. Water-cooled chillers run more efficiently on average than air-cooled ones at a given location because of lower lift and smaller compressors.

Key points

  1. The study covers an 18 MW liquid-cooled module and the heat rejection system upstream of the CDU.
  2. Outdoor loop temperatures: 69.8 °F supply and 87.8 °F return, matching 77 °F supply to the chip.
  3. Four configurations: ACC, WCC + DAC, WCC + ADAC, WCC + CCCT.
  4. Six climates: London, Amsterdam, Dubai, Dulles, Amarillo, Chicago; ASHRAE 2025 bin data.
  5. Load is a constant 100% over 8,760 hours.
  6. Free-cooling chillers are excluded because of about 15% capacity loss and up to 50% higher fan energy.
  7. WCC + CCCT minimizes energy and peak demand; dry systems save water at higher energy and infrastructure cost.
  8. Adiabatic dry coolers are a flexible middle ground, particularly in drier climates.
  9. AFCOM 2026: AI training rack density above 350 kW/rack by 2030; air cooling limit about 50 kW/rack.

Using it in design

  • Select the heat rejection technology by multi-variable comparison of climate, water availability, energy and water cost, electrical capacity and growth plan, not by a single preference.
  • For dry coolers or ACC, compute annual free cooling hours from bin data and check chiller dependence in hot climates.
  • For adiabatic or evaporative options, assess annual water use together with water source and treatment needs.
  • Compare peak electrical demand and the larger footprint of dry systems with layout and grid connection capacity.
  • Because the study assumes 100% load, model part-load and hybrid operating scenarios separately for the project.

Who should read it

Mechanical designers, planners and owners selecting external heat rejection technology for liquid-cooled data centres.

Document contents

  1. Introduction
  2. Climate characterization of study locations
  3. Assumptions, selection methodology and operating logic
  4. Findings by evaluation metric (CAPEX, OPEX, peak demand, water consumption, footprint)
  5. Application of results
  6. Future considerations and expansion of study scope
  7. Appendix

Publication details

Authors
Baltimore Aircoil Company
Publisher
Baltimore Aircoil Company
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

Baltimore Aircoil Company (2026). Evaluating External Heat Rejection Options for Liquid-Cooled Data Center Applications. Baltimore Aircoil Company. https://baltimoreaircoil.com/download_api_endpoint/7080/BAC_D2C%20Data%20Center%20Cooling%20Technologies_WhitePaper-Imperial_USLetter.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.