What do you need to know about designing HVAC systems in data centers? (roundtable)
Consulting-Specifying Engineer · Bill Kosik, Brian Rener et al.
A roundtable in which four mission-critical HVAC engineers share project experience on hot-climate design, air-side economization, unusual heat sinks and the energy-water nexus.
On this page
Overview
This piece is a roundtable discussion published in Consulting-Specifying Engineer in 2023. The participants are Bill Kosik, Brian Rener, Ameya Soparkar and Robert Sty. Four mission-critical HVAC engineers describe recent project experience.
On hot-climate design, a Middle East project is described, designed for 120 F ambient with 95-105 F condenser water, sand-trap louvres and 45-degree underground bends. Phoenix ambient exceeds 115 F; the advice is to relocate air-cooled chillers and generators and to use CFD to avoid exhaust and radiant heat recirculation. The piece also touches on air-side economization with fan-wall air handling units.
Project examples include the University of Utah: up to 10 MW, outside air plus direct evaporative cooling, Tier III, PUE 1.2-1.3, with backup air-cooled chillers running less than 5% of the year. A Korean 10 MW site supplies 75 F and 40% RH via direct outside air, switches to mechanical cooling on Gobi dust events, and reaches PUE 1.25. Colocation chilled water loops are set at 44/56 F for general use and 50/60 F for higher-temperature loops to extend water-side economization.
Unusual heat sinks include snow storage, canal water and in-rack CO2, and thermosyphon coolers are said to perform like towers below about 50 F outdoor temperature with no water use. The discussion also covers the energy-water nexus in drought-restricted regions. As a limit, these are experiences from specific projects and may not apply unchanged in another climate or at another load; they do, however, illustrate with concrete examples the design risks met in hot and arid climates.
Key points
- Middle East project: 120 F ambient, 95-105 F condenser water, sand-trap louvres, 45-degree underground bends.
- Phoenix ambient exceeds 115 F; relocate air-cooled chillers and generators and use CFD to avoid exhaust and radiant heat recirculation.
- University of Utah: up to 10 MW, outside air plus direct evaporative cooling, Tier III, PUE 1.2-1.3, backup chillers run under 5% of the year.
- Korean 10 MW site: 75 F / 40% RH via direct outside air; switches to mechanical cooling on dust events; PUE 1.25.
- Colocation chilled water loops: 44/56 F general and 50/60 F higher-temperature loops to extend water-side economization.
- Thermosyphon coolers perform like towers below about 50 F outdoor with no water use.
- Unusual heat sinks: snow storage, canal water, in-rack CO2.
Using it in design
- Flag hot-climate risks in site design checks: ambient above 115 F, and recirculation between chillers and generator exhaust; suggest CFD.
- Support multiple chilled-water temperature loops per site.
- Report water use alongside energy so dry and evaporative options can be compared.
- For dusty regions, define a changeover scenario to mechanical cooling in the outside-air system.
Who should read it
Mechanical designers doing data center HVAC and site selection in hot and arid climates.
Related standards
- ASHRAE Thermal Guidelines for Data Processing Environments
Publication details
- Authors
- Bill Kosik; Brian Rener; Ameya Soparkar; Robert Sty
- Publisher
- Consulting-Specifying Engineer
- Year
- 2023
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Bill Kosik; Brian Rener; Ameya Soparkar; Robert Sty (2023). What do you need to know about designing HVAC systems in data centers? (roundtable). Consulting-Specifying Engineer. https://www.csemag.com/what-do-you-need-to-know-about-designing-hvac-systems-in-data-centers/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.