How to design data centers: HVAC systems (roundtable)

Consulting-Specifying Engineer · Peter Czerwinski, Garr Di Salvo et al.

A 2021 roundtable in which mission-critical engineers share data centre HVAC project results, with examples from PUE 1.15 down to 1.04 and leak protection.

On this page

Overview

In this 2021 roundtable from Consulting-Specifying Engineer, mission-critical engineers share results from data centre HVAC projects. The first example is a multistory retrofit that reached an annualized PUE of 1.15 using air-cooled chillers with integrated free cooling. The project allowed rack intake up to the A2 limit of 95 F, and the air-cooled chillers gave 100% capacity without compressors at 40 F ambient.

The second example is the 16-year-old Massachusetts Information Technology Center, an existing government data centre where transducers, surveys and modelling cut energy use by 24% and water use by 37%. The third is NREL's ESIF, where water-cooled racks with thermosyphon coolers plus towers achieved PUE 1.04 and halved water use. At the University of Utah, the outside-air economizer is limited by a weather station during high humidity or poor air quality, and PUE stays below 1.3.

Respondents also cover leak protection for piping near IT or electrical equipment and chilled-water return-first strategies to widen delta-T. Piping near IT or electrical equipment needs drip trays with leak detection and spray guards at joints. The piece is a freely accessible expert article, not a standard or calculation method; only the record's summary and key facts were used here and the full text was not read.

Key points

  1. Retrofit allowed rack intake up to the A2 limit of 95 F; air-cooled chillers gave 100% capacity without compressors at 40 F ambient; annualized PUE 1.15.
  2. Massachusetts Information Technology Center (16 years old): 24% energy and 37% water reduction via transducers, surveys and modelling.
  3. NREL ESIF: water-cooled racks with thermosyphon plus towers achieved PUE 1.04 and halved water use.
  4. University of Utah: outside-air economizer limited by a weather station during high humidity or poor air quality; PUE below 1.3.
  5. Piping near IT or electrical equipment needs drip trays with leak detection and spray guards at joints.

Using it in design

  • Compare chillers with integrated free cooling and record the ambient temperature at which free cooling takes over.
  • Apply a rule requiring drip trays with leak detection when chilled-water or liquid-cooling piping routes over IT or electrical equipment.
  • In existing facilities, treat surveys and right-sizing as the first step for energy and water savings.
  • Design the outside-air economizer with limiting logic tied to humidity and air quality.

Who should read it

Mechanical engineers designing, retrofitting or operating data centre HVAC systems.

Related standards

  • ASHRAE Thermal Guidelines for Data Processing Environments

Publication details

Authors
Peter Czerwinski; Garr Di Salvo; Brian Rener; Scott Gatewood
Publisher
Consulting-Specifying Engineer
Year
2021
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Peter Czerwinski; Garr Di Salvo; Brian Rener; Scott Gatewood (2021). How to design data centers: HVAC systems (roundtable). Consulting-Specifying Engineer. https://csemag.com/articles/how-to-design-data-centers-hvac-systems

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.