How to design data centers: HVAC systems (roundtable)
Consulting-Specifying Engineer · Peter Czerwinski, Garr Di Salvo et al.
A 2021 roundtable in which mission-critical engineers share data centre HVAC project results, with examples from PUE 1.15 down to 1.04 and leak protection.
On this page
Overview
In this 2021 roundtable from Consulting-Specifying Engineer, mission-critical engineers share results from data centre HVAC projects. The first example is a multistory retrofit that reached an annualized PUE of 1.15 using air-cooled chillers with integrated free cooling. The project allowed rack intake up to the A2 limit of 95 F, and the air-cooled chillers gave 100% capacity without compressors at 40 F ambient.
The second example is the 16-year-old Massachusetts Information Technology Center, an existing government data centre where transducers, surveys and modelling cut energy use by 24% and water use by 37%. The third is NREL's ESIF, where water-cooled racks with thermosyphon coolers plus towers achieved PUE 1.04 and halved water use. At the University of Utah, the outside-air economizer is limited by a weather station during high humidity or poor air quality, and PUE stays below 1.3.
Respondents also cover leak protection for piping near IT or electrical equipment and chilled-water return-first strategies to widen delta-T. Piping near IT or electrical equipment needs drip trays with leak detection and spray guards at joints. The piece is a freely accessible expert article, not a standard or calculation method; only the record's summary and key facts were used here and the full text was not read.
Key points
- Retrofit allowed rack intake up to the A2 limit of 95 F; air-cooled chillers gave 100% capacity without compressors at 40 F ambient; annualized PUE 1.15.
- Massachusetts Information Technology Center (16 years old): 24% energy and 37% water reduction via transducers, surveys and modelling.
- NREL ESIF: water-cooled racks with thermosyphon plus towers achieved PUE 1.04 and halved water use.
- University of Utah: outside-air economizer limited by a weather station during high humidity or poor air quality; PUE below 1.3.
- Piping near IT or electrical equipment needs drip trays with leak detection and spray guards at joints.
Using it in design
- Compare chillers with integrated free cooling and record the ambient temperature at which free cooling takes over.
- Apply a rule requiring drip trays with leak detection when chilled-water or liquid-cooling piping routes over IT or electrical equipment.
- In existing facilities, treat surveys and right-sizing as the first step for energy and water savings.
- Design the outside-air economizer with limiting logic tied to humidity and air quality.
Who should read it
Mechanical engineers designing, retrofitting or operating data centre HVAC systems.
Related standards
- ASHRAE Thermal Guidelines for Data Processing Environments
Publication details
- Authors
- Peter Czerwinski; Garr Di Salvo; Brian Rener; Scott Gatewood
- Publisher
- Consulting-Specifying Engineer
- Year
- 2021
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Peter Czerwinski; Garr Di Salvo; Brian Rener; Scott Gatewood (2021). How to design data centers: HVAC systems (roundtable). Consulting-Specifying Engineer. https://csemag.com/articles/how-to-design-data-centers-hvac-systems
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.