Reference Design #501: High-Efficiency Cooling for the 1 GW AI Factory

Trane · Trane Technologies

Trane's 2025 reference design splits a 1 GW AI campus into ~100 MW blocks and serves a 13.74 MW air load and 102.4 MW liquid load per block with water-cooled chillers and dry coolers.

On this page

Overview

The document is a 1 GW mechanical cooling blueprint for AI data centers housing NVIDIA racks. It combines air-cooled and direct-to-chip liquid-cooled loads in one plant and gives guidance on chillers, dry coolers, fan coil walls, coolant distribution units (CDUs), pumps and facility piping. It is presented as a mechanical foundation that complements the electrical and controls design.

Design values are given for Albuquerque, New Mexico (1,619 m elevation, 40 °C maximum ambient). In one 100 MW block the air-side load is 13.74 MW (3,906 tons) and the liquid (direct-to-chip) load is 102.4 MW (29,120 tons). The technical loop runs at 30 °C supply and 40 °C return, and the fan coil wall supplies 27 °C air. Facility loops are 22/32 °C for the air load and 26/36 °C for the liquid load.

The central architectural choice is water-cooled centrifugal chillers (CenTraVac CVHH) paired with dry coolers. Dry coolers use no water, so WUE is zero, and the refrigerant is R-1233zd with a GWP of 1. The document argues that water-cooled chillers need fewer units than air-cooled ones, give better PUE, and tolerate airflow loss better because dry coolers and water-cooled plant keep running at reduced capacity.

Later sections cover best practice: decoupled production and distribution loops, single- versus dual-temperature plants, swing chillers that can serve either loop, partitioning into ~100 MW blocks, free cooling, freeze protection and thermal energy storage. The closing sections describe electrical integration with Eaton and Tracer-based controls and cloud services. It is a manufacturer reference design, so equipment choices are based on Trane products.

Key points

  1. Load per 100 MW block: air side 13.74 MW (3,906 tons), liquid side 102.4 MW (29,120 tons).
  2. Load per chiller: 6.87 MW on the medium-temperature (air) loop and 10.24 MW on the high-temperature (liquid) loop; evaporator flow 9,978 and 14,878 LPM respectively.
  3. The heat rejection loop runs between 45.6 °C and 53.3 °C; the chillers operate in a dry-cooler, high-lift application with leaving condenser temperature up to 68.3 °C.
  4. CVHH chillers reach 3,000 tons (11 MW); restart after power loss takes 43 to 76 seconds depending on starter or drive.
  5. Large CDUs deliver up to 14 MW at 4 °C approach with over 90% effectiveness; secondary PG25 supply reaches 45 °C and CDU power draw is below 2% of the load cooled.
  6. The fan coil wall delivers up to 800 kW at over 110K CFM with entering air up to 40 °C; its power draw is below 6% of the load cooled.
  7. The 1 GW campus is split into eight ~100 MW partitions, each served by about 48-inch piping and 11 CDUs (10 MW each) at N+2 redundancy.
  8. A single-temperature plant adds unnecessary lift to the liquid loop and raises energy use; a dual-temperature plant removes that penalty and gives more free-cooling hours on the high-temperature loop.
  9. A thermal energy storage tank can sit on the facility supply, facility return or technical loop supply; a UPS is then needed only for the technical loop.

Using it in design

  • Divide the campus into ~100 MW partitions instead of one chiller plant, and check per partition that pipe, valve and pump sizes stay practical.
  • When the liquid-to-air load ratio is uncertain, assign swing chillers so both loops keep redundancy; this reduces the total chiller count where full dual-loop redundancy is not required.
  • Use a colder dedicated loop (22/32 °C) for air load and a warmer one (26/36 °C) for liquid load to reduce chiller lift and energy.
  • When selecting dry coolers, evaluate local peak dry-bulb temperature and free-cooling modes hour by hour, and plan glycol or heating for freeze protection.
  • For CDUs, specify approach temperature, 40 PSID minimum head, 25-micron secondary filtration and triple-redundant header sensors.
  • Check chiller restart time (43 to 76 seconds) and the location of thermal storage against the heat-up tolerance of the IT load.

Who should read it

Mechanical engineers, consultants and decision makers designing cooling for AI and high-density data centers.

Document contents

  1. Introduction
  2. Design overview
  3. System benefits
  4. Key system components (chillers, dry coolers, fan coil walls, CDUs)
  5. Best practices (decoupled loops, redundancy, block sizing, free cooling, freeze protection, thermal energy storage)
  6. Integrated electrical and power architecture
  7. Controls, monitoring and optimization
  8. System controls and Trane Cloud

Related standards

  • ASHRAE TC 9.9 liquid cooling classes

Publication details

Authors
Trane Technologies
Publisher
Trane
Year
2025
Document number
DC-PRR001D-EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© 2025 Trane. All Rights Reserved (p. 33)

Citation

Trane Technologies (2025). Reference Design #501: High-Efficiency Cooling for the 1 GW AI Factory. Trane. DC-PRR001D-EN. https://www.trane.com/content/dam/Trane/Commercial/global/markets/data-centers/Trane-ReferenceDesign-1GW.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.