Reference Design #501: High-Efficiency Cooling for the 1 GW AI Factory
Trane · Trane Technologies
Trane's 2025 reference design splits a 1 GW AI campus into ~100 MW blocks and serves a 13.74 MW air load and 102.4 MW liquid load per block with water-cooled chillers and dry coolers.
On this page
Overview
The document is a 1 GW mechanical cooling blueprint for AI data centers housing NVIDIA racks. It combines air-cooled and direct-to-chip liquid-cooled loads in one plant and gives guidance on chillers, dry coolers, fan coil walls, coolant distribution units (CDUs), pumps and facility piping. It is presented as a mechanical foundation that complements the electrical and controls design.
Design values are given for Albuquerque, New Mexico (1,619 m elevation, 40 °C maximum ambient). In one 100 MW block the air-side load is 13.74 MW (3,906 tons) and the liquid (direct-to-chip) load is 102.4 MW (29,120 tons). The technical loop runs at 30 °C supply and 40 °C return, and the fan coil wall supplies 27 °C air. Facility loops are 22/32 °C for the air load and 26/36 °C for the liquid load.
The central architectural choice is water-cooled centrifugal chillers (CenTraVac CVHH) paired with dry coolers. Dry coolers use no water, so WUE is zero, and the refrigerant is R-1233zd with a GWP of 1. The document argues that water-cooled chillers need fewer units than air-cooled ones, give better PUE, and tolerate airflow loss better because dry coolers and water-cooled plant keep running at reduced capacity.
Later sections cover best practice: decoupled production and distribution loops, single- versus dual-temperature plants, swing chillers that can serve either loop, partitioning into ~100 MW blocks, free cooling, freeze protection and thermal energy storage. The closing sections describe electrical integration with Eaton and Tracer-based controls and cloud services. It is a manufacturer reference design, so equipment choices are based on Trane products.
Key points
- Load per 100 MW block: air side 13.74 MW (3,906 tons), liquid side 102.4 MW (29,120 tons).
- Load per chiller: 6.87 MW on the medium-temperature (air) loop and 10.24 MW on the high-temperature (liquid) loop; evaporator flow 9,978 and 14,878 LPM respectively.
- The heat rejection loop runs between 45.6 °C and 53.3 °C; the chillers operate in a dry-cooler, high-lift application with leaving condenser temperature up to 68.3 °C.
- CVHH chillers reach 3,000 tons (11 MW); restart after power loss takes 43 to 76 seconds depending on starter or drive.
- Large CDUs deliver up to 14 MW at 4 °C approach with over 90% effectiveness; secondary PG25 supply reaches 45 °C and CDU power draw is below 2% of the load cooled.
- The fan coil wall delivers up to 800 kW at over 110K CFM with entering air up to 40 °C; its power draw is below 6% of the load cooled.
- The 1 GW campus is split into eight ~100 MW partitions, each served by about 48-inch piping and 11 CDUs (10 MW each) at N+2 redundancy.
- A single-temperature plant adds unnecessary lift to the liquid loop and raises energy use; a dual-temperature plant removes that penalty and gives more free-cooling hours on the high-temperature loop.
- A thermal energy storage tank can sit on the facility supply, facility return or technical loop supply; a UPS is then needed only for the technical loop.
Using it in design
- Divide the campus into ~100 MW partitions instead of one chiller plant, and check per partition that pipe, valve and pump sizes stay practical.
- When the liquid-to-air load ratio is uncertain, assign swing chillers so both loops keep redundancy; this reduces the total chiller count where full dual-loop redundancy is not required.
- Use a colder dedicated loop (22/32 °C) for air load and a warmer one (26/36 °C) for liquid load to reduce chiller lift and energy.
- When selecting dry coolers, evaluate local peak dry-bulb temperature and free-cooling modes hour by hour, and plan glycol or heating for freeze protection.
- For CDUs, specify approach temperature, 40 PSID minimum head, 25-micron secondary filtration and triple-redundant header sensors.
- Check chiller restart time (43 to 76 seconds) and the location of thermal storage against the heat-up tolerance of the IT load.
Who should read it
Mechanical engineers, consultants and decision makers designing cooling for AI and high-density data centers.
Document contents
- Introduction
- Design overview
- System benefits
- Key system components (chillers, dry coolers, fan coil walls, CDUs)
- Best practices (decoupled loops, redundancy, block sizing, free cooling, freeze protection, thermal energy storage)
- Integrated electrical and power architecture
- Controls, monitoring and optimization
- System controls and Trane Cloud
Related standards
- ASHRAE TC 9.9 liquid cooling classes
Publication details
- Authors
- Trane Technologies
- Publisher
- Trane
- Year
- 2025
- Document number
- DC-PRR001D-EN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© 2025 Trane. All Rights Reserved (p. 33)
Citation
Trane Technologies (2025). Reference Design #501: High-Efficiency Cooling for the 1 GW AI Factory. Trane. DC-PRR001D-EN. https://www.trane.com/content/dam/Trane/Commercial/global/markets/data-centers/Trane-ReferenceDesign-1GW.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.