Technical guideFree to read2025

Reference Design #504: High-Efficiency Cooling for the 1 GW AI Factory, Air-Cooled Magnetic Bearing Chillers

Original title Reference Design #504: High-Efficiency Cooling for the 1 GW AI Factory - Air-Cooled Magnetic Bearing Chillers

Trane · Trane Technologies

Trane's second 2025 reference design serves a 13.74 MW air and 102.4 MW liquid load per 100 MW block with 3 MW-class air-cooled magnetic-bearing chillers: no cooling towers and a WUE of zero.

On this page

Overview

The document is the air-cooled counterpart of reference design #501 and solves the same 1 GW AI campus with oil-free, magnetic-bearing TCA/TCAB chillers. Load and temperature assumptions are unchanged: 13.74 MW air-side and 102.4 MW liquid-side load per block, a 30/40 °C technical loop, 27 °C fan coil wall supply air, and a 40 °C maximum ambient for Albuquerque.

The air-cooled chillers carry about 2.75 MW on the air loop and 2.93 MW on the liquid loop. Because no condenser-water system or cooling tower is needed, installation and commissioning are simpler and WUE is zero. The document stresses that large packaged units mean fewer chillers and a smaller footprint. Refrigerants are the low-GWP R-515B and R-1234ze.

The central idea is dedicated temperature loops. Liquid load is served on a warmer 26 °C supply loop and the air load on a 22 °C loop. With about 93% of load on the warmer loop, the document reports a 14% cooling system improvement and roughly 35 MW of power available for reallocation versus a single 22 °C baseline loop. These figures come from the manufacturer's own analysis.

It then covers operating strategies: compressor-assisted economizer operation, running circuits at partial capacity, circuit-level unloading and adiabatic pre-cooling. Electrical integration, controls and cloud services follow the same structure as #501. It is a manufacturer reference design based on Trane products.

Key points

  1. Load per chiller: 2.75 MW (781 tons) on the medium-temperature loop and 2.93 MW (832 tons) on the high-temperature loop; evaporator flow 3,941 and 4,200 LPM.
  2. Facility loops: 22 °C supply / 32 °C return for the air load, 26 °C supply / 36 °C return for the liquid load.
  3. TCA chillers reach 850 tons (over 3 MW), operate from -29 to 54 °C ambient and support facility water up to 30 °C.
  4. Restart after power loss takes 160 seconds to reach 80% of full load.
  5. With 93% of load on the 26 °C loop and 7% on the 22 °C fan coil loop, the document cites a 14% cooling system improvement and about 35 MW available to reallocate.
  6. Compressor-assisted economizer operation runs compressors at lower pressure ratios when conditions allow, holding capacity while cutting power, without glycol or free-cooling coils.
  7. An 850-ton unit has two 425-ton circuits; unloading from 850 to 425 tons by running both circuits at about 50% cuts power by about 33% compared with one circuit at full load.
  8. Adiabatic pre-cooling raises condenser performance in hot, dry climates at peak ambient; it either reduces the chiller count or lowers power and sound with the same count.
  9. Freeze protection uses factory heaters down to -20 °F (about -29 °C), heat trace on exposed piping and pumps, and minimum evaporator flow.

Using it in design

  • Compare the air-cooled option with the water-cooled one (#501) on WUE of zero, less site work and faster commissioning where water is scarce or cooling towers are unwanted.
  • Choose separate medium- and high-temperature chillers when load ratios and temperatures are stable and well defined; use swing chillers to share redundancy across both loops when they are not.
  • Operate the chiller array with redundant units running as well: lower load per unit reduces condenser approach and raises efficiency. Optimize together with the generator power allocation.
  • Check the 160-second restart time (to 80% load) against the thermal ride-through of the IT load and any thermal storage.
  • In hot, dry climates, evaluate adiabatic pre-cooling scenario by scenario for first cost, unit count and water use.
  • On sites with freeze risk, include heaters, heat trace and minimum flow control in the specification.

Who should read it

Mechanical engineers and consultants designing the cooling plant of AI and high-density data centers where water use is limited.

Document contents

  1. Introduction
  2. Design overview
  3. System benefits (dedicated temperature loops, token per watt)
  4. Full load reduced lift operation
  5. Key system components (TCDC fan coil walls, CDU, TCA air-cooled chillers)
  6. Best practices (redundancy, freeze protection, thermal energy storage, adiabatic pre-cooling, chiller plant unloading strategy)
  7. Integrated electrical and power architecture
  8. Controls, monitoring and optimization

Publication details

Authors
Trane Technologies
Publisher
Trane
Year
2025
Document number
DC-PRR006D-EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© 2025 Trane. All Rights Reserved (p. 34)

Citation

Trane Technologies (2025). Reference Design #504: High-Efficiency Cooling for the 1 GW AI Factory - Air-Cooled Magnetic Bearing Chillers. Trane. DC-PRR006D-EN. https://www.trane.com/content/dam/Trane/Commercial/global/markets/data-centers/Trane-ReferenceDesign-TCA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.