Cost-Optimal Decarbonization Pathways for Data Centers in Japan: A Bottom-Up Model Integrating Location, Energy Systems, and Carbon Pricing
Energies (MDPI AG) · Jin Toyohara, Weisheng Zhou
A 2026 Energies study finds that in the DC-DECOM model, regional siting of Japanese data centres reaches 2040 net zero at 18-23% lower total system cost than a metropolitan-only scenario.
On this page
Overview
The study presents a bottom-up cost optimisation model (DC-DECOM) aiming for carbon neutrality of the information and communications technology (ICT) sector in Japan's data-centre industry by 2040. The model represents PUE as a dynamic function of ambient temperature and cooling technology and combines technology selection, regional energy supply and carbon pricing in one cost-minimisation framework.
Three scenarios are compared: a reference case (REF), a centralised carbon-neutral scenario (C-CN) restricting new capacity to metropolitan areas, and a regional decentralisation scenario (R-CN) allowing nationwide siting. Inputs are calibrated against IEA, Uptime Institute, Japan's Ministry of Internal Affairs and Communications white papers and JST data.
R-CN reaches the 2040 net-zero target at 18-23% lower total system cost than C-CN. The gap splits into four channels: cooling-energy reduction about 35%, lower regional renewable procurement cost about 30%, lower carbon cost about 25% and lower siting cost about 10%. Sensitivity analysis identifies the carbon-price trajectory and hardware-efficiency improvement rate as the most influential parameters. Results are scenario projections, not measured results from actual Japanese facilities.
Key points
- Target: carbon neutrality of Japan's ICT sector by 2040; the model is called DC-DECOM.
- PUE is modelled as a function of ambient temperature and cooling technology.
- Three scenarios: REF, metropolitan-only C-CN and nationwide R-CN.
- R-CN gives 18-23% lower total system cost than C-CN.
- Gap channels: cooling energy ~35%, regional renewable procurement ~30%, carbon cost ~25%, siting cost ~10%.
- Carbon-price trajectory and hardware-efficiency improvement rate are the most influential parameters; the R-CN advantage stays positive across ±1σ variations and two combined stress tests.
Using it in design
- In multi-region capacity planning, model PUE as a function of ambient temperature and cooling technology rather than a constant.
- Compare cooling energy, regional renewable procurement and carbon cost in one cost model when choosing locations.
- Run sensitivities on carbon price and hardware-efficiency improvement rate.
- Use the scenario results as planning indicators, not as measured facility data.
Who should read it
Data-centre strategists, energy analysts and sustainability consultants working on capacity and location planning.
Publication details
- Authors
- Jin Toyohara; Weisheng Zhou
- Publisher
- Energies (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Jin Toyohara; Weisheng Zhou (2026). Cost-Optimal Decarbonization Pathways for Data Centers in Japan: A Bottom-Up Model Integrating Location, Energy Systems, and Carbon Pricing. Energies (MDPI AG). https://doi.org/10.3390/en19102485
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.