Necron 3DT Series 10-15-20 kVA Online UPS Datasheet

Original title Necron 3DT series 10-15-20 kVA

Necron

Necron's 3DT series, in 10, 15 and 20 kVA, is a double-conversion UPS with three-phase input and single-phase output; the manufacturer sheet gives power, efficiency, battery and environmental ratings.

On this page

Overview

Necron 3DT is a family of tower-type true online double-conversion UPS units built for mid-range office applications, automation and high-technology loads such as CT scan monitoring. Its distinguishing feature is three-phase input with single-phase output. A DSP-controlled microprocessor shortens the response time to input fluctuations and the unit handles unbalanced loads and frequency or voltage ripple.

The sheet gives three models in one table: 10 kVA / 9 kW, 15 kVA / 13.5 kW and 20 kVA / 18 kW, with an output power factor of 0.9. Efficiency exceeds 92% in mains mode and 90% in battery mode at 100% load. The input phase voltage range is 120±5 to 274±5 VAC and the bypass range is 60±5 to 300±5 VAC. Output THDv is below 2% on linear load and below 5% on non-linear load.

On dependability, MTBF is above 210,000 hours and MTTR below 30 minutes. Parallel operation supports N+1 and N+X with up to 6 units. Battery voltage is 192 VDC. Operating temperature is 0 to 40 °C with 15 to 25 °C recommended, altitude is below 1000 m and noise is under 65 dBA at 1 m. The document is a product sheet; runtime tables, system topology and installation detail are outside its scope.

Key points

  1. Three models: 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW; output power factor 0.9.
  2. Efficiency: above 92% in mains mode and above 90% in battery mode at 100% load.
  3. Input 380/220 VAC, 50 Hz; frequency window 46 to 54 Hz; input power factor 0.95.
  4. Output voltage selectable 208/220/230/240 VAC, accuracy ±1%; THDv below 2% on linear load.
  5. Overload: 30 s at 105 to 125%, 300 ms at 125 to 135% before the bypass alarm.
  6. Battery voltage 192 VDC; paralleling N+1 and N+X, up to 6 units.
  7. MTBF above 210,000 hours, MTTR below 30 minutes.
  8. Operation 0 to 40 °C, relative humidity 20 to 95% non-condensing, altitude below 1000 m.

Using it in design

  • The 3-in/1-out structure suits single-phase critical loads only; check phase balance and input draw at the distribution board separately.
  • With a 0.9 output power factor, size by kW rather than kVA: the 20 kVA model carries 18 kW.
  • Account for the 192 VDC string voltage and an external battery cabinet in battery calculations; take runtime from the battery manufacturer's tables.
  • For higher redundancy, plan an N+1 parallel set of up to 6 units and write the optional manual bypass switch into the specification.
  • Use the recommended 15 to 25 °C operating range as the cooling design target.

Who should read it

Electrical engineers and procurement teams selecting small and mid-size UPS units.

Document contents

  1. General
  2. Efficiency
  3. Input
  4. Output
  5. Battery
  6. Communication
  7. Environment
  8. Standards
  9. Dimensions and weight

Publication details

Authors
Necron
Publisher
Necron
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Necron Necron 3DT series 10-15-20 kVA. Necron. https://www.necron.com.tr/images/products/975513DT_Series.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.