Necron 3DT Series 10-15-20 kVA Online UPS Datasheet
Original title Necron 3DT series 10-15-20 kVA
Necron
Necron's 3DT series, in 10, 15 and 20 kVA, is a double-conversion UPS with three-phase input and single-phase output; the manufacturer sheet gives power, efficiency, battery and environmental ratings.
On this page
Overview
Necron 3DT is a family of tower-type true online double-conversion UPS units built for mid-range office applications, automation and high-technology loads such as CT scan monitoring. Its distinguishing feature is three-phase input with single-phase output. A DSP-controlled microprocessor shortens the response time to input fluctuations and the unit handles unbalanced loads and frequency or voltage ripple.
The sheet gives three models in one table: 10 kVA / 9 kW, 15 kVA / 13.5 kW and 20 kVA / 18 kW, with an output power factor of 0.9. Efficiency exceeds 92% in mains mode and 90% in battery mode at 100% load. The input phase voltage range is 120±5 to 274±5 VAC and the bypass range is 60±5 to 300±5 VAC. Output THDv is below 2% on linear load and below 5% on non-linear load.
On dependability, MTBF is above 210,000 hours and MTTR below 30 minutes. Parallel operation supports N+1 and N+X with up to 6 units. Battery voltage is 192 VDC. Operating temperature is 0 to 40 °C with 15 to 25 °C recommended, altitude is below 1000 m and noise is under 65 dBA at 1 m. The document is a product sheet; runtime tables, system topology and installation detail are outside its scope.
Key points
- Three models: 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW; output power factor 0.9.
- Efficiency: above 92% in mains mode and above 90% in battery mode at 100% load.
- Input 380/220 VAC, 50 Hz; frequency window 46 to 54 Hz; input power factor 0.95.
- Output voltage selectable 208/220/230/240 VAC, accuracy ±1%; THDv below 2% on linear load.
- Overload: 30 s at 105 to 125%, 300 ms at 125 to 135% before the bypass alarm.
- Battery voltage 192 VDC; paralleling N+1 and N+X, up to 6 units.
- MTBF above 210,000 hours, MTTR below 30 minutes.
- Operation 0 to 40 °C, relative humidity 20 to 95% non-condensing, altitude below 1000 m.
Using it in design
- The 3-in/1-out structure suits single-phase critical loads only; check phase balance and input draw at the distribution board separately.
- With a 0.9 output power factor, size by kW rather than kVA: the 20 kVA model carries 18 kW.
- Account for the 192 VDC string voltage and an external battery cabinet in battery calculations; take runtime from the battery manufacturer's tables.
- For higher redundancy, plan an N+1 parallel set of up to 6 units and write the optional manual bypass switch into the specification.
- Use the recommended 15 to 25 °C operating range as the cooling design target.
Who should read it
Electrical engineers and procurement teams selecting small and mid-size UPS units.
Document contents
- General
- Efficiency
- Input
- Output
- Battery
- Communication
- Environment
- Standards
- Dimensions and weight
Publication details
- Authors
- Necron
- Publisher
- Necron
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Necron Necron 3DT series 10-15-20 kVA. Necron. https://www.necron.com.tr/images/products/975513DT_Series.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.