Necron DTK Series 1-2-3 kVA Online UPS Technical Specifications

Original title Necron DTK series 1-2-3 kVA technical specifications

Necron

Necron DTK is a 1, 2 and 3 kVA double-conversion UPS family with unity output power factor; the sheet gives 0 ms battery transfer, 97% efficiency in ECO mode and charging current up to 12 A.

On this page

Overview

Necron DTK is a DSP-microprocessor online double-conversion UPS series for home, office and laboratory loads. The manufacturer says it makes standard many features competitors sell as options, offers more kW through a 1.0 output power factor and, with up to 12 A standard charging, gives a base for long backup times.

The sheet covers the 1, 2 and 3 kVA models in standard and long-backup (L) versions in one table. Input voltage is 100 to 300 VAC, frequency 40 to 70 Hz and input power factor above 0.99; output voltage is 208/220/230/240 VAC. Efficiency is ≥93% to ≥94.5% in line mode and ≥97% in ECO mode. Transfer from line to battery is 0 ms and from inverter to bypass is typically 4 ms.

Battery voltage is 36, 48, 72 or 96 VDC depending on the model, with external batteries. Charging current is 1 to 4 A or 1 to 12 A depending on model. Operating temperature is 0 to 40 °C, noise is below 50 dB at 1 m and altitude is 1000 m without derating. The document is a product sheet and has no system-design guidance or runtime tables.

Key points

  1. Capacity 1 kVA / 1 kW, 2 kVA / 2 kW and 3 kVA / 3 kW; output power factor 1.0, pure sine wave.
  2. Input 100 to 300 VAC, 40 to 70 Hz, power factor above 0.99, THDi below 4% on linear load.
  3. Efficiency: ≥93% to ≥94.5% in line mode, ≥97% in ECO mode.
  4. Transfer: line to battery 0 ms, inverter to bypass typically 4 ms.
  5. Overload in line mode: up to 30 min at 102 to 110%, 10 min at 110 to 130%.
  6. Battery 36, 48, 72 or 96 VDC; charging current 1 to 12 A; two/three-stage charging.
  7. Communication RS232/USB; SNMP card and dry-contact kit optional.
  8. Operation 0 to 40 °C, humidity 0 to 95% non-condensing, noise below 50 dB.

Using it in design

  • With a 1.0 output power factor, kVA equals kW; size directly against load kW.
  • For long-backup (L) models, match the external battery voltage and the 12 A charging current to the battery capacity.
  • ECO mode lifts efficiency to 97%, but the load then runs from bypass; check the load's tolerance for the 4 ms transfer.
  • Add the SNMP card to the specification for monitoring alongside RS232/USB.

Who should read it

Engineers and buyers selecting UPS units for small critical loads such as network cabinets, labs and offices.

Document contents

  1. Input
  2. Output
  3. Efficiency
  4. Battery
  5. Management
  6. Environment
  7. Standards and approvals
  8. Physical

Publication details

Authors
Necron
Publisher
Necron
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Necron Necron DTK series 1-2-3 kVA technical specifications. Necron. https://www.necron.com.tr/images/products/68735DTK_Series_1-2-3kVA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.