Necron DTK Series 1-2-3 kVA Online UPS Technical Specifications
Original title Necron DTK series 1-2-3 kVA technical specifications
Necron
Necron DTK is a 1, 2 and 3 kVA double-conversion UPS family with unity output power factor; the sheet gives 0 ms battery transfer, 97% efficiency in ECO mode and charging current up to 12 A.
On this page
Overview
Necron DTK is a DSP-microprocessor online double-conversion UPS series for home, office and laboratory loads. The manufacturer says it makes standard many features competitors sell as options, offers more kW through a 1.0 output power factor and, with up to 12 A standard charging, gives a base for long backup times.
The sheet covers the 1, 2 and 3 kVA models in standard and long-backup (L) versions in one table. Input voltage is 100 to 300 VAC, frequency 40 to 70 Hz and input power factor above 0.99; output voltage is 208/220/230/240 VAC. Efficiency is ≥93% to ≥94.5% in line mode and ≥97% in ECO mode. Transfer from line to battery is 0 ms and from inverter to bypass is typically 4 ms.
Battery voltage is 36, 48, 72 or 96 VDC depending on the model, with external batteries. Charging current is 1 to 4 A or 1 to 12 A depending on model. Operating temperature is 0 to 40 °C, noise is below 50 dB at 1 m and altitude is 1000 m without derating. The document is a product sheet and has no system-design guidance or runtime tables.
Key points
- Capacity 1 kVA / 1 kW, 2 kVA / 2 kW and 3 kVA / 3 kW; output power factor 1.0, pure sine wave.
- Input 100 to 300 VAC, 40 to 70 Hz, power factor above 0.99, THDi below 4% on linear load.
- Efficiency: ≥93% to ≥94.5% in line mode, ≥97% in ECO mode.
- Transfer: line to battery 0 ms, inverter to bypass typically 4 ms.
- Overload in line mode: up to 30 min at 102 to 110%, 10 min at 110 to 130%.
- Battery 36, 48, 72 or 96 VDC; charging current 1 to 12 A; two/three-stage charging.
- Communication RS232/USB; SNMP card and dry-contact kit optional.
- Operation 0 to 40 °C, humidity 0 to 95% non-condensing, noise below 50 dB.
Using it in design
- With a 1.0 output power factor, kVA equals kW; size directly against load kW.
- For long-backup (L) models, match the external battery voltage and the 12 A charging current to the battery capacity.
- ECO mode lifts efficiency to 97%, but the load then runs from bypass; check the load's tolerance for the 4 ms transfer.
- Add the SNMP card to the specification for monitoring alongside RS232/USB.
Who should read it
Engineers and buyers selecting UPS units for small critical loads such as network cabinets, labs and offices.
Document contents
- Input
- Output
- Efficiency
- Battery
- Management
- Environment
- Standards and approvals
- Physical
Publication details
- Authors
- Necron
- Publisher
- Necron
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Necron Necron DTK series 1-2-3 kVA technical specifications. Necron. https://www.necron.com.tr/images/products/68735DTK_Series_1-2-3kVA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.