Necron HT Series 10-15-20-30 kVA 3/3 Online UPS Technical Sheet

Original title Necron HT series 10-15-20-30 kVA

Necron

Technical sheet for Necron's HT series of 10, 15, 20 and 30 kVA three-phase online UPS: 0.9 output power factor, 0.99 input power factor, up to 98% efficiency in ECO mode and parallel operation of up to 6 units.

On this page

Overview

The sheet lists the Necron HT models of 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW and 30 kVA / 27 kW in one table. The series is a DSP-controlled, double-conversion UPS family with active power factor correction (APFC) and three-phase input and output. Dual input (separate mains and bypass feeds), an LCD+LED display and load-dependent fan speed are standard.

On the input side the nominal voltage is 360/380/400/415 V AC (3Ph+N+PE) with an input power factor of 0.99 or better; the voltage window is 277-485 V AC at 50-100% load and 190-277 V AC at lower load. At the output, regulation is ±1%, crest factor 3:1, and THDv is at most 2% on linear and 5% on non-linear load. Transfer time from mains to battery and from inverter to bypass is 0 ms.

On the battery side the standard model uses a 240 V DC bus and the long-backup (batteryless) model a 192 V DC bus (192/216/240 V optional); the battery count can be set to 14/16/18/20. Standard models with internal batteries range from 20x9 Ah to 60x9 Ah. Efficiency is at least 93% in mains mode and at least 98% in ECO mode. The sheet is a short product leaflet and gives no autonomy curves or heat-load tables.

Overload behaviour is defined per band, and the document also lists the communication options and the physical data for both the long-backup and the standard internal-battery versions, which is enough for early-stage room and cabinet planning.

Key points

  1. Four ratings: 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW, 30 kVA / 27 kW; output power factor 0.9.
  2. Input power factor 0.99 or better; input frequency range 40-70 Hz; bypass voltage window -40% / +15% (adjustable).
  3. Output regulation ±1%; THDv at most 2% (linear) and 5% (non-linear); crest factor 3:1.
  4. Overload: 102-125% for 10 min, 125-150% for 1 min, above 150% transfer to bypass after 0.5 s.
  5. Efficiency: at least 93% in mains mode, at least 98% in ECO mode.
  6. Optional parallel operation of up to 6 units; RS232/USB/EPO standard, RS485/AS400/SNMP optional.
  7. Dimensions 350x655x732 mm (batteryless L model); net weight 55-65 kg without batteries, 110-235 kg with internal batteries; IP20, noise at most 60-65 dB (1 m).
  8. Operating temperature 0-40 °C, relative humidity below 95% non-condensing.

Using it in design

  • Compare load in kW using the 0.9 output power factor: the 30 kVA model is 27 kW of real capacity.
  • If parallel redundancy is needed, record the 6-unit limit and N+1 load sharing in the capacity plan.
  • For the long-backup model, match the 192/216/240 V DC battery bus option to the external battery cabinet design.
  • With IP20 protection and a 0-40 °C range, place the unit in a controlled electrical room.
  • Use the overload bypass thresholds (10 min at 102-125%) in the protection selectivity study.

Who should read it

Electrical designers and specifiers selecting small and medium three-phase UPS systems.

Document contents

  1. Features
  2. Technical Specifications (input, output, battery, system, other)

Publication details

Authors
Necron
Publisher
Necron
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Necron Necron HT series 10-15-20-30 kVA. Necron. https://www.necron.com.tr/images/products/77242HT_Serisi.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.