Necron HT Series 10-15-20-30 kVA 3/3 Online UPS Technical Sheet
Original title Necron HT series 10-15-20-30 kVA
Necron
Technical sheet for Necron's HT series of 10, 15, 20 and 30 kVA three-phase online UPS: 0.9 output power factor, 0.99 input power factor, up to 98% efficiency in ECO mode and parallel operation of up to 6 units.
On this page
Overview
The sheet lists the Necron HT models of 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW and 30 kVA / 27 kW in one table. The series is a DSP-controlled, double-conversion UPS family with active power factor correction (APFC) and three-phase input and output. Dual input (separate mains and bypass feeds), an LCD+LED display and load-dependent fan speed are standard.
On the input side the nominal voltage is 360/380/400/415 V AC (3Ph+N+PE) with an input power factor of 0.99 or better; the voltage window is 277-485 V AC at 50-100% load and 190-277 V AC at lower load. At the output, regulation is ±1%, crest factor 3:1, and THDv is at most 2% on linear and 5% on non-linear load. Transfer time from mains to battery and from inverter to bypass is 0 ms.
On the battery side the standard model uses a 240 V DC bus and the long-backup (batteryless) model a 192 V DC bus (192/216/240 V optional); the battery count can be set to 14/16/18/20. Standard models with internal batteries range from 20x9 Ah to 60x9 Ah. Efficiency is at least 93% in mains mode and at least 98% in ECO mode. The sheet is a short product leaflet and gives no autonomy curves or heat-load tables.
Overload behaviour is defined per band, and the document also lists the communication options and the physical data for both the long-backup and the standard internal-battery versions, which is enough for early-stage room and cabinet planning.
Key points
- Four ratings: 10 kVA / 9 kW, 15 kVA / 13.5 kW, 20 kVA / 18 kW, 30 kVA / 27 kW; output power factor 0.9.
- Input power factor 0.99 or better; input frequency range 40-70 Hz; bypass voltage window -40% / +15% (adjustable).
- Output regulation ±1%; THDv at most 2% (linear) and 5% (non-linear); crest factor 3:1.
- Overload: 102-125% for 10 min, 125-150% for 1 min, above 150% transfer to bypass after 0.5 s.
- Efficiency: at least 93% in mains mode, at least 98% in ECO mode.
- Optional parallel operation of up to 6 units; RS232/USB/EPO standard, RS485/AS400/SNMP optional.
- Dimensions 350x655x732 mm (batteryless L model); net weight 55-65 kg without batteries, 110-235 kg with internal batteries; IP20, noise at most 60-65 dB (1 m).
- Operating temperature 0-40 °C, relative humidity below 95% non-condensing.
Using it in design
- Compare load in kW using the 0.9 output power factor: the 30 kVA model is 27 kW of real capacity.
- If parallel redundancy is needed, record the 6-unit limit and N+1 load sharing in the capacity plan.
- For the long-backup model, match the 192/216/240 V DC battery bus option to the external battery cabinet design.
- With IP20 protection and a 0-40 °C range, place the unit in a controlled electrical room.
- Use the overload bypass thresholds (10 min at 102-125%) in the protection selectivity study.
Who should read it
Electrical designers and specifiers selecting small and medium three-phase UPS systems.
Document contents
- Features
- Technical Specifications (input, output, battery, system, other)
Publication details
- Authors
- Necron
- Publisher
- Necron
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Necron Necron HT series 10-15-20-30 kVA. Necron. https://www.necron.com.tr/images/products/77242HT_Serisi.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.