Sacred Sun SHUIFP512100D high-voltage UPS LFP battery system (Sun Pulse series)

Original title Sun Pulse SHUIFP512100D lithium UPS battery

Sacred Sun

Sacred Sun SHUIFP512100D is a 512 V 100 Ah (51.2 kWh) LFP high-voltage UPS battery system: 228.16 kW constant power for 10 minutes, 98.4 kW for 30 minutes, over 2500 cycles.

On this page

Overview

The brochure presents Shandong Sacred Sun's Sun Pulse series high-voltage UPS lithium battery system. The system uses LFP cells for UPS, communication and energy storage, and with its medium and high rate cells is recommended for emergency backup of 15 minutes and above (advised back-up time at least 15 min). Compared with a lead-acid VS battery, it states over 50% smaller footprint, over 70% lighter weight and over 70% higher power density.

System parameters: rated voltage 512 V, capacity 100 Ah, energy 51.2 kWh, voltage range 432-584 V, cell 3.2 V 50 Ah (160S2P). Maximum discharge current is 550 A, maximum charge current 50 A, and cycle life is over 2500 at 25 °C, 0.5C/1C, 100% DOD. Constant power and current: 228.16 kW (490 A) for 10 min, 186.08 kW (400 A) for 15 min, 98.4 kW (200 A) for 30 min, 65.7 kW (133.3 A) for 45 min and 50.25 kW (100 A) for 60 min. Output at 5.5C and 2.7 V per cell is 220 kW.

Safety and management: a three-layer BMS (a BMU in each pack, a BCU in each cabinet, a BAU for the system) monitors cell temperature and voltage, prevents overcharge and over-discharge, and keeps deviation between series strings below 2%. There is four-level protection (cell, module, rack, system) and a built-in fire protection system. Listed features include intelligent detachment from clusters with online maintenance, a dual power supply mode and no need for float charging.

Physical and environmental data: cabinet 600x1000x2000 mm, system weight about 797 kg, pack 440x820x133 mm; discharge temperature -20 to 50 °C (recommended 5-40 °C), charge temperature 0-45 °C (recommended 15-30 °C), humidity below 95% non-condensing and IP20 protection. Communication is CAN2.0, RS485, dry contact and Modbus IP; perfluorohexanone or S-type aerosol (optional) is listed for fire fighting. Certification is UN38.3.

Key points

  1. Rated 512 V, 100 Ah, 51.2 kWh; voltage range 432-584 V; cell 3.2 V 50 Ah, 160S2P.
  2. Constant power: 10 min 228.16 kW, 15 min 186.08 kW, 30 min 98.4 kW, 45 min 65.7 kW, 60 min 50.25 kW.
  3. Constant current: 490, 400, 200, 133.3 and 100 A (10, 15, 30, 45, 60 min).
  4. Maximum discharge current 550 A, maximum charge current 50 A; cycles >2500 (25 °C, 0.5C/1C, 100% DOD).
  5. Cabinet 600x1000x2000 mm, weight about 797 kg; IP20.
  6. Discharge -20 to 50 °C (recommended 5-40 °C); charge 0-45 °C (recommended 15-30 °C).
  7. Three-layer BMS (BMU, BCU, BAU); string deviation below 2%.
  8. Over 50% smaller footprint and over 70% lighter than lead-acid (manufacturer's claim).
  9. CAN2.0/RS485/dry contact/Modbus IP; fire fighting: perfluorohexanone or S-type aerosol.

Using it in design

  • Compare the load against the 10, 15, 30, 45 and 60 minute table values to set the cabinet count; a load above 186 kW for 15 minutes, for example, needs parallel cabinets.
  • Confirm that the UPS DC bus voltage fits the 432-584 V range and the 50 A maximum charge current.
  • Enter the roughly 797 kg cabinet weight and the 600x1000 mm footprint in the floor-loading calculation of the battery room.
  • Design cooling to keep the room within the recommended charge (15-30 °C) and discharge (5-40 °C) ranges.
  • Align the perfluorohexanone or S-type aerosol option with the battery room fire design and local regulation.
  • Add the BMS communication (CAN2.0/RS485/Modbus IP) to the UPS and BMS/DCIM integration plan.

Who should read it

Electrical designers and operations teams selecting high-voltage lithium UPS battery systems for data centres and financial institutions.

Document contents

  1. Overview and applications
  2. BMS function (three layers)
  3. Performance data
  4. System parameters
  5. Work conditions and communication
  6. Certification and firefighting

Publication details

Authors
Sacred Sun
Publisher
Sacred Sun
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sacred Sun Sun Pulse SHUIFP512100D lithium UPS battery. Sacred Sun. https://www.sacredsun.com/uploads/soft/250715/1-250G5163504.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.