SafeCore SC-100 high-voltage lithium UPS battery
Sacred Sun
Sacred Sun's SafeCore SC-100 is a 512 V 50 Ah LFP UPS battery cabinet built from 6C high-rate cells: up to 97.6 kW continuous, 15 minutes of backup, 600 x 1000 x 2000 mm, about 500 kg.
On this page
Overview
Sacred Sun's SC-100 data sheet presents a high-voltage lithium iron phosphate (LFP) battery system for UPS, communication and energy storage. Medium and high rate cells are aimed at emergency backup of 15 minutes and more, and customised solutions are available. The system code is SHUIFP51250D (512 V 50 Ah).
System parameters: rated voltage 512 V, capacity 50 Ah, voltage range 432-576 V, 160 cells in series, peak discharge current 250 A, maximum continuous output power 97.6 kW and backup time of at least 15 minutes. The build is 1 master and 10 slave packs; the pack is 440 x 470 x 133 mm, the HV box 440 x 680 x 222 mm, the cabinet 600 x 1000 x 2000 mm and the system weighs 500 ± 10 kg.
The performance table gives backup time at constant power: 97.6 kW (200 A) for 15 minutes and 49.3 kW (100 A) for 30 minutes. Discharge temperature is -20 to 45 °C (recommended 5-40 °C) and charge temperature 0-45 °C (recommended 15-30 °C). Communication is CAN2.0/RS485, protection is IP20, fire suppression is perfluorohexanone or S-type aerosol (optional) and certification is UN38.3. The sheet also has cell discharge curves and a 4C cycle life curve.
Key points
- System: 512 V, 50 Ah, 160 cells in series, voltage range 432-576 V.
- Peak discharge current 250 A; maximum continuous output power 97.6 kW; backup time ≥ 15 minutes.
- Constant power: 97.6 kW (200 A) for 15 min, 49.3 kW (100 A) for 30 min.
- Build: 1 master + 10 slave packs; pack 440 x 470 x 133 mm; HV box 440 x 680 x 222 mm.
- Cabinet 600 x 1000 x 2000 mm; system weight 500 ± 10 kg; IP20.
- Discharge -20 to 45 °C (recommended 5-40 °C); charge 0-45 °C (recommended 15-30 °C).
- Communication CAN2.0 / RS485; fire suppression perfluorohexanone or S-type aerosol (optional).
- Certification UN38.3; 6C high-rate LFP cell, modular structure for expansion.
Using it in design
- For a 15-minute backup target, compare UPS DC power with the 97.6 kW cabinet limit and compute parallel cabinets for higher power, noting the fall to 49.3 kW per cabinet at 30 minutes.
- Verify the UPS DC bus voltage window (432-576 V, 512 V nominal) against the battery range the UPS maker accepts.
- Put the 500 kg weight and 600 x 1000 mm footprint into layout and floor loading; take access dimensions for the HV box and packs from the cabinet data.
- Write the 0-45 °C charge limit and recommended 15-30 °C range into the battery room climate design.
- Match the fire suppression method (perfluorohexanone or aerosol) to local fire and lithium battery rules.
Who should read it
Data centre electrical designers and specification engineers selecting high-voltage lithium UPS battery systems.
Document contents
- Overview
- System parameters
- Work conditions and communication
- Features
- Certification
- Performance data and curves
Publication details
- Authors
- Sacred Sun
- Publisher
- Sacred Sun
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sacred Sun SafeCore SC-100 high-voltage lithium UPS battery. Sacred Sun. https://www.sacredsun.com/uploads/soft/260223/1-2602231PS0.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.