Technical guideFree to readYear not stated

HPPL12-360W High-Purity Lead Battery (Sacredsun, 12 V 90 Ah)

Original title HPPL12-360W high-purity lead battery

Sacred Sun

The Sacredsun HPPL12-360W is a thin plate pure lead (TPPL) 12 V / 90 Ah (10 h) battery for UPS and data centres with a 15-year design life, 445 W per cell at 10 minutes (1.67 V) and 3.2 mΩ internal resistance.

On this page

Overview

The document is the datasheet of the HPPL12-360W from Sacredsun's HPPL series. The thin plate pure lead (TPPL) technology is presented as a high-power, high-energy, long-life design for UPS and telecom use; the pure lead grid's corrosion resistance gives a long float life and endurance at elevated temperature. Listed benefits include design for high-rate discharge, faster recharge, high power density, 15-year design life at 25 °C, shelf life up to 2 years, an operating range of -40 to +60 °C, a PC-ABS UL94-V0 flame-retardant container and upright installation. Applications are UPS, data centres, renewable energy, emergency power and electrical facilities; standards are IEC 60896-21/22:2004, JIS C8704-1/2:2006 and the EUROBAT guide.

Technical values: capacity of 445 W/cell for 10 min (1.67 V), 360 W/cell for 15 min, 59.4 A for 1 h (1.80 V) and 90 Ah (9.0 A) for 10 h. Size is 341 x 173 x 213 mm (220 mm total height), weight about 27.8 kg, internal resistance 3.2 mΩ (fully charged, 25 °C), maximum discharge current 1080 A (5 s), short-circuit current 3800 A and self-discharge below 2% per month. Charge voltage is 2.35 V per cell for cycle use (maximum charge current 54 A) and 2.23 V per cell for float, both with -3 mV/°C/cell compensation.

The rest of the sheet gives constant-current and constant-power discharge tables for end voltages of 1.60-1.80 V per cell from 10 minutes to 10 hours. For example at 1.67 V per cell, 10 minutes gives 243.1 A and 445.0 W per cell, and 15 minutes gives 191.6 A and 360.0 W per cell.

Key points

  1. 12 V, 90 Ah (10 h, 9.0 A, 1.80 V); 59.4 A for 1 h (1.80 V).
  2. Constant power (1.67 V per cell): 445 W per cell (10 min), 360 W per cell (15 min).
  3. Design life 15 years (25 °C); shelf life up to 2 years; operating -40 to +60 °C.
  4. Size 341 x 173 x 220 mm (total height); weight about 27.8 kg.
  5. Internal resistance 3.2 mΩ; maximum discharge current 1080 A (5 s); short-circuit current 3800 A.
  6. Float 2.23 V per cell; cycle 2.35 V per cell (maximum 54 A); compensation -3 mV/°C/cell.
  7. Self-discharge below 2% per month; PC-ABS UL94-V0 container.
  8. Standards: IEC 60896-21/22:2004, JIS C8704-1/2:2006, EUROBAT.

Using it in design

  • For UPS autonomy, compute the required cells and blocks from the 10 and 15 minute watts-per-cell values in the table.
  • Set charger float to 2.23 V per cell with -3 mV/°C/cell compensation.
  • Feed the 3800 A short-circuit current and 1080 A maximum discharge current into DC protective device breaking capacity and selectivity studies.
  • Correct the 15-year design life for actual operating temperature and plan replacement accordingly.

Who should read it

Electrical engineers designing data-centre UPS battery banks.

Document contents

  1. Benefits
  2. Applications and standards
  3. Specifications
  4. Constant current discharge data
  5. Constant power discharge data

Publication details

Authors
Sacred Sun
Publisher
Sacred Sun
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sacred Sun HPPL12-360W high-purity lead battery. Sacred Sun. https://www.sacredsun.com/uploads/soft/210524/1-210524100512.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.