Technical guideFree to read2013

Legrand Power Protection Guide: factory-assembled MCCB ATS

Legrand

Legrand's 2013 residential and commercial power protection guide lists factory-assembled and tested automatic transfer switches (ATS) built on DPX3 and DPX moulded case circuit breakers from 16 A to 630 A: 37 ready-made assemblies, each ordered under one catalogue number, with breaking capacities of 25, 36, 50 and 70 kA.

On this page

Overview

The guide is a broad product catalogue covering Legrand air circuit breakers (DMX3), moulded case breakers (DPX3, DPX), miniature breakers, residual current devices, time switches and energy metering. The part relevant to data-centre design is the moulded case automatic transfer switch section on pages 102 and 103. These assemblies change over automatically from the main source to a standby supply when power fails, and the document names hospitals, airports, tunnels, manufacturing plants and data centres among the applications.

Each ATS assembly has three parts: two motor-operated moulded case breakers on a mechanical interlock plate (the basic transfer switch), a pre-wired control panel mounted on a metal plate, and a controller. The breakers carry a 230 V AC/DC shunt release, a value that belongs to the auxiliary circuit. The control panel connects to the controller and the breakers through plug-in wire looms. A common load-side busbar is available on request. All assemblies use 3 pole breakers.

The catalogue number combines frame size, pole count, breaking capacity and nominal current in one code: ATS 160 3P 25kA 25, for example, is a DPX3 160 frame, 3 pole, 25 kA, 25 A assembly. The DPX3 160 series has 17 assemblies from 25 A to 160 A, the DPX3 250 series 12 assemblies from 100 A to 250 A, and the DPX 630 series 8 assemblies at 400 A and 630 A with thermal magnetic or electronic trip units.

Transfer logic is shown as a flow chart. When the main source voltage disappears, a confirmation delay adjustable from 0.1 to 10 s runs, the main breaker opens, and after a second delay of 0.5 to 120 s the standby breaker closes. When the main source returns, a wait of 3 to 120 s is followed by a changeover delay of 0.5 to 120 s. For DMX3 air circuit breakers the same function is provided by the microprocessor control unit Cat. No. 261 93 and a cable-operated mechanical interlock.

Key points

  1. The factory-assembled MCCB ATS range runs from 16 A to 630 A and is built only on 3 pole DPX3 or DPX breakers.
  2. Assembly content: two motor-operated breakers on a mechanical interlock plate, a pre-wired control panel and a controller, all ordered under one catalogue number.
  3. DPX3 160 assemblies: 25 kA (25, 40, 63, 80, 100, 125, 160 A), 36 kA and 50 kA (63, 80, 100, 125, 160 A).
  4. DPX3 250 assemblies: 100, 160, 200 and 250 A at 36, 50 and 70 kA breaking capacity.
  5. DPX 630 assemblies: 400 and 630 A at 36 and 70 kA breaking capacity, with thermal magnetic or electronic trip units.
  6. The shunt release on the breakers is 230 V AC/DC, which is the control circuit voltage.
  7. Delays in the control algorithm are adjustable: source-loss confirmation 0.1 to 10 s, changeover delays 0.5 to 120 s, wait before return to the main source 3 to 120 s.
  8. The ATS controllers 261 93 (standard) and 261 94 (communicating, RS 485) are supplied at 230 V AC and 12, 24, 48 V DC, acquire DMX and DPX breaker status and issue generator on/off commands.

Using it in design

  • When selecting an ATS assembly, compare the prospective short-circuit current at the connection point with the assembly's breaking capacity (25, 36, 50 or 70 kA) and choose the nominal current from the load current.
  • Calculate the interruption time during transfer from the sum of the algorithm delays; it is in the order of seconds, so IT load needs a UPS between the ATS and the load.
  • Because the assemblies are 3 pole, assess separately whether they suit earthing arrangements that need the neutral to be switched.
  • Set the wait before return to the main source (3 to 120 s) in line with generator cool-down time and the time the utility needs to stabilise.
  • Where remote monitoring is needed, specify the 261 94 controller with RS 485 port and connect it to the building management system.

Who should read it

Electrical engineers designing low-voltage switchboards, teams engineering generator and utility transfer, and panel builders.

Document contents

  1. DMX3 air circuit breakers (ACBs)
  2. Automatic transfer switch for critical applications
  3. DPX3 / DPX MCCBs
  4. MCCB Automatic Transfer Switches
  5. Example of algorithm for the functioning of an automatic transfer switch
  6. How to order: basic transfer switch, control panel, controller
  7. ATS for DPX3 160 3P TM MCCBs
  8. ATS for DPX3 250 3P TM MCCBs
  9. ATS for DPX 630 3P MCCBs

Publication details

Authors
Legrand
Publisher
Legrand
Year
2013
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Legrand (2013). Legrand Power Protection Guide: factory-assembled MCCB ATS. Legrand. https://content.voltimum.com/au/1117/legrand_-_power_protection_guide_2013_17.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.