Legrand
Legrand's 2013 residential and commercial power protection guide lists factory-assembled and tested automatic transfer switches (ATS) built on DPX3 and DPX moulded case circuit breakers from 16 A to 630 A: 37 ready-made assemblies, each ordered under one catalogue number, with breaking capacities of 25, 36, 50 and 70 kA.
On this page
Overview
The guide is a broad product catalogue covering Legrand air circuit breakers (DMX3), moulded case breakers (DPX3, DPX), miniature breakers, residual current devices, time switches and energy metering. The part relevant to data-centre design is the moulded case automatic transfer switch section on pages 102 and 103. These assemblies change over automatically from the main source to a standby supply when power fails, and the document names hospitals, airports, tunnels, manufacturing plants and data centres among the applications.
Each ATS assembly has three parts: two motor-operated moulded case breakers on a mechanical interlock plate (the basic transfer switch), a pre-wired control panel mounted on a metal plate, and a controller. The breakers carry a 230 V AC/DC shunt release, a value that belongs to the auxiliary circuit. The control panel connects to the controller and the breakers through plug-in wire looms. A common load-side busbar is available on request. All assemblies use 3 pole breakers.
The catalogue number combines frame size, pole count, breaking capacity and nominal current in one code: ATS 160 3P 25kA 25, for example, is a DPX3 160 frame, 3 pole, 25 kA, 25 A assembly. The DPX3 160 series has 17 assemblies from 25 A to 160 A, the DPX3 250 series 12 assemblies from 100 A to 250 A, and the DPX 630 series 8 assemblies at 400 A and 630 A with thermal magnetic or electronic trip units.
Transfer logic is shown as a flow chart. When the main source voltage disappears, a confirmation delay adjustable from 0.1 to 10 s runs, the main breaker opens, and after a second delay of 0.5 to 120 s the standby breaker closes. When the main source returns, a wait of 3 to 120 s is followed by a changeover delay of 0.5 to 120 s. For DMX3 air circuit breakers the same function is provided by the microprocessor control unit Cat. No. 261 93 and a cable-operated mechanical interlock.
Key points
- The factory-assembled MCCB ATS range runs from 16 A to 630 A and is built only on 3 pole DPX3 or DPX breakers.
- Assembly content: two motor-operated breakers on a mechanical interlock plate, a pre-wired control panel and a controller, all ordered under one catalogue number.
- DPX3 160 assemblies: 25 kA (25, 40, 63, 80, 100, 125, 160 A), 36 kA and 50 kA (63, 80, 100, 125, 160 A).
- DPX3 250 assemblies: 100, 160, 200 and 250 A at 36, 50 and 70 kA breaking capacity.
- DPX 630 assemblies: 400 and 630 A at 36 and 70 kA breaking capacity, with thermal magnetic or electronic trip units.
- The shunt release on the breakers is 230 V AC/DC, which is the control circuit voltage.
- Delays in the control algorithm are adjustable: source-loss confirmation 0.1 to 10 s, changeover delays 0.5 to 120 s, wait before return to the main source 3 to 120 s.
- The ATS controllers 261 93 (standard) and 261 94 (communicating, RS 485) are supplied at 230 V AC and 12, 24, 48 V DC, acquire DMX and DPX breaker status and issue generator on/off commands.
Using it in design
- When selecting an ATS assembly, compare the prospective short-circuit current at the connection point with the assembly's breaking capacity (25, 36, 50 or 70 kA) and choose the nominal current from the load current.
- Calculate the interruption time during transfer from the sum of the algorithm delays; it is in the order of seconds, so IT load needs a UPS between the ATS and the load.
- Because the assemblies are 3 pole, assess separately whether they suit earthing arrangements that need the neutral to be switched.
- Set the wait before return to the main source (3 to 120 s) in line with generator cool-down time and the time the utility needs to stabilise.
- Where remote monitoring is needed, specify the 261 94 controller with RS 485 port and connect it to the building management system.
Who should read it
Electrical engineers designing low-voltage switchboards, teams engineering generator and utility transfer, and panel builders.
Document contents
- DMX3 air circuit breakers (ACBs)
- Automatic transfer switch for critical applications
- DPX3 / DPX MCCBs
- MCCB Automatic Transfer Switches
- Example of algorithm for the functioning of an automatic transfer switch
- How to order: basic transfer switch, control panel, controller
- ATS for DPX3 160 3P TM MCCBs
- ATS for DPX3 250 3P TM MCCBs
- ATS for DPX 630 3P MCCBs
Publication details
- Authors
- Legrand
- Publisher
- Legrand
- Year
- 2013
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Legrand (2013). Legrand Power Protection Guide: factory-assembled MCCB ATS. Legrand. https://content.voltimum.com/au/1117/legrand_-_power_protection_guide_2013_17.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.