Cat CTG Series Automatic Transfer Switch LEXX0523-09, pp.1,5
Caterpillar
Caterpillar CTG series automatic transfer switches: 40-3000 A, UL 1008 at 480 VAC, MX150 control panel, open (CTG) and delayed (CTGD) transition models, NEMA 1 enclosure sizes.
On this page
Overview
Caterpillar's catalogue LEXX0523-09 (11/2012) presents the Cat CTG series automatic transfer switches (ATS). The series offers the dependability of a contactor-type transfer switch in a pre-configured form, controlled by an MX150 microprocessor panel that shows switch position, timers and available sources.
Ratings run from 40 to 3000 A in 2, 3 or 4 poles. The switch is UL 1008 listed at 480 VAC, CSA certified at 600 VAC (200-225 A, 480 V) and IEC listed at 480 V. It is a double-throw, mechanically interlocked, electrically operated, mechanically held design, supplied as standard open transition (CTG) or delayed transition (CTGD). The standard enclosure is Type 1; open style or Types 3R, 4, 4X and 12 are available.
Control defaults: normal-source under-voltage pickup 90%, dropout 80%; under-frequency pickup 95%; engine start delay 3 s (0-10 s); retransfer delay 30 min (0-60 min); engine cool-down 5 min (0-60 min). For CTGD the delay from neutral position is 5 s by default (0-10 min). Options include timed plant exerciser, space heater, network communications (LonWorks/Modbus) and EPM 2000 and EPM 6000 meters.
The NEMA 1 enclosure table gives dimensions in inches (mm) and weight in lb (kg). 40-200 A is 24 x 18 x 11 in (610 x 457 x 279 mm) at 69 lb (31 kg); 400 A is 46 x 24 x 14 in at 168 lb (76 kg) for 2-3 poles; 800-1200 A is 74 x 40 x 19.5 in; 1600-3000 A is 90 x 35.5 x 48 in at 1030-1400 lb. The notes call dimensions and weights approximate and add 15% for packaging.
Key points
- Ratings 40-3000 A, 2/3/4 poles; UL 1008 480 VAC, CSA 600 VAC (200-225 A), IEC 480 V.
- Open transition CTG and delayed transition CTGD; MX150 microprocessor panel.
- Pickup/dropout defaults: normal-source under-voltage 90%/80%, frequency pickup 95%.
- Engine start delay 3 s (0-10 s); retransfer delay 30 min (0-60 min).
- CTGD neutral-position delay default 5 s (0-10 min).
- Exerciser timer at 7, 14, 28 day intervals; event log of 16 records.
- NEMA 1: 610 x 457 x 279 mm at 31 kg for 40-200 A; 2286 x 902 x 1219 mm at 467-635 kg for 1600-3000 A.
- Seismic compliance IEEE 693-2005 and IBC-2003; add 15% to weights for packaging.
Using it in design
- Select ATS current against generator and load current, and choose open or delayed transition for motor and transformer loads.
- Set retransfer and cool-down delays consistently with the generator operating strategy.
- Use NEMA 1 dimensions and weights in electrical room layout; allow 3 in extra depth and 3 in for lifting eyes.
- On 2600 and 3000 A units check the side or rear ventilation clearance requirement.
Who should read it
Electrical designers selecting ATSs for generator and standby power systems.
Document contents
- Features
- Standard features and options
- Options: power measurement meters
- Testing standards and terminals
- MX150 control setting ranges
- NEMA 1 dimensional specifications
- Application notes
Publication details
- Authors
- Caterpillar
- Publisher
- Caterpillar
- Year
- Year not stated
- Document number
- LEXX0523-09
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Caterpillar Cat CTG Series Automatic Transfer Switch LEXX0523-09, pp.1,5. Caterpillar. LEXX0523-09. https://s7d2.scene7.com/is/content/Caterpillar/LEXX0523-09
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.