ACSC Series Air Cooled Chiller With Screw Compressor, 80-500 TR, 50 Hz (Coolex)

Original title Coolex Air Cooled Screw Water Chiller ACSC, CCH3A21-5-003, physical data p.12

Coolex

Coolex ACSC catalogue for R-134A screw air-cooled chillers: 80-500 TR (282-1760 kW), 50 Hz, rated at 35°C and 46°C ambient, with correction factors and a selection procedure.

On this page

Overview

The catalogue presents the ACSC series, designed for very high ambient temperatures such as the Gulf climate. Units have at least two semi-hermetic screw compressors, an insulated DX shell-and-tube evaporator, condenser coils and R-134A, shipped factory charged and tested. Capacity runs from 80 to 500 TR (282-1760 kW) and is rated under AHRI conditions. The tables cover physical and electrical data, correction factors, the selection procedure, performance tables, dimensions, piping and installation information.

The model code encodes a 415 V, 3-phase, 50 Hz supply and a double, triple or quadruple refrigerant circuit. In the physical data table, ACSC 080 is nominal 81 TR (285 kW) and ACSC 190 is 194 TR (683 kW). Two rating rows are given: standard AHRI 550/590 conditions (35°C ambient, 6.7°C leaving water, 5.5°C range, fouling factor 0.018 m² °C/kW) and 46°C ambient; for ACSC 080 these are 285 kW and 237 kW. Capacity control is stepless over 100-25%.

Correction tables give multipliers for altitude and fouling: capacity factor 0.99 at 600 m and 0.95 at 3,000 m; evaporator fouling of 0.000044 m² °C/W gives 0.992 on capacity and 0.997 on power input, and 0.000088 gives 0.978 and 0.990. Range correction is given as curves. The selection procedure is explained with a worked example. Because the tables cover one pair of conditions, other ambient and water temperatures must be selected from the performance tables and correction factors.

Key points

  1. Capacity range 80-500 TR (282-1760 kW), R-134A, 415 V/3-phase/50 Hz, double, triple or quadruple circuit.
  2. Semi-hermetic screw compressors with stepless capacity control of 100-25%; DX shell-and-tube evaporator and electronic expansion valve.
  3. Standard rating is AHRI 550/590: 35°C ambient, 6.7°C leaving water, 5.5°C range, fouling 0.018 m² °C/kW.
  4. A second rating is given at 46°C ambient: ACSC 080 falls from 285 kW (35°C) to 237 kW; ACSC 190 from 683 kW to 588 kW.
  5. Altitude correction: 600 m 0.99; 1,200 m 0.98; 1,800 m 0.97; 2,400 m 0.96; 3,000 m 0.95.
  6. Evaporator fouling correction: 0.000044 m² °C/W gives 0.992 capacity and 0.997 power; 0.000088 gives 0.978 and 0.990.
  7. ACSC 080 sound pressure is 72.3/68.8/63.5 dBA at 3/5/10 m and operating weight 3,001 kg; ACSC 190 weighs 5,454 kg.
  8. Condenser fans are 800 mm, 920 rpm direct-drive axial; ACSC 080 has 6 fans and 63,000 CFM.

Using it in design

  • Select from both the 35°C AHRI row and the 46°C ambient row; in hot climates the 46°C row shows capacity about 14-17% lower.
  • Apply altitude and fouling corrections to capacity and power input; use the range correction if design water delta-T differs from 5.5°C.
  • Choose the circuit count (2, 3, 4) together with the redundancy and part-load scenario.
  • On the water side, include evaporator water volume (87-166 L range), connection size and pressure-drop curves in pump and buffer tank calculations.
  • Check sound level and operating weight for roof or slab loading and neighbour constraints.

Who should read it

Mechanical designers and procurement engineers planning a data centre chiller plant with air-cooled screw chillers.

Document contents

  1. Introduction
  2. Nomenclature
  3. Outstanding features
  4. Main standard features
  5. Optional features
  6. Physical data
  7. Electrical data
  8. Correction factor tables and curves
  9. Selection procedure
  10. Water flow limit and cooler water pressure drop curves
  11. Performance data tables (English and metric)
  12. Unit dimensions
  13. Piping and installation information
  14. Guide specification

Publication details

Authors
Coolex
Publisher
Coolex
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Coolex Coolex Air Cooled Screw Water Chiller ACSC, CCH3A21-5-003, physical data p.12. Coolex. https://res.cloudinary.com/dyzk9phzo/image/upload/v1763128812/New_ACSC_80-500_50Hz_CCH3A21-5-003_co9clw.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.