Technical guideFree to readYear not stated

GAMI General Data for R407C, Page 1: CCU75-CCU240 Air-Cooled Screw Chillers

Original title GAMI Cool Wave General Data for R407C, page 1

GAMI

Gulf Air Conditioning Manufacturing Industries (GAMI) R407C chiller table, page 1: CCU75-CCU240, 191-692 kW (35°C air) and 158-601 kW (46°C air), 12/7°C water, 50 Hz.

On this page

Overview

The web page tabulates the first model group of GAMI's R407C air-cooled chiller series with semi-hermetic screw compressors: CCU75, 100, 120, 150, 180, 200, 220 and 240. Each model has a step-control (ATG) and a continuous-control (ATGZ) version. Data is in kW, kcal/h and Btu/h, with 380/415 V, 3-phase, 50 Hz supply.

Nominal capacity is given at two conditions. The first is 12/7°C chilled water in/out and 35°C (dry bulb) condenser inlet air: 191, 280, 346, 382, 519, 573, 626 and 692 kW. The second uses the same water temperatures with 46°C air: 158, 243, 301, 315, 451, 473, 544 and 601 kW. For hot-climate design the second row shows capacity falling by about 13-17% (for example CCU75: from 191 to 158 kW).

Capacity steps vary by model: CCU75 has 100/75/50/0%, CCU100 100/75/50/25/0% and CCU120 100/66/33/17/0%; the continuous version spans 100-25% with a 12.5% or 8.3% step on some models. Circuits number 1 to 4 (CCU75: 1, CCU100-150: 2, CCU180-200: 3, CCU220-240: 4). The table also gives dimensions (height 2,400, width 1,800, depth 2,130-7,960 mm), plate evaporator, direct-drive propeller fans (0.9 kW each), safety devices, connection type (Victaulic), and net and shipping weights. Input power and EER are not given on this page.

Key points

  1. Models CCU75-CCU240, R407C, semi-hermetic screw compressors, step (ATG) and continuous (ATGZ) control.
  2. Nominal capacity 191-692 kW at 12/7°C water and 35°C air; 158-601 kW at 46°C air.
  3. CCU75: 191 kW (35°C) and 158 kW (46°C); CCU240: 692 and 601 kW.
  4. Circuit count: 1 for CCU75, 2 for CCU100-150, 3 for CCU180-200, 4 for CCU220-240.
  5. Step control example: CCU120 at 100/66/33/17/0%; continuous control 100-25%.
  6. Dimensions: height 2,400 mm, width 1,800 mm, depth 2,130 mm (CCU75) to over 7,960 mm (CCU220-240).
  7. Net weight from 1,650 kg (CCU75) to 4,500 kg (CCU200), and as twin units for CCU220-240.
  8. Supply 380/415 V, 3-phase, 50 Hz; condenser fan motors 0.9 kW.

Using it in design

  • Read capacity from the 35°C and 46°C rows; in hot climates such as the Gulf use the row matching your design ambient.
  • Compare the continuous-control version (ATGZ) with step control for part-load efficiency and water temperature stability.
  • Assess circuit count (1-4) for redundancy and remaining capacity during maintenance.
  • Apply depth (over 7.96 m) and weight to roof or slab loading and layout planning.
  • Because input power and EER are not given, base energy calculations on data requested from the manufacturer.

Who should read it

Mechanical designers selecting air-cooled chillers for hot climates.

Document contents

  1. General data: R407C
  2. Nominal cooling capacity
  3. Capacity control
  4. Dimensions
  5. Compressor and heat exchangers
  6. Safety devices and connections
  7. Weight and shipping dimensions

Publication details

Authors
GAMI
Publisher
GAMI
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GAMI GAMI Cool Wave General Data for R407C, page 1. GAMI. https://gibca.com/groupweb/gami/html/data_r407c_page1.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.