GAMI General Data for R407C, Page 2: CCU270-CCU400 Air-Cooled Screw Chillers

Original title GAMI Cool Wave General Data for R407C, page 2

GAMI

Gulf Air Conditioning Manufacturing Industries (GAMI) R407C chiller table, page 2: CCU270-CCU400, 728-1,146 kW (35°C air) and 616-946 kW (46°C air), 12/7°C water, 50 Hz.

On this page

Overview

The web page tabulates the large models of GAMI's R407C air-cooled screw chiller series: CCU270, 300, 310, 320, 330, 360, 370, 380 and 400. Each model comes in step-control (ATG) and continuous-control (ATGZ) versions. It continues the CCU75-240 models on page 1 and uses the same conditions. The table presents capacity, dimension, compressor and weight data in model columns.

Nominal capacity is given at two conditions. With 12/7°C chilled water and 35°C condenser air the values are 728, 764, 799, 865, 901, 955, 1,038, 1,092 and 1,146 kW. At the same water temperatures with 46°C air they are 616, 631, 694, 752, 766, 789, 902, 924 and 946 kW. For the largest model, CCU400, capacity loss at hot air is about 17% (from 1,146 to 946 kW).

Circuit count rises to 4 (CCU270-300), 5 (CCU310-360) and 6 (CCU370-400). Capacity steps are model specific, for example 100/75/50/38/25/13/0%, 100/80/60/50/30/10/0% and 100/83/66/50/33/17/0%; the continuous version spans 100-25% with 12.5 or 10% steps. Dimensions: height 2,400, width 1,800, depth from 7,960 mm to 11,560 mm. Compressors are semi-hermetic screw, condenser fans are 0.9 kW direct-drive propeller fans, the evaporator is a plate heat exchanger and control is microprocessor based.

Key points

  1. Models CCU270, 300, 310, 320, 330, 360, 370, 380, 400; R407C, semi-hermetic screw compressors.
  2. Capacity 728-1,146 kW at 12/7°C water and 35°C air; 616-946 kW at 46°C air.
  3. CCU400: 1,146 kW (35°C) and 946 kW (46°C); CCU270: 728 and 616 kW.
  4. Circuit count 4 for CCU270-300, 5 for CCU310-360, 6 for CCU370-400.
  5. Step control examples: 100/75/50/38/25/13/0%, 100/80/60/50/30/10/0%, 100/83/66/50/33/17/0%.
  6. Continuous control over 100-25% with 12.5 or 10% steps.
  7. Depth from 7,960 mm (CCU270-300) to 11,560 mm (CCU370-400) and more; height 2,400, width 1,800 mm.
  8. Plate evaporator, thermostatic expansion valve with MOP, microprocessor control; condenser fan motors 0.9 kW.

Using it in design

  • Check capacity at the 46°C air row as well; on large models a loss of up to 17% at hot air affects load and redundancy sizing.
  • On 5 and 6 circuit models, assess the remaining capacity with one circuit out of service in N+1 terms.
  • Plan the long unit depths (9.76 and 11.56 m) for roof or slab layout, air circulation and maintenance access.
  • Compare the 100-25% range of the continuous version with your part-load profile.
  • Because input power and EER are not given, compute operating energy from data obtained from the manufacturer.

Who should read it

Mechanical designers selecting large air-cooled chillers for hot climates.

Document contents

  1. General data: R407C (large models)
  2. Nominal cooling capacity
  3. Capacity control
  4. Dimensions
  5. Compressor and heat exchangers
  6. Safety devices and connections

Publication details

Authors
GAMI
Publisher
GAMI
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GAMI GAMI Cool Wave General Data for R407C, page 2. GAMI. https://gibca.com/groupweb/gami/html/data_r407_c_page2.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.