Mehr Asl Variable Frequency Air Cooled Magnetic Bearing Centrifugal Chiller, PDF page 5

Mehr Asl

Mehr Asl's SALC air-cooled magnetic bearing centrifugal chillers come in general-application (12/7°C) and data-centre (22/15°C) variants, six models in all with COP from 3.53 to 4.66.

On this page

Overview

The Mehr Asl (Tabriz, Iran) catalogue presents an air-cooled chiller series with R134a refrigerant, magnetic bearing centrifugal compressors and microchannel condensers. The company was founded in 1990, works under ISO 9001 and ISO 14000 and states it tests to standards such as ARI 590 and ISO 5151. The catalogue says natural (free) cooling avoids cooling water loss and can save up to 50% of cost at low ambient temperature.

Core technologies are listed: an oil-free, friction-free magnetic suspension compressor, frequency-converted starting with current as low as 2 A, permanent-magnet synchronous direct drive, a falling film evaporator (15% better heat exchange efficiency, 40% less refrigerant charge) and a microchannel condenser (30% better heat transfer than a coil exchanger, 15.2% overall efficiency gain from a W-shaped layout, 60% less weight and 40% less volume for the same area).

The technical tables separate two variants. The general-purpose SALC1TD120M6W, 140M6W and 160M6W are rated for 12°C inlet and 7°C outlet water, while the data-centre SALC1TD130M6W, 180M6W and 200M6W are rated for 22°C inlet and 15°C outlet water; air temperature is 35°C dry bulb in both. Capacity is printed in kcal/h times 10^4: 30.9, 40.4, 47.3 and 36.1, 49, 58.1.

The table lists compressor input and fan power separately, so total plant input must be calculated separately. Capacity is usable only with the stated water temperatures, heat-rejection condition and 50 Hz supply. The chiller runs across a 0 to 100% load range, is said to keep operating normally at 10% load and restarts quickly in 20 seconds.

Key points

  1. General models (12/7°C water): capacity 30.9 / 40.4 / 47.3 ×10^4 kcal/h; nominal input 101 / 133 / 142 kW; COP 3.55 / 3.53 / 3.87.
  2. Data-centre models (22/15°C water): capacity 36.1 / 49 / 58.1 ×10^4 kcal/h; nominal input 104 / 136 / 145 kW; COP 4.04 / 4.19 / 4.66; IPLV 6.7.
  3. Compressor maximum input is 92, 121 and 127 kW; maximum rated current 158, 208 and 218 A; starting current 2 A.
  4. Total fan power is 24 / 24 / 32 kW for the general models and 24 / 32 / 38 kW for the data-centre models.
  5. Chilled water flow is 61.7 / 80.8 / 94.6 m³/h (general) and 60.5 / 82.1 / 97.2 m³/h (data centre); evaporator pressure drop 63 kPa.
  6. Weight is 2800-4300 kg (general) and 3200-4700 kg (data centre); noise 85 dB.
  7. Dimensions are 4700×2200×2500, 5900×2200×2500 and 7100×2200×2500 mm; pipe diameter DN100 or DN125.
  8. Power is 3-phase, 380/400 V, 50 Hz; refrigerant R134A.

Using it in design

  • Capacity is given in kcal/h, so convert to kW with 1 kW = 860 kcal/h and verify the water temperatures (7°C or 15°C).
  • The water flow formula (capacity × 0.172 or × 0.144 m³/h) holds only at the standard condition; recompute flow for a different ΔT.
  • Do not take compressor input as total chiller input; add fan power.
  • For the data-centre models the 22/15°C water is warm, so check that terminal units are selected for that temperature.
  • Use the weight and dimension tables for layout and structural load.

Who should read it

Data-centre mechanical designers evaluating air-cooled magnetic bearing centrifugal chillers.

Document contents

  1. About Mehr Asl Company
  2. Certificates, standards and laboratories
  3. Air cooled magnetic bearing centrifugal chiller
  4. Core technical
  5. Technical parameters: general applications (SALCxxM6W)
  6. Unit size table R134A (7°C)
  7. Technical parameters: data center (SALCxxM6W)
  8. Unit size table R134A (15°C)

Publication details

Authors
Mehr Asl
Publisher
Mehr Asl
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Mehr Asl Mehr Asl Variable Frequency Air Cooled Magnetic Bearing Centrifugal Chiller, PDF page 5. Mehr Asl. https://mehrasl.ir/farsi/Air-Cooled-Centrifugal-Chiller.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.