Technical guideFree to read2020

Petra PSC4 Air-Cooled Smart Chiller (R-410A, scroll, 2020 catalogue)

Original title Petra PSC4 technical catalogue, 50 Hz SI performance p.45

Petra

Petra Engineering's July 2020 PSC4 catalogue: air-cooled R-410A chiller with hermetic scroll compressors, nominal capacity up to 1,565 kW (445 TR) as a single-piece, single power entry unit with modulation down to 10% of nominal.

On this page

Overview

The catalogue presents Petra's PSC4 series of air-cooled liquid chillers with hermetic scroll compressors and R-410A refrigerant. It is positioned for a wide capacity range, high efficiency, low sound and compact footprint, suitable for schools, hospitals and sites in residential areas. The manufacturer is ISO 9001:2015 and ISO 14001:2015 certified, its main products are UL and ETL listed, and air-cooled chillers are rated to the AHRI standard. Each unit is 100 percent factory tested and commissioned.

PSC4 is offered with nominal capacity up to 1,565 kW (445 nominal tons) as a single-piece, single power entry unit; the nominal capacity columns cover blocks such as 50, 55, 65, 75, 85, 95 and 105 tons. Construction: welded C-channel base, 1.8 mm tubular cross members, paint certified to 5,000 hours of salt spray (ASTM B117), condenser coils with protective panels and suction-gas-cooled hermetic scroll compressors. A microprocessor controller and the Petra graphical touch screen modulate capacity down to 10 percent of nominal.

Low ambient options: head pressure control by condenser fan speed, operation down to 0 °C and -17 °C (0 °F) ambient, cooler tape heater protection down to 0, -18 and -29 °C ambient. The catalogue covers physical data, model layout, load distribution, selection procedure, performance data, pressure drop curves, typical piping and refrigerant schematics, electrical data, wiring diagrams, application data, unit clearances and guide specification.

Key points

  1. Nominal capacity up to 1,565 kW (445 TR), single-piece with single power entry.
  2. Hermetic scroll compressors, R-410A; capacity modulation down to 10 percent of nominal.
  3. Condenser coils have protective panels; paint is certified to 5,000 hours salt spray (ASTM B117).
  4. Low ambient: operation down to 0 °C and -17 °C; cooler tape heater down to 0, -18 and -29 °C ambient.
  5. Head pressure is managed by condenser fan speed control.
  6. Dual power connection option: one for compressors, one for other loads.
  7. Rated to AHRI standard; 100 percent factory tested and commissioned.
  8. Low sound level; positioned for use near schools, hospitals and residential areas.

Using it in design

  • When sizing, compare nominal tons and AHRI conditions with the design ambient and water temperature; use the selection procedure and performance data.
  • For low ambient temperatures, choose the 0 °C or -17 °C option and the cooler heater by the site's coldest temperature.
  • Use the dual power entry option to separate compressor and auxiliary feeds when designing electrical redundancy.
  • Check clearance and footprint requirements with the unit clearance table and sound level for sound-sensitive surroundings.
  • For part-load efficiency, match the modulation steps down to 10 percent with the hall load profile.

Who should read it

Mechanical designers selecting air-cooled chillers and specification writers.

Document contents

  1. Outstanding features
  2. Standard features
  3. Optional features
  4. Microprocessor controller
  5. Petra graphical touch screen
  6. Physical data
  7. Model layout
  8. Load distribution
  9. Selection procedure
  10. Performance data
  11. Pressure drop curves
  12. Piping schematics
  13. Electrical data
  14. Application data
  15. Unit clearance
  16. Guide specification

Publication details

Authors
Petra
Publisher
Petra
Year
2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Petra (2020). Petra PSC4 technical catalogue, 50 Hz SI performance p.45. Petra. https://petramisr.com/files/PSC4-Jul2020.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.