Santak Castle6-10k user manual, section 1.4, printed p.5
Original title Santak Castle6-10k user manual, section1.4, printed p.5
Eaton
The Santak Castle C6K/C10K manual covers 6 and 10 kVA (5.4 and 9 kW) online double-conversion UPS: input 120-275 V, output 220 V ±1%, THD below 2%, with an altitude derating table.
On this page
Overview
The manual presents the Santak Castle Online series as a double-conversion UPS for computer, communication and industrial control systems. The rectifier converts mains AC to DC, which charges the batteries and feeds the inverter; the inverter permanently produces a pure sine voltage. On mains failure, maintenance-free batteries feed the inverter; on inverter failure or overload the UPS transfers to bypass and returns to the inverter when the fault clears.
Section 1.4 compares five models: C6K and C10K (long body with internal batteries, 58.9 and 62.1 kg), C6KS and C10KS (short body for external batteries, 14.2 and 15.9 kg) and 3C10KS (three-phase input, 16.9 kg). Body sizes are 248 x 500 x 616 mm (C6K, C10K) and 212 x 500 x 420 mm (S models). Power is 6 kVA/5.4 kW and 10 kVA/9 kW.
Input voltage range is 120-275 Vac, frequency 40-70 Hz, power factor 0.99 (0.95 for 3C10KS) and maximum input current 32.1-56.6 A (at 176 Vac input, full load and empty battery charging). Output is 220 Vac ±1%, 50 Hz ±1%, power factor 0.9, crest factor 3:1 and THD below 2% on linear full load. On overload the UPS transfers to bypass after 10 min for 105-125% (0-30 °C) or 1 min (30-40 °C), after 30 s for 125-150% and after 0.5 s above 150%.
Battery backup at full load is 4 min for the C6K and 3 min for the C10K; charge time is 7 hours to 90%. For S models the time depends on external battery capacity. Operation is 0-40 °C, storage -25 to 55 °C, humidity 20-90%, with no derating below 1000 m; a correction factor falls from 95% at 1500 m to 67% at 5000 m. At least 50 cm of space around the unit is recommended.
Key points
- Models: C6K (6 kVA/5.4 kW), C10K (10 kVA/9 kW), C6KS, C10KS and 3C10KS (three-phase input).
- Body: C6K 248 x 500 x 616 mm 58.9 kg; C10K 62.1 kg; S models 212 x 500 x 420 mm, 14.2-16.9 kg.
- Input: 120-275 Vac, 40-70 Hz, power factor 0.99 (3C10KS 0.95), maximum current 32.1-56.6 A (176 Vac).
- Output: 220 Vac ±1%, 50 Hz ±1%, power factor 0.9, crest factor 3:1, THD < 2%.
- Overload: 105-125% 10 min (0-30 °C) or 1 min (30-40 °C); 125-150% 30 s; above 150% 0.5 s, then bypass.
- Backup at full load 4 min (C6K) and 3 min (C10K); charge 7 hours to 90%.
- Standards: EN 62040-2:2005, EN 62040-1:2008+A1:2013, YD/T 1095-2008.
- Altitude derating: 1000 m 100%, 1500 m 95%, 2000 m 91%, 3000 m 82%, 4000 m 74%, 5000 m 67%.
- Operation 0-40 °C, storage -25 to 55 °C, humidity 20-90%; output line recommended no longer than 10 m.
Using it in design
- Verify the load in watts: with output power factor 0.9, the limits are 5.4 kW for the 6 kVA model and 9 kW for the 10 kVA model.
- Size input protection and cables with the maximum input current (up to 56.6 A at 176 Vac); the wide input window (120-275 V) tolerates weak mains.
- Compare the 3-4 minute backup of the internal-battery models with the runtime target; longer autonomy needs an external battery pack on the S model.
- Apply the derating table above 1000 m (for example 91% of nominal load at 2000 m).
- Leave 50 cm of ventilation space around the unit in the layout and keep the output cable under 10 m and communication cables under 3 m.
Who should read it
Electrical engineers selecting and commissioning single-phase UPS for small technical rooms and industrial control loads.
Document contents
- Introduction (symbols, front and rear view, product specification)
- Installation (cables, connection, external battery, parallel card, EPO)
- Control and display panel
- Operation
- Maintenance
- Troubleshooting
Publication details
- Authors
- Eaton
- Publisher
- Eaton
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eaton Santak Castle6-10k user manual, section1.4, printed p.5. Eaton. https://osscom.santak.com/Castle%206-10k%20user%20manual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.