SKM Quick Selection Guide Applied Products, APCN-S 50 Hz table

SKM

The SKM quick selection guide gives APCN-S screw chiller capacities of 80.93-436.1 tons, EER at 95, 115 and 118.4°F ambient, plus dimensions and weights in one table.

On this page

Overview

The guide gathers selection tables for chillers, air handling units, fan coil units, ecology units, packaged units, condensing units, swimming pool units and CRAC units from S.K.M Air Conditioning LLC, a leading HVAC manufacturer in the Gulf. The company holds ISO 9001, ISO 14001 and ISO 45001 certifications.

The chiller section includes the ACMR (scroll, R410A, 8-280 TR, 30-980 kW), APCN-S (screw), APCN-V (inverter), APCY-E, APCY-H and APCY-P series. ACMR is rated to AHRI 550/590 and 551/591, with a 0 to 52°C operating range and an IP54 control panel.

The APCN-S 50 Hz table lists 28 models from APCN5080S to APCN5440S. For each model it gives total cooling capacity (tons), total input power (kW) and EER (Btu/W.h) at 95°F, 115°F and 118.4°F ambient. Table conditions are 44°F leaving chilled water, 10°F range, 0.0001 h.ft2.°F/Btu fouling, refrigerant R134a and 380-415V/3Ph/50Hz supply.

For example, APCN5080S gives 80.93 tons at EER 11.18 at 95°F, 73.31 tons at EER 8.14 at 115°F and 71.83 tons at EER 7.69 at 118.4°F, so capacity falls about 11% at 118.4°F ambient. The largest model (APCN5440S) gives 436.1 tons at 95°F and 387.5 tons at 118.4°F. Sound pressure at 1 m runs 77.9 to 82.8 dB(A) and weight 3884 to 16341 kg; models from 375S upward have three circuits.

Key points

  1. The APCN-S 50 Hz table has 28 models: APCN5080S (80.93 tons) to APCN5440S (436.1 tons) at 95°F ambient.
  2. Table condition: 44°F leaving chilled water, 10°F range, fouling 0.0001 h.ft2.°F/Btu, R134a.
  3. APCN5080S EER is 11.18 (95°F), 8.14 (115°F) and 7.69 (118.4°F) Btu/W.h.
  4. At 118.4°F ambient capacity drops about 11% from the 95°F value (80.93 to 71.83 tons).
  5. Sound pressure is 77.9-82.8 dB(A) at 1 m; weight 3884-16341 kg.
  6. Models have two circuits; APCN5375S and above have three.
  7. The ACMR scroll series covers 8-280 TR (30-980 kW), R410A, AHRI 550/590 and 551/591 basis, 0 to 52°C operating range.
  8. Supply is 380-415V/3Ph/50Hz.

Using it in design

  • In hot-climate projects select chiller capacity from the design ambient column (115 or 118.4°F), not the 95°F value; capacity falls about 11%.
  • Compare EER at the same ambient temperature; APCN5080S falls from 11.18 at 95°F to 7.69 at 118.4°F.
  • Plan part-load and redundancy strategy together with the two- or three-circuit structure.
  • Check sound pressure (77.9-82.8 dB(A) at 1 m) and weight (3.9-16.3 t) against roof or slab capacity and noise limits.
  • This table is for 50 Hz and R134a only; use the relevant table for 60 Hz or the inverter APCN-V.

Who should read it

Mechanical designers selecting air-cooled chillers for hot climates who must account for capacity loss at high ambient temperature.

Document contents

  1. SKM Overview
  2. SKM Products Line-up
  3. Quick Selection: Chiller
  4. Air Handling Unit
  5. Fan Coil Unit
  6. Ecology Unit
  7. Packaged Unit
  8. Condensing Unit
  9. Swimpool Unit
  10. CRAC Unit
  11. Chillers ACMR 50 Hz
  12. Chillers APCN-S 50 Hz and 60 Hz

Publication details

Authors
SKM
Publisher
SKM
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SKM SKM Quick Selection Guide Applied Products, APCN-S 50 Hz table. SKM. https://skmaircon.com/catalogues_new/QuickSelection-AppliedProducts.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.