Technical guideFree to readYear not stated

SKM SCRR + SCRW precision cooling (CRAC) catalogue

Original title SKM SCRR + RCA CRAC catalogue, 50Hz general data p.10 Tables 7–8

SKM

The SKM SCRR+RCA (DX) and SCRW (chilled water) CRAC catalogue gives capacity ratings, electrical data and installation requirements for 5-30 TR (17-105 kW) precision air conditioners.

On this page

Overview

The catalogue presents the SKM Computer Room Series (CRAC) as precision air conditioners designed for the Gulf's severe climate, controlling temperature and humidity for data centres and IT equipment. The series comes in two forms: SCRR+RCA is a direct-expansion (DX) type combining an indoor unit (SCRR) with an outdoor unit (RCA); SCRW is a chilled-water type connected to a chilled water source such as a chiller.

SCRR+RCA units use hermetic scroll compressors; 12 models cover 5-23 TR at 60 Hz and 5-21 TR at 50 Hz, rated to AHRI 1360 and exceeding SASO 2874. SCRW has 10 models of 5-30 TR in both 50 and 60 Hz. Refrigerant options R-134a, R-410A and R-22 appear on the cover; airflow can be down-flow or up-flow (front or down return).

The model code encodes power supply (R: 380-400V/3Ph/60Hz, Y: 380-415V/3Ph/50Hz), airflow direction (U, F, D), nominal capacity in kW, single or double circuit, frequency and fluid type (R: R-410A, W: chilled water). Capacity tables give SCRR+RCA gross capacity at 50 and 60 Hz for outdoor ambient of 95°F (35°C), 105°F (40.6°C), 115°F (46.1°C) and 125°F (51.7°C), with wet-bulb and bypass factor (BPF) conditions.

The remainder covers electrical data, typical wiring diagrams, dimensions, loading points, recommended clearances, unit configuration, installation and commissioning, handling and guide specifications. An options section lists additional equipment.

Key points

  1. Capacity range 5-30 TR (17-105 kW); two types: SCRR+RCA (DX) and SCRW (chilled water).
  2. SCRR+RCA: 12 models, 5-23 TR at 60 Hz and 5-21 TR at 50 Hz; hermetic scroll compressor.
  3. SCRW: 10 models, 5-30 TR, 50 and 60 Hz.
  4. Rated to AHRI 1360; exceeds SASO 2874.
  5. Gross capacity tables at 95, 105, 115 and 125°F (35, 40.6, 46.1 and 51.7°C) outdoor ambient.
  6. Airflow can be down-flow (D) or up-flow (U: down return, F: front return).
  7. Power supply 380-400V/3Ph/60Hz or 380-415V/3Ph/50Hz.
  8. The code structure gives capacity in kW, circuit count (single or double) and refrigerant.

Using it in design

  • At high-ambient sites select DX CRAC capacity from the design outdoor temperature column (for example 115 or 125°F), not the nominal value.
  • Choose between chilled-water SCRW and DX SCRR+RCA by chiller availability, pipe routing and outdoor unit placement.
  • Match down-flow or up-flow configuration to the raised floor and aisle layout.
  • Carry the recommended service clearances and loading-point data into the floor and layout plan.
  • Separate gross capacity from sensible capacity in the load calculation; data-centre load is mainly sensible.

Who should read it

Mechanical designers selecting precision air conditioners for computer rooms and comparing DX with chilled-water CRAC in hot climates.

Document contents

  1. Introduction
  2. Legend
  3. Nomenclature
  4. Component Features
  5. Optional Features
  6. Unit Specifications
  7. Capacity Ratings
  8. Electrical Data
  9. Typical Wiring Diagram
  10. Dimensional Data
  11. Loading Points
  12. Recommended Clearances
  13. Unit Configuration
  14. Installation and Commissioning
  15. Unit Handling
  16. Guide Specifications

Publication details

Authors
SKM
Publisher
SKM
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SKM SKM SCRR + RCA CRAC catalogue, 50Hz general data p.10 Tables 7–8. SKM. https://www.skmaircon.com/catalogues_new/crac.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.