Soeteck STS Cabinet Static Transfer Switch: Model Range Table
Original title Soeteck STS C model range table
Soeteck
Soeteck STS cabinet static transfer switch: 32, 40, 63, 100 and 125 A models, typical 5 ms transfer at 340-420 V input, 3P/4P configuration, fan-cooled cabinet, 42 to 55 kg.
On this page
Overview
The document is the product page of Soeteck's cabinet static transfer switch (STS). The unit transfers automatically between primary and backup sources in a typical 5 ms and is designed for data centres, telecom networks and industrial automation. Input and output are 3P or 4P, voltage is 340-420 V (configurable) and frequency 50-60 Hz. An LCD display shows input voltage, output current, system status and fault alarms, and the cabinet's cooling fans keep operation stable under load.
There are five models: SY-STS-C-32A, -40A, -63A, -100A and -125A. Size is 430 mm wide, 600 mm deep and 800 mm high; weights are 42, 45, 48, 52 and 55 kg respectively. The communication interface is RS-485 in the model table and RS232 in the description text. IEC/EN (EMC) and CE compliance is stated. Use examples include UPS-to-UPS transitions, generator redundancy and high-availability industrial supply.
The technical specifications and brochure sections are marked 'coming soon'. The document therefore does not give transfer trigger thresholds, overload capacity, short-circuit withstand or efficiency values; it tabulates only rated current, voltage range, typical transfer time, size and weight.
Key points
- Five models: SY-STS-C-32A, -40A, -63A, -100A, -125A; cabinet type.
- Typical transfer time 5 ms; automatic transfer between primary and backup sources.
- 3P/4P configuration, 340-420 V (configurable), 50-60 Hz.
- Size 430 × 600 × 800 mm; weight 42, 45, 48, 52 and 55 kg.
- LCD display: input voltage, output current, status and fault alarms.
- Fan-cooled cabinet; communication is RS-485 (table) or RS232 (description).
- IEC/EN (EMC) compliance and CE.
Using it in design
- Select the current rating (32 to 125 A) against the downstream load total and set the 3P/4P configuration according to the system neutral.
- For UPS-to-UPS or UPS-to-generator transfer, compare the synchronism of the two sources and the 5 ms transfer with the load's tolerance.
- Check the cabinet footprint (430 × 600 mm), height (800 mm) and the 42 to 55 kg weight in the electrical room layout.
- Plan the maintenance of the cooling fans; compare with fanless solutions.
- Since transfer trigger thresholds are not in the document, request them from the manufacturer.
Who should read it
Electrical engineers designing dual-source supply in data-centre, telecom and industrial facilities.
Document contents
- Overview
- Model range
- Technical specifications
Publication details
- Authors
- Soeteck
- Publisher
- Soeteck
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Soeteck Soeteck STS C model range table. Soeteck. https://soeteck.com/en/products/critical-power/static-transfer-switches/soeteck-sts-series-cabinet-static-transfer-switch-32-40-63-100-125a/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.