Uniti Power Echo UPS Series Brochure

Uniti Power / Secure Power Ltd

Uniti Power Echo is a 1, 2 and 3 kVA 2U rack on-line double-conversion UPS series with 0.9 output power factor, a 90-275 VAC input window, 0 ms transfer, and a 3 kVA ER model that extends with external 72 V battery modules.

On this page

Overview

The brochure presents the compact Echo series from UK company Uniti Power (Secure Power Ltd), designed for network, security, retail and distributed IT. There are three models: ECH1000RMi2U (1000 VA/900 W), ECH2000RMi2U (2000 VA/1800 W) and ECH3000RMi2UER (3000 VA/2700 W). All are true double conversion, 2U high and 428 mm deep. Input is 208/220/230/240 VAC with a 90-275 VAC window and input power factor above 0.99; the bypass window is 187-265 V.

Output power factor is 0.9, voltage regulation +/-1%, THDv under 2% on linear load, with a pure sine waveform. Efficiency is 89%, 90% and 91% in line mode and 85%, 86% and 87% in battery mode. Transfer time is 0 ms between battery and inverter, under 4 ms between inverter and bypass and under 10 ms between ECO and battery. The 1 and 2 kVA models have internal batteries (12 V/9 Ah x 2 and x 4); the 3 kVA ER model uses 72 V external batteries and has no internal battery.

Runtime at full load is 3.8 minutes for 1 kVA and 3.6 minutes for 2 kVA; the 3 kVA ER with 1, 2, 3 and 4 EBM72VRM2U modules reaches 3.7, 10.9, 18.5 and 26.0 minutes at full load and 23.9, 53.2, 87.8 and 124.5 minutes at 25% load. The brochure also describes the UPNETG2S network management card (Gigabit Ethernet, SNMP v1/v3, Modbus TCP, MQTT, REST API), the Winpower G2 and SPS G2 software, an environmental probe and rack rail kits. Product and packaged dimensions and weights are in separate rows.

Key points

  1. Three models: ECH1000RMi2U 1000 VA/900 W, ECH2000RMi2U 2000 VA/1800 W, ECH3000RMi2UER 3000 VA/2700 W.
  2. Output power factor 0.9; input PF >0.99; input window 90-275 VAC; bypass 187-265 V.
  3. Efficiency 89/90/91% in line mode and 85/86/87% in battery mode.
  4. Transfer: battery-inverter 0 ms, inverter-bypass <4 ms, ECO-battery <10 ms.
  5. The 1 and 2 kVA models have internal batteries (24 V and 48 V); the 3 kVA ER has none and uses 72 V external modules.
  6. Full-load runtime: 3.8 min (1 kVA), 3.6 min (2 kVA); 3 kVA ER with 1-4 modules 3.7, 10.9, 18.5 and 26.0 min.
  7. Product size 439.8 x 88 x 428 mm (W x H x D); weight 13, 18 and 9.3 kg; noise <50 dB; IP20.
  8. Warranty 3-year parts, 1-year batteries; RS232/USB, EPO and a short-depth network card slot.

Using it in design

  • With a 0.9 output power factor the 3 kVA model gives 2.7 kW; select load by watts.
  • For a runtime target, choose the number of external battery modules for the 3 kVA ER model by load fraction; internal-battery models give only minutes at full load.
  • The wide 90-275 VAC input window reduces battery use on weak mains; confirm with the manufacturer whether the window depends on load.
  • In rack layout allow 2U and 428 mm depth, plus a separate 2U for each additional battery module.
  • In monitoring design, consider the UPNETG2S card's SNMP, Modbus TCP, MQTT and REST interfaces.

Who should read it

Designers selecting compact on-line UPSs for network racks, edge data centres and small server rooms.

Document contents

  1. Echo UPS series
  2. Key features
  3. How it works
  4. Accessories
  5. Network management and software
  6. Runtime options
  7. Datasheet

Publication details

Authors
Uniti Power / Secure Power Ltd
Publisher
Uniti Power / Secure Power Ltd
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Uniti Power / Secure Power Ltd Uniti Power Echo UPS Series Brochure. Uniti Power / Secure Power Ltd. https://unitipower.com/media/downloads/uniti/Uniti-Echo-Range-Brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.