Uniti Power Tempo Series 850/1200/2200 VA UPS Data Sheet
Original title Uniti Power Tempo Series 850/1200/2200 VA Data Sheet
Uniti Power / Secure Power Ltd
Uniti Power Tempo is a line-interactive UPS series of 850, 1200 and 2200 VA with 170-280 VAC input, 2-8 ms transfer, stepped sine output, 20-50 minutes backup at 100 W and a 6-year warranty.
On this page
Overview
The data sheet presents the Tempo line-interactive series with AVR (automatic voltage regulation), designed for workstations, networking equipment and essential electronics. The models are TMP850IEC (850 VA/480 W), TMP1200IEC (1200 VA/600 W) and TMP2200IEC (2200 VA/1200 W). Output power factors are 0.56, 0.5 and 0.55. The series is aimed at small offices, home working and retail.
Input is 230 VAC and accepts 170-280 VAC. In battery mode the output is +/-10% and +/-1 Hz with a stepped sine waveform. Transfer time is typically 2-6 ms on the small model and 4-8 ms on the larger ones. Efficiency is 95% in line mode, 88% in AVR mode and 60% in battery mode. The battery is 12 V/9 Ah (1 block), 12 V/7 Ah (2 blocks) and 12 V/9 Ah (2 blocks), with estimated backup at 100 W of 20, 40 and 50 minutes; recharge is 90% in 4 hours after full discharge.
Physically, product size is 100 x 143 x 290 mm (850 VA) to 139 x 195 x 364 mm (1200-2200 VA) and weight 5.2, 7.9 and 10.4 kg; packaged size and weight are given separately. Noise is under 40 and 45 dB and operation is 0-40 C. Protection covers discharge, overcharge and overload; there is RJ11 and RJ45 line protection and a USB interface, with no external slot. Warranty is 6-year parts and 1-year batteries.
Key points
- Three models: TMP850IEC 850 VA/480 W, TMP1200IEC 1200 VA/600 W, TMP2200IEC 2200 VA/1200 W.
- Output power factor 0.56, 0.5 and 0.55.
- Input 230 VAC, window 170-280 VAC; battery-mode output +/-10% and +/-1 Hz; stepped sine.
- Transfer time typically 2-6 ms (850 VA) and 4-8 ms (1200 and 2200 VA).
- Efficiency: 95% in line mode, 88% in AVR mode, 60% in battery mode.
- Battery 12 V/9 Ah x1, 12 V/7 Ah x2, 12 V/9 Ah x2; backup at 100 W of 20, 40 and 50 min.
- Size 100 x 143 x 290 mm and 139 x 195 x 364 mm (W x H x D); weight 5.2, 7.9, 10.4 kg.
- Warranty 6-year parts, 1-year batteries; output sockets 3 and 6 x IEC 10 A.
Using it in design
- With a 0.5-0.56 output power factor, select by W; the 2200 VA model gives only 1200 W.
- Verify compatibility of the stepped sine output with the load's power supply type.
- Runtime is quoted for 100 W; scale it if the real load differs.
- Battery-mode efficiency is 60%, so for long backup evaluate load power together with battery capacity.
- Use a double-conversion UPS for critical white-space load; Tempo is for small edge loads.
Who should read it
Those selecting line-interactive UPSs for small office, network and edge loads.
Document contents
- Product summary and features
- Input
- Output
- Efficiency
- Battery
- Surge suppression
- Physical
- Environment
- Interface and warranty
Publication details
- Authors
- Uniti Power / Secure Power Ltd
- Publisher
- Uniti Power / Secure Power Ltd
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Uniti Power / Secure Power Ltd Uniti Power Tempo Series 850/1200/2200 VA Data Sheet. Uniti Power / Secure Power Ltd. https://unitipower.com/media/downloads/uniti/Uniti-Tempo-Data-Sheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.