Uniti Power Symphony Range Brochure V1.2025
Uniti Power / Secure Power Ltd
A manufacturer brochure for a 1.5 kVA to 10 kVA rack/tower double-conversion UPS family, giving nominal power, output voltage, efficiency, external battery modules and technical specifications.
On this page
Overview
The Symphony family has four models: SPY1500RMi2U (1500 VA / 1500 W), SPY3000RMi2U (3000 VA / 3000 W), SPY6KiRTB (6000 VA / 6000 W) and SPY10KiRTB (10000 VA / 10000 W). All have a power factor of 1.0. The 1.5 and 3 kVA models are 2U and the 6 and 10 kVA models 5U rack/tower. Double-conversion efficiency is 85% for the 1.5 kVA model, 93% for the 3 kVA and 95% for the 6 and 10 kVA; in ECO mode it rises to 97% and 98% respectively.
At the input the 1.5 and 3 kVA models carry full load across 160-300 V and derate linearly to 50% load between 110 and 160 V. Output is 200/208/220/230/240 VAC, with power derating at low output voltage: 10% at 208 V and 20% at 200 V. The 6 and 10 kVA models have an input of 160-275 V and an output of 220/230/240 V, and over their 0-50 °C operating range power drops to 50% between 40 and 50 °C.
For the 6 and 10 kVA configurations the power module (438x573x86.2 mm, 2U) and battery module (438x593x129 mm, 3U) are defined with separate dimensions; total height is 5U. The internal battery is 240 VDC (20 x 12 V / 9 Ah) and gives 7.9 minutes at full load and 19.2 minutes at half load on the 6 kVA, and 3.8 and 9.3 minutes on the 10 kVA. With external battery modules (EBMs) runtime rises, for example to 183.3 minutes at half load on the 6 kVA with 5 modules. Parallel operation of up to three units is optional on the 6 and 10 kVA models; the 1.5 and 3 kVA models have no parallel option.
For monitoring the range offers the UPNETG2 network management card (SNMP v1/v3, Modbus TCP, MQTT, REST API), Winpower G2 and SPS G2 software, a volt-free relay card (SPYREL), an environment probe and a parallel card (SPYPK). The warranty is 6 years on electronic components and 2 years on internal batteries and accessories.
Key points
- Models: SPY1500RMi2U, SPY3000RMi2U, SPY6KiRTB, SPY10KiRTB; all PF 1.0, true on-line double conversion.
- Efficiency: double conversion 85% (1.5 kVA), 93% (3 kVA), 95% (6 and 10 kVA); ECO mode 97% (1.5 and 3 kVA) and 98% (6 and 10 kVA).
- 1.5 and 3 kVA: power derating at low output voltage, 10% at 208 V and 20% at 200 V.
- Input voltage: 160-300 V full load for 1.5 and 3 kVA; 160-275 V for 6 and 10 kVA; load derates to 50% between 110 and 160 V.
- 6 and 10 kVA: power module 438x573x86.2 mm (2U), battery module 438x593x129 mm (3U).
- Internal battery runtime (full / half load): 3.3 / 8.7 min (1.5 kVA), 3.5 / 9.1 min (3 kVA), 7.9 / 19.2 min (6 kVA), 3.8 / 9.3 min (10 kVA).
- Up to 3 units in parallel (optional) for 6 and 10 kVA; 1.5 and 3 kVA do not support parallel.
- Transfer time 0 ms (line/bypass 4 ms, ECO/inverter 10 ms); overload 100-105% continuous, 105-125% for 3 min (1.5 and 3 kVA) or 10 min (6 and 10 kVA).
- Altitude derating: 1% per 100 m between 1000 and 3000 m.
Using it in design
- In small and edge rooms read the nominal power against the model's output voltage; on 200 and 208 V supplies the 1.5 and 3 kVA models are derated.
- Before taking the ECO-mode efficiency into the design PUE, check that the ECO-to-inverter transfer is 10 ms and compatible with load sensitivity.
- Compare the runtime requirement with the internal battery runtime; for longer runtime pick the EBM count from the table (at most 6 modules for the 6 kVA and 10 kVA).
- If N+1 is needed, build it only from the 6 and 10 kVA models, with the parallel card and up to three units.
- In the rack layout account for the 5U height and the separate weight and size of the battery module.
Who should read it
Electrical and IT infrastructure engineers selecting UPSs for edge and small critical rooms.
Document contents
- Symphony range introduction
- True online double-conversion technology
- Connectivity: UPNETG2, Winpower G2, SPS G2
- Accessories and external battery modules
- Model table and runtime
- 1500VA and 3000VA technical specifications
- 6kVA and 10kVA technical specifications
Publication details
- Authors
- Uniti Power / Secure Power Ltd
- Publisher
- Uniti Power / Secure Power Ltd
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Uniti Power / Secure Power Ltd (2025). Uniti Power Symphony Range Brochure V1.2025. Uniti Power / Secure Power Ltd. https://unitipower.com/media/downloads/uniti/Uniti-Power-Symphony-Range-Brochure-V1.2025.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.