AdPoS Maxi-J E 19-inch module 10–20 kVA datasheet
AdPoS
A datasheet dated November 2023 from German manufacturer AdPoS for the Maxi-J E 19-inch UPS module, built for installation in industrial cabinets such as IP54 enclosures: three models of 10, 15 and 20 kVA with 8, 12 and 16 kW active power, at least 95% efficiency in on-line operation, and 440 x 735 x 130 mm and 34 kg without batteries.
On this page
Overview
The Maxi-J E is a 19-inch UPS module placed inside a cabinet or enclosure to provide uninterrupted power in industrial areas considered critical because of ambient conditions. The example in the datasheet shows the module mounted in a Rittal IP54 cabinet with a fan, with a separate battery compartment. The unit works on the on-line double-conversion principle; the rectifier uses IGBTs and draws a near-sinusoidal current even at part load. A separate supply input for the bypass is optional and raises availability for critical processes. Battery start is possible.
Input and output are 380/400/415 V AC, three-phase with neutral. The input voltage range is -25% to +20% at full load and -40% to +20% at 80% load; the frequency range is 40 to 70 Hz. Input current distortion is at most 3% on linear load and input power factor at least 0.99 at full load. The technical table gives an output power factor of 0.8 and lists active power as 8, 12 and 16 kW, while the feature list on the first page states an output power factor of 0.9. The kW values in the table are the basis for design.
The battery circuit has a nominal voltage of ±240 V DC; the standard is 40 blocks, configurable from 30 to 44, with a maximum charging current of 5 A. Efficiency is at least 95% in on-line mode and at least 99% in eco mode. The module's degree of protection is IP20, and higher protection comes from the cabinet it is installed in. Ambient temperature is 0 to +40 °C, and installation altitude is up to 1000 m without derating, with a 1% reduction per 100 m between 1000 and 2000 m. The datasheet is in German.
Key points
- Models: 10 kVA / 8 kW, 15 kVA / 12 kW, 20 kVA / 16 kW; output power factor 0.8 in the technical table.
- Dimensions 440 x 735 x 130 mm (W x D x H), weight 34 kg without batteries; the same for all three models.
- Efficiency: at least 95% in on-line mode, at least 99% in eco mode.
- Input: THDi at most 3% (linear load), power factor at least 0.99 (full load); voltage range -25%/+20% at full load.
- Overload: 105% continuous, up to 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute; short-circuit current 2.5 x In for 200 ms.
- Battery: ±240 V DC, 40 blocks (configurable 30 to 44), maximum charging current 5 A, float voltage 2.27 V per cell.
- Noise at most 60 dB(A) at 1 m; degree of protection IP20; EMC class C3 (EN 62040-2).
- Interfaces: relay contacts, RS-232, SNMP (optional adapter); an emergency off function is provided.
Using it in design
- Match the load to the active power in the table (8, 12, 16 kW); do not rely on the 0.9 power factor in the feature list without confirmation from the manufacturer.
- Because the module is IP20, provide an IP54 cabinet with fan or air conditioner in dusty or humid areas, and confirm by heat calculation that the temperature inside stays at or below 40 °C.
- Calculate heat loss from the 95% efficiency (about 0.8 kW at 16 kW load) and add it to the cabinet cooling load.
- Check that the 5 A maximum charging current recharges the chosen battery capacity in an acceptable time.
- For critical processes, specify the separate bypass supply option and feed the bypass line from a different source.
Who should read it
Electrical and automation engineers designing in-cabinet UPS for industrial environments or edge sites.
Document contents
- Leistungsmerkmale
- Eingang
- Ausgang
- Batterie
- Abmessungen und Gewichte
- Betriebsarten
- Allgemein
Publication details
- Authors
- AdPoS
- Publisher
- AdPoS
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AdPoS AdPoS Maxi-J E 19-inch module 10–20 kVA datasheet. AdPoS. https://www.adpos-ups.de/wp-content/uploads/2024/07/AdPoS-Maxi-J-E-10-20kVA-DE.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.