AdPoS Maxi-J I Pro XS TY 10–20 kVA datasheet

AdPoS

A two-page datasheet dated January 2023 from German manufacturer AdPoS for the three-phase input, three-phase output Maxi-J I Pro XS TY UPS series: three models rated 10 kVA/10 kW, 15 kVA/15 kW and 20 kVA/18 kW, efficiency up to 96%, parallel operation of up to 8 units, and 120 kg without batteries.

On this page

Overview

The datasheet describes a tower UPS family designed for internet data centres, service providers, server rooms, and industrial and medical applications. The three models share one cabinet of 380 x 840 x 1400 mm (width, depth, height). Batteries sit inside the cabinet: up to 120 blocks of 12 V, 7 Ah or 9 Ah (3 strings of 40) can be fitted, and total weight depends on the battery complement. There are separate switches for input, bypass, maintenance, output and battery, and eight sensors watch temperature, overload, battery undervoltage, fan failure and short circuit.

The input is 380/400/415 V AC three-phase with neutral and PE. At full load the input voltage range is 304 to 478 V phase to phase; between 228 and 304 V the load is reduced linearly from 100% to 75%. Input power factor is above 0.99 and current distortion below 3% at full linear load. Output voltage accuracy is ±1.5%, and voltage distortion is below 1% on linear load and below 6% on non-linear load. Transfer time between bypass and inverter is 0 ms. Efficiency is above 95% in both mains and battery mode.

The rated power row gives the 20 kVA model as 18 kW, while the common output power factor row states 1. The 10 and 15 kVA models are therefore assessed at unity power factor and the 20 kVA model at 0.9. A footnote in the datasheet refers to a 30 kVA model and states that its power factor is 1 up to 30 °C and 0.9 above. Operating temperature is 0 to 40 °C and altitude up to 1000 m without derating. The datasheet is in German and cites IEC/EN 62040-1, 62040-2 and 62040-3.

Key points

  1. Models: 10 kVA / 10 kW, 15 kVA / 15 kW, 20 kVA / 18 kW.
  2. Cabinet 380 x 840 x 1400 mm (W x D x H); UPS weight 120 kg without batteries.
  3. Efficiency up to 96%; above 95% in mains and battery mode.
  4. Input power factor above 0.99, THDi below 3% (full linear load); input frequency 40 to 70 Hz.
  5. Inverter overload capacity: up to 110% for 1 hour, 110% to 125% for 10 minutes, 125% to 150% for 1 minute; bypass 125% continuous.
  6. Battery: ±240 V DC (480 V DC in total), 12 V 7 Ah or 9 Ah blocks, up to 120; charging power up to 20% of UPS rated power.
  7. Parallel operation of up to 8 units (optional); battery start optional.
  8. Noise at 1 m is 58 dB at full load and 55 dB at 45% load; degree of protection IP20.

Using it in design

  • Size the 20 kVA model against its 18 kW limit; with unity power factor IT load the usable power is 18 kW.
  • Because internal battery capacity is limited to 7 or 9 Ah blocks, confirm the required backup time against the manufacturer's discharge tables.
  • Add battery mass to the 120 kg cabinet weight in the floor loading; up to 120 blocks raise total mass considerably.
  • Write the parallel option (up to 8 units) into the specification for N+1 or capacity growth.
  • On sites with a weak grid, allow for the load being limited to as little as 75% at low mains voltage (228 to 304 V).

Who should read it

Electrical engineers selecting 10 to 20 kVA three-phase UPS units for server rooms and small data centres.

Document contents

  1. Anwendungen
  2. Besonderheiten
  3. Eingang
  4. Bypass
  5. Output
  6. Battery
  7. Wirkungsgrad
  8. System
  9. Allgemeine Daten
  10. Abmessungen und Gewichte

Publication details

Authors
AdPoS
Publisher
AdPoS
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AdPoS AdPoS Maxi-J I Pro XS TY 10–20 kVA datasheet. AdPoS. https://www.adpos-ups.de/wp-content/uploads/2024/02/AdPoS-Maxi-J-I-Pro-XS-TY-10-20kVA-DE_220224.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.