AdPoS Mini-J II 1000/2000/3000 VA datasheet

AdPoS

A four-page datasheet dated August 2021 from German manufacturer AdPoS for the single-phase on-line double-conversion Mini-J II UPS series: 1000, 2000 and 3000 VA (900, 1800 and 2700 W) in the 230 V version, plus 1500 VA in the 120 V version, with efficiency above 90% in line mode and above 96.5% in eco mode.

On this page

Overview

The Mini-J II is a digitally controlled on-line UPS designed with a short installation depth for telecommunication tasks. It can stand alone as a tower or be fitted in a 19-inch cabinet. The datasheet gives the 120 V and 230 V versions in the same table on separate rows: the 230 V version comes as 1K, 2K and 3K models, and the 1.5K column belongs to the 120 V version only. Output power factor is 0.9 on all models. Batteries can be replaced during operation, and battery extension modules and additional chargers are offered.

On the 230 V version the input voltage range depends on load: 180 to 300 V at full load, from 150 V up to 75% load and from 110 V up to 60% load. Input power factor is 0.99 at full linear load. Output voltage is set to 200, 208, 220, 230 or 240 V with static regulation within ±1%; voltage distortion is below 3% at full linear load and below 6% at full non-linear load. Transfer from mains to battery takes 0 ms, and transfer from inverter to bypass is typically 4 ms on the 230 V version.

Backup time on internal batteries is short: on the 230 V models it is 1 to 4 minutes at full load and 6 to 11 minutes at half load, depending on model and battery complement. Recharge to 90% takes 4 to 8 hours depending on model. The inverter runs continuously up to 105% load and moves to bypass after 30 seconds at 106% to 120% and after 10 seconds at 121% to 150%. The 230 V version is offered in 2U rack, 3U/4U rack and tower cases; the 2U cases measure 440 x 88 x 405 mm or 440 x 88 x 600 mm. The datasheet is in German.

Key points

  1. Ratings: 1000 VA / 900 W, 1500 VA / 1350 W (120 V only), 2000 VA / 1800 W, 3000 VA / 2700 W.
  2. Efficiency (full linear load, 230 V): above 90% for 1K, 91% for 2K and 91.5% for 3K in line mode; above 86% in battery mode and above 96.5% in eco mode.
  3. Input power factor 0.99; output voltage distortion below 3% on linear load and below 6% on non-linear load; crest factor 3:1.
  4. Transfer time: 0 ms from mains to battery; typically 4 ms from inverter to bypass on the 230 V version.
  5. Backup time on the 230 V version is 1 to 4 minutes at full load and 6 to 11 minutes at 50% load; above 2550 W the maximum backup time is 30 minutes.
  6. Battery blocks are 12 V 7.2 Ah or 9 Ah; nominal battery voltage is 24 to 96 V DC depending on model.
  7. Input connection on the 230 V version is IEC 320-C14 (10 A) for 1K and 2K and IEC 320-C20 (16 A) for 3K.
  8. Operating temperature 0 to 40 °C; standard interfaces RS-232, USB and EPO; SNMP/web card optional.

Using it in design

  • Match the load to the watt rating: the 3000 VA model carries 2700 W.
  • Compare the 1 to 4 minute internal backup time at full load with generator start time, and add a battery extension module and additional charger where it falls short.
  • In the rack layout, allow for the 600 mm depth of the 2K and 3K models plus rear cable clearance.
  • State the voltage version (120 V or 230 V) and case type (2U, 3U/4U, tower) explicitly before ordering; the 1500 VA model does not exist in the 230 V version.
  • Enable eco mode only where mains quality is adequate and the load tolerates the 4 ms transfer.

Who should read it

Engineers and IT infrastructure staff selecting small single-phase UPS units for network cabinets, telecom rooms and edge sites.

Document contents

  1. Merkmale
  2. Nennleistung
  3. Eingang
  4. Ausgang
  5. Wirkungsgrad
  6. Batterie
  7. Ladegerät
  8. Umschaltzeit
  9. Frontplatte
  10. Schutz
  11. Abmessungen und Gewicht
  12. Schnittstelle
  13. Umgebungsbedingungen
  14. Normen und Zertifizierungen

Publication details

Authors
AdPoS
Publisher
AdPoS
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AdPoS AdPoS Mini-J II 1000/2000/3000 VA datasheet. AdPoS. https://www.adpos-ups.de/wp-content/uploads/2022/06/AdPoS-Mini-J-II-1000-2000-3000VA-DE.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.