Milleteknik SINUS UPS 200W S: Swedish online manual
Milleteknik
The Milleteknik SINUS UPS 200W S is a wall-mounted offline UPS for camera surveillance, PoE switches and gate control, with 200 W continuous power, 230 V single-phase sine output, a typical 20 ms transfer time and a weekly automatic battery test.
On this page
Overview
The Swedish online manual describes Milleteknik's SIN series offline UPS (SINUS UPS 200W S, article SM01U0011FP002B70). The UPS normally feeds the load from the mains and, on mains failure, feeds it from the batteries through the inverter. The unit is for fixed installation and must be installed by an authorised installer. The main uses are camera surveillance, PoE switches and other security systems, and industrial and garage gate controls. The manual covers installation, commissioning, maintenance, battery replacement, sizing, alarm indicators and technical data.
The technical data give a single-phase 230 V sine output: continuous power 200 W, maximum operating power 200 W and a short-term maximum starting power of 1 kVA (no continuous kVA value is given). Input is 230 V (-15%, +20%); battery-mode output is 230 V -10%. Efficiency is about 90%, no-load power about 10 W and charging current 1 A. Transfer time is typically 20 ms. The battery is 24 V (the manual names a 7.2 Ah 12 V AGM battery) and is not included; replacement is advised every 10-12 years, and at +5 to +15 / +25 to +30 C battery ageing is twice as fast.
Protections are electronic current limiting (300% of rated capacity), shutdown within 5 seconds on heavy overload or short circuit with automatic restart when the mains returns, deep-discharge protection below 19 V and overcharge disconnection at 27.9 V. A weekly automatic test runs the UPS for 6 seconds with an internal test load and checks the battery, output voltage and inverter. The battery test raises a battery-fault alarm if the end voltage is below 24.0 V or the voltage drops by more than 2.5 V. Alarms are given on a potential-free relay contact.
The enclosure is sheet metal, white, IP20, wall-mounted, 230 mm high, 216 mm wide and 85 mm deep; battery dimensions are given separately from the enclosure. Ambient temperature is +5 to +40 C (+15 to +25 C for best battery life), humidity 20-90% and environmental class 1, indoor. Compliance: EMC 2014/30/EU, low voltage 2014/35/EU, EN 62368-1, CE. The manual advises keeping the load below rated power, not exceeding the starting power, and carrying out backup operation within one hour of a mains loss.
Key points
- Offline topology; continuous active power 200 W; no kVA value given.
- Starting power up to 1 kVA; electronic current limiting at 300% of rated capacity.
- Input 230 V (-15%, +20%); battery-mode output 230 V -10%; single-phase sine.
- Efficiency about 90%; no-load power about 10 W; charging current 1 A.
- Typical transfer time 20 ms.
- Battery 24 V (7.2 Ah 12 V AGM type) not included; replace after 10-12 years.
- Deep-discharge protection at 19 V; overcharge cut-off at 27.9 V.
- Weekly automatic test (6 s); potential-free relay alarm.
- Enclosure 230 x 216 x 85 mm (H x W x D), white, IP20, wall mounting.
- Ambient +5 to +40 C (+15 to +25 C for the battery), humidity 20-90%.
Using it in design
- Compare the load with 200 W continuous and 1 kVA starting power; add up camera and PoE loads with a margin.
- Assess the typical 20 ms transfer time against load sensitivity; prefer an on-line UPS for interruption-sensitive IT loads.
- Add the battery dimensions separately from the enclosure to the layout and procure the battery separately.
- Connect the weekly self-test alarm contact to remote monitoring or the building management system.
- If ambient exceeds +25 C, plan a battery replacement interval shorter than 10-12 years.
Who should read it
Installers and electricians seeking a simple wall-mount UPS for security, gate automation and small network loads.
Document contents
- Summary
- Safety
- Component overview
- Mounting and connection
- Commissioning
- Maintenance and battery replacement
- UPS sizing
- Alarm and status indicators
- FAQ and checks
- Technical specifications
Publication details
- Authors
- Milleteknik
- Publisher
- Milleteknik
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Milleteknik Milleteknik SINUS UPS 200W S: Swedish online manual. Milleteknik. https://www.milleteknik.se/Manualer/SIN/200WS/sv/index-sv.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.