Technical guideFree to readYear not stated

Milleteknik SINUS UPS 600W FLX L: Swedish online manual

Milleteknik

Swedish online manual for Milleteknik's 600 W offline UPS: 444 x 438 x 212 mm enclosure, two 12 V 45 Ah batteries, about 20 ms transfer time and a built-in self-test system.

On this page

Overview

The manual covers installation, commissioning, operation and technical data for the SINUS UPS 600W FLX L, article code FL01U0021FP006. It is an offline UPS that takes over the output when mains fails and supplies a current-limited sine voltage until mains returns or the batteries are fully discharged. Transfer time is about 20 ms and the output is single-phase sine.

The installation section treats wall mounting and 19-inch rack mounting separately. The enclosure is 10 U high with dimensions of 444 mm height, 438 mm width and 212 mm depth, and has an IP 32 rating. At least 100 mm of free space is asked for above and beside the unit for ventilation, and mounting at a working height of 1.4 to 1.8 m is recommended. An isolating load switch on the incoming mains is required. Wiring goes through the two-board MiniSinus main board, which provides a PICTO output and an emergency lighting output that is live only during mains failure.

The technical data section details protection and monitoring. Batteries charge to an end voltage of 27.3 V, deep-discharge protection acts below 19 V, and the unit shuts down within 3 to 5 seconds on severe overload or short circuit. The self-test system monitors battery charging, battery ageing and the inverter, and raises an alarm when battery capacity has fallen 20 to 40 percent from new. Alarms are passed on through potential-free relay contacts.

The document is a product manual aimed at small loads such as camera surveillance, PoE switches and gate or garage-door control, not at data-centre systems. The product is not intended for emergency-lighting control. The original language of the manual is Swedish; other languages may be machine translations.

Key points

  1. Maximum continuous power 600 W; the main board allows 1 kVA peak start power and a 5 A charge current.
  2. Enclosure 444 x 438 x 212 mm (height x width x depth), 10 U, IP 32, wall or 19-inch rack mounting, ambient +5 to +40 °C (+15 to +25 °C for best battery life).
  3. Two 12 V, 45 Ah AGM batteries fit; batteries are not included. The reference battery weighs 14.5 kg.
  4. Transfer time about 20 ms; efficiency about 90 percent; no-load power about 10 W while the inverter runs.
  5. Input 230 V AC, -15 percent to +20 percent; battery-mode output 230 V AC, -10 percent.
  6. Battery end-of-charge voltage 27.3 V, deep-discharge protection below 19 V, overcharge cut-off at 27.9 V.
  7. The self-test turns 20 to 40 percent capacity loss into an alarm; the mains-failure alarm is given within 3 seconds.
  8. Backup operation should take place within one hour of a mains failure because the inverter draws idle power.

Using it in design

  • Keep the connected load below 600 W, leaving margin for cable losses, and check the short-term start power of loads against the 1 kVA limit.
  • Calculate backup runtime using the 10 W idle draw and the practical 5 to 6 year replacement interval of 45 Ah batteries.
  • Reserve 100 mm free space above and below in a rack, and above and beside on a wall, in the layout plan.
  • Wire the potential-free alarm relays into monitoring; mains failure, incorrect charge voltage, aged battery and inverter fault can be tracked separately.

Who should read it

Designers who select small UPS units for surveillance, PoE and access-control systems, and technicians who install them.

Document contents

  1. About Sinus UPS from Milleteknik
  2. Installation and commissioning
  3. Mounting: wall and 19-inch rack
  4. Connection: battery, mains input, 230 V output, alarm
  5. Inverter, battery, charger and protection functions
  6. Self-test system
  7. Maintenance and battery replacement
  8. Sizing
  9. Front panel and status indications
  10. FAQ and alarm check procedures
  11. Technical specifications
  12. Warranty and support

Publication details

Authors
Milleteknik
Publisher
Milleteknik
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Milleteknik Milleteknik SINUS UPS 600W FLX L: Swedish online manual. Milleteknik. https://www.milleteknik.se/Manualer/SIN/600WFLXL/sv/index-sv.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.