Addressing Data Center Thermal Capacity with Rear Door Heat Exchangers (Cisco and DeepCoolAI)
Original title Addressing Data Center Thermal Capacity with Rear Door Heat Exchangers
Cisco and DeepCoolAI
Cisco and DeepCoolAI's solution brief: passive and active rear door heat exchangers (RDHx) up to 200 kW in 42U, 48U and 52U sizes, with the CDAI-RDHX-60 model giving up to 57 kW of cooling.
On this page
Overview
The document is a solution brief introducing the partnership between Cisco and DeepCoolAI. The growing density and power consumption of Cisco's AI computing platforms create cooling challenges; DeepCoolAI's RDHx (rear door heat exchanger) product line removes heat directly from the rack, reducing the need for traditional air conditioning and lowering energy use.
The solution section says DeepCoolAI offers passive and active RDHx: capacity up to 200 kW, cabinet heights of 42U, 48U and 52U, widths of 600 mm and 800 mm, and power supply of 208-277 VAC or 48 VDC. The design can be customised to client requirements. The CDAI-RDHX-60 model shown gives up to 57 kW of cooling.
Features include thickened copper pipe, casters at the bottom, a hinge built for the added load, top or bottom connection, retrofit onto existing racks, 18 hot-swappable variable-speed fans, BMS connection, dew-point control and a smart valve system. Benefits listed are removal of up to 100% of rack heat, potential cooling-energy savings of up to 70% against traditional air cooling, and an estimated 2-3 year return on investment.
The document is a joint marketing brief. The figures are the vendors' or general estimates citing third-party sources; it holds no measured and certified capacity for a specific model, no entering and leaving water temperatures and no net sensible definition.
Key points
- Passive and active RDHx are offered with capacity up to 200 kW.
- Cabinet sizes 42U, 48U, 52U; widths 600 mm and 800 mm.
- Power supply 208-277 VAC or 48 VDC.
- The CDAI-RDHX-60 model gives up to 57 kW of cooling with 18 hot-swappable variable-speed fans.
- Top or bottom connection; retrofit onto existing racks is possible.
- Dew-point control, a smart valve system and BMS connection are included.
- The vendor states RDHx can remove up to 100% of rack heat.
- Up to 70% potential reduction in cooling energy against traditional air cooling and a 2-3 year ROI estimate for liquid cooling are cited.
Using it in design
- For high-density AI racks, select RDHx by capacity, cabinet size (42U-52U) and electrical supply type (208-277 VAC or 48 VDC).
- When choosing between active and passive RDHx, add fan power and hot-swap needs to the per-rack energy calculation.
- Connect dew-point control and smart valve data to the BMS and keep water temperature above room dew point.
- For retrofit onto existing racks, check hinge load, casters and door-swing clearance.
- Recalculate savings and payback claims from project measurements instead of using them as general estimates; ask the vendor for the test condition behind any model capacity.
Who should read it
Mechanical engineers and platform architects evaluating rear-door cooling for AI and high-density racks.
Document contents
- Partner Alliance Solution Brief
- The Challenge
- The Solution: Rear Door Heat Exchanger
- Key Features
- Key Benefits
Publication details
- Authors
- Cisco and DeepCoolAI
- Publisher
- Cisco and DeepCoolAI
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Cisco and DeepCoolAI Addressing Data Center Thermal Capacity with Rear Door Heat Exchangers. Cisco and DeepCoolAI. https://www.cisco.com/c/dam/en/us/td/docs/engineering_alliances/DeepCoolAI-Cisco_Soluton_Brief.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.