LOVATO PD135GB11_18 Enclosed automatic transfer switches ATS
LOVATO Electric
LOVATO Electric's leaflet PD135GB11_18, dated November 2018, presents the ATP series of ready-to-connect automatic transfer switches in IP65 metal enclosures. The series covers six four-pole contactor models rated 45 A to 160 A in AC1, equivalent to 31 to 111 kVA at 400 V.
On this page
Overview
The leaflet introduces LOVATO Electric's ATP series: factory-wired, contactor-based transfer panels that switch the load automatically or manually between a main line and a secondary line such as a generator set. Each panel comes in an IP65 metal enclosure painted RAL 7035 and combines four components: the ATL 600 automatic transfer switch controller, four-pole BF series contactors with electrical and mechanical interlock, the ATL DPS1 dual power supply module, and P1 MB series miniature circuit breakers (1 A, C curve, 10 kA) protecting the measuring lines.
The controller monitors both lines with independent thresholds and timings: phase sequence and phase loss, voltage asymmetry, minimum and maximum voltage, and minimum and maximum frequency. The ATL 600 manages the contactors and commands the generator set; its backlit graphic LCD shows system status, voltage and frequency measurements, statistics and alarms. The internal memory records up to 100 events. There are six programmable digital inputs and seven programmable relay outputs, and the interface offers five languages.
The panels are designed for 230/400 V AC low-voltage systems and take their 230 V AC auxiliary supply from the input lines. The order table lists six codes with AC1 operating current, equivalent power at 230 V and 400 V, and enclosure dimensions: the 45, 60, 80 and 100 A models use a 500 × 400 × 200 mm enclosure, and the 125 and 160 A models a 600 × 400 × 200 mm enclosure. The series complies with IEC 60947-6-1 and IEC 60947-4-1.
The document is a four-page product leaflet. It carries no transfer time, short-circuit withstand current, IEC 60947-6-1 utilisation category or weight. The current ratings apply to AC1 duty (resistive or slightly inductive loads); contactor selection for motor or heavily inductive loads is assessed separately. The manufacturer lists data centres among the application fields, and the 160 A upper limit places the series at the scale of small equipment rooms, edge sites and auxiliary service boards.
Key points
- ATP series: IP65 metal enclosure, ATL 600 controller, four-pole interlocked BF contactors, ATL DPS1 dual power supply module and P1 MB measuring-line breakers (1 A, C curve, 10 kA).
- Six models with AC1 operating currents of 45, 60, 80, 100, 125 and 160 A, all four-pole.
- Equivalent power at 400 V is 31, 42, 55, 69, 87 and 111 kVA respectively; at 230 V it is 10, 14, 18, 23, 29 and 37 kVA.
- Enclosure dimensions (H × W × D): 500 × 400 × 200 mm for 45 to 100 A, 600 × 400 × 200 mm for 125 and 160 A.
- Voltage measurement inputs: rated 100...480 V AC (line to line), measuring range 50...576 V AC, frequency 45...65 Hz.
- Monitored line quantities: phase sequence, phase loss, voltage asymmetry, under and over voltage, under and over frequency.
- 6 programmable digital inputs and 7 programmable relay outputs (6 NO and 1 changeover, 8 A 250 V AC); 100-event log.
- Compliance: IEC 60947-6-1 and IEC 60947-4-1.
Using it in design
- Select the model by comparing load current with the AC1 rating: a load of up to 69 kVA at 400 V needs the 100 A model, and up to 111 kVA needs the 160 A model.
- Where the neutral is earthed separately at each source, show on the single-line diagram that the four-pole construction also switches the neutral.
- Allow for the 500 × 400 × 200 mm or 600 × 400 × 200 mm enclosure and the top and bottom cable-entry flanges in the panel layout.
- Transfer time and short-circuit withstand are not in the leaflet, so take them from the manufacturer's technical data for upstream protection coordination and for the IT load's interruption tolerance.
- Wire the generator start command and alarm outputs from the ATL 600 programmable relays to the building monitoring system.
Who should read it
Electrical designers and panel builders selecting mains-to-generator transfer panels for small and medium facilities.
Document contents
- Enclosed automatic transfer switches ATS
- Control functions of the lines
- Automatic transfer switch controllers type ATL 600, Dual power supply module type ATL DPS1, MCBs P1 MB series, Four-pole interlocked contactors BF series, Enclosure
- Application fields
- Operational characteristics
- Order codes
Publication details
- Authors
- LOVATO Electric
- Publisher
- LOVATO Electric
- Year
- 2018
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LOVATO Electric (2018). LOVATO PD135GB11_18 Enclosed automatic transfer switches ATS. LOVATO Electric. https://catalogue.lovatoelectric.com/gl_en/Product/GetDocument?doc=Depliant%5CAUTOMATIC-TRANSFER-SWITCH-CONTROLLERS%5CPD135GB11_18.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.