ELITUPS three-phase static transfer switch STS series, Rev.0
ELIT
A five-page Rev. 0 sheet from Italian manufacturer ELIT Srl describing its three-phase STS series static transfer switches: 100, 150, 200, 250, 300, 400 and 600 A models in 3-pole and 4-pole versions, with transfer time of at most 4 ms between synchronised sources and 99.5% efficiency at full load.
On this page
Overview
The sheet covers a family of solid-state transfer switches that move a load between two independent AC sources without interruption. The STS monitors both sources continuously; one is assigned as primary and the other as alternate. When the feeding line leaves the user-defined voltage or frequency band the load moves automatically to the alternate source, and it is returned to the preferred source once voltage is back in band. Transfer can be automatic, manual or remote. The manufacturer states that transfer time is below a quarter period and recommends that both sources be online UPSs for maximum protection.
All models are defined for 380-400-415 VAC 3Ph+N at 50/60 Hz (48-64 Hz) and come in a 3-pole version (phases only) or a 4-pole version (phases and neutral). Transfer time after a source failure is at most 4 ms with synchronised sources, 10 ms with unsynchronised sources and at most 2 ms for manual switching. Synchronous transfer is controlled in zero-current mode. Asynchronous transfer can be set three ways: with a delay from 20 to 255 ms, with zero-current mode, or disabled.
Overload capability varies by model. Every model carries 120% for 60 minutes. The 10-minute value lies between 140% and 170% and the 1-minute value between 180% and 250%; for example 140% and 180% for STS 100, 170% and 250% for STS 200, and 160% and 220% for STS 600. An output circuit breaker is standard and an input breaker is optional. A maintenance bypass and an output isolator give full isolation during maintenance. Power supply circuits and ventilation are redundant.
Mechanical data is given per model. The STS 100 cabinet is 685 x 530 x 1500 mm and weighs 145 kg in 3-pole and 175 kg in 4-pole form. The 200-400 A models sit in a 685 x 580 x 1770 mm cabinet at 195-255 kg. The STS 600 cabinet is 915 x 735 x 1905 mm and weighs 340 kg in 3-pole and 375 kg in 4-pole form. Noise at 1 m is below 52, 55 or 60 dBA depending on model. Communication is through RS232, a 7-contact relay board (4 programmable) and an SNMP accessory slot. Standards are EN 62310-1 and EN 62310-2.
Key points
- Models: STS 100, 150, 200, 250, 300, 400 and 600 A; 3-pole and 4-pole (switched neutral) versions.
- Voltage: 380-400-415 VAC 3Ph+N, 50/60 Hz (48-64 Hz).
- Transfer time: ≤ 4 ms with synchronised sources, 10 ms unsynchronised, ≤ 2 ms for manual switching.
- Asynchronous transfer: with settable delay of 20-255 ms, with zero-current mode, or disabled.
- Overload: 120% for 60 minutes on all models; 140-170% for 10 minutes and 180-250% for 1 minute depending on model.
- Efficiency: 99.5% at 100% load.
- Weight (3-pole / 4-pole): STS 100 145/175 kg, STS 150 165/190 kg, STS 200 195/205 kg, STS 600 340/375 kg.
- Cabinet: STS 100 685 x 530 x 1500 mm, STS 150 685 x 700 x 1500 mm, STS 200-400 685 x 580 x 1770 mm, STS 600 915 x 735 x 1905 mm.
- Ambient 0-40 °C; noise at 1 m < 52 dBA (100-150 A), < 55 dBA (200-400 A), < 60 dBA (600 A).
- Standards: EN 62310-1 (safety), EN 62310-2 (EMC), CE.
Using it in design
- Use an STS to connect single-fed PDUs and loads to two UPS buses in a 2N or distributed-redundant architecture, and choose the current rating from the downstream PDU current.
- Where the neutrals of the two sources are earthed separately in a TN-S system, choose the 4-pole version; with a common neutral the 3-pole version is sufficient. Record the decision on the earthing diagram.
- Specify that the two UPS outputs are kept synchronised; on loss of synchronism transfer rises to 10 ms and the asynchronous transfer setting (delay, zero current or disabled) must suit the load type.
- In the fault-clearing study, compare the STS overload curve (for example 220% for 1 minute on STS 400) with the trip times of downstream breakers.
- Add the loss from 99.5% efficiency to the heat load: at 400 A and 400 V, about 277 kVA of throughput gives a loss of around 1.4 kVA.
- Use the cabinet dimensions and 4-pole weights in the layout, and leave front access space for the maintenance bypass.
Who should read it
Electrical engineers designing 2N and distributed-redundant power architectures and designers working on selectivity and earthing studies.
Document contents
- Principles of Working
- Features
- Control Panel
- Interfaces
- Technical table: STS 100, STS 150, STS 200
- Technical table: STS 250, STS 300, STS 400
- Technical table: STS 600
Publication details
- Authors
- ELIT
- Publisher
- ELIT
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ELIT ELITUPS three-phase static transfer switch STS series, Rev.0. ELIT. https://www.elit-ups.com/wp-content/uploads/2018/04/ELITUPS-Sistemi-di-trasferimento-trifase-serie-STS-inglese.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.